ENGLISH Warnings / Alarms 130 131 132 133 134 135 136 STD. SENSOR WARNINGS HIGH TEMPERATURE LOW TEMPERATURE HIGH HUMIDITY LOW HUMIDITY 28 C 17 C 65 %rH 22 %rH Help on: STD. SENSOR WARNINGS These Warnings are generated from the Standard Return Sensor of each Unit, if the thresholds are over- / underridden. The Warnings are delayed for a time of 30 Minutes after Unit start. 150 USER INPUT 1,2 151 152 USER INPUT 1 153 USER INPUT 2 154 155 156 140 141 142 143 144 145 146 EEAP WARNINGS HIGH TEMPERATURE LOW TEMPERATURE HIGH HUMIDITY LOW HUMIDITY EEAP CONNECTED Help on: EEAP WARNINGS These Warnings are generated from the optional EEAP Sensor, if the thresholds are over- / underridden. The Warnings are delayed for a time of 30 Minutes after Unit start. Para 146 shows if EEAP is connected. WARNING ALARM Help on: USER INPUT 1,2 1/4 According to the value set for this parameter (both inputs have the same selection possibilities) Microface will take some actions when the switch connected to the corresponding input of Microface is open : Help on: USER INPUT 1,2 3/4 2nd Setpoint' :the reference value for Return Air Temperature regulation switches to Temp.Setpoint 2 No Power' :everything is stopped except Fans and Freecooling function Help on: USER INPUT 1,2 2/4 nHumi' :the humidification is disabled nComp' :the compressor(s) disabled WARNING' :a Warning is generated (the unit continue its operations) ALARM' :an alarm is generated (the unit stops its operations) Help on: USER INPUT 1,2 4/4 Not Used' : Microface will not take any action on User Input opening. LSI' : self-setting on UI2 when a STD. Internal Humidifier is selected. 51 32 C 12 C 85 % rH 10 % rH YES User Manual Microface E & Hiromatic G/E 18.01.2002 51