Download 4 - E-THERM as

Transcript
User Manual
3200 Series
9.1
Input/Output Parameters
9.1.1
Input/Output 1 List (IO-1)
May be configured as relay, logic or DC output or to accept a digital input from external switch contacts. Connections are
made to terminals 1A and 1B. OP1 beacon is operated from the IO-1 channel when it is configured as an output.
INPUT/OUTPUT LIST 1 ‘ I O -1 ’
Name
1. i d
1. FUNC
Scrolling Display
I/O 1 TYPE
I/O 1 FUNCTION
Parameter Description
I/O channel 1 hardware
type defined by the
hardware fitted
I/O channel function.
If the instrument is
ordered as valve
positioner (codes VC or
VP), only options available
are , none, d.out, UP,
or dwn
Note: If output 1 is set
to Up ensure the other
valve position output is
set to dwn and vice
versa
1.SRC.A
I/O 1 SOURCE A
1.SRC.B
I/O 1 SOURCE B
1.SRC.C
I/O 1 SOURCE C
1.SRC.D
I/O 1 SOURCE D
1 . D . IN
44
DIGITAL INPUT
FUNCTION
These parameters only
appear when the channel
function is a Digital
output,
i.e. 1.FUNC = d.out
Value
Default
none
No input or output fitted
dC.OP
DC output - non-isolated (see note 1)
ReLy
Relay output
L.IO
Logic Input/Output
SSR
Triac output
none
Disabled. If disabled no further
parameters are shown
d.out
Digital output
UP
Valve open codes VC and VP only
dwn
Valve close codes VC and VP only
Heat
Heat output
CooL
Cool output
d.in
Digital input if ‘1. i d ’ = ‘L.IO’
w.SP
Working setpoint re-transmission
PV
Process variable re-transmission
OP
Output power demand retransmission
none
No event connected to the output
AL1
Alarm 1
AL2
Alarm 2
AL3
Alarm 3
AL4
Alarm4
Selects an event status to
be connected to the
output channel.
ALL.A
All alarms
nw.AL
Any new alarm
Ct.AL
CT alarm, load, leak & overcurrent
The output status is the
result of an OR of Src A,
Src B, Src C, and Src D
Lbr
Loop break alarm
Sbr
Sensor break alarm
t.End
Timer end status
Up to four events can,
therefore, operate the
output
t.run
Timer run status
mAn
Manual status
rmt.F
Remote fail - see section 9.1.2
See section 9.1.4
Pwr.f
Power fail
prg.e
Programmer event. See also section
13.2.3
This parameter is only
applicable to I/O 1 and
only appears if the
channel function is a
Digital IP
none
Input not used
Ac.AL
Alarm acknowledge
SP2
Setpoint 2 select
Loc.b
Front keypad disable (keylock)
i.e. 1.FUNC = d.in
t.res
Timer/programmer reset
Only one function may be
activated by a physical
input
t.run
Timer/programmer run
t.rrS
Timer/programmer run/reset. Make
to run, break to reset
t.HLd
Timer/programmer hold
Man
Manual status
Sby
Standby mode. In this mode control
outputs go to zero demand
rmt
Remote digital setpoint select
rec
Recipe select through IO1 digital input
UP
Remote key ‘Up’
dwn
Remote key ‘Down’
Access Level
As
ordered
Read only
HEAt
Conf
Shown if I/O 1 TYPE =
dc.OP Retransmission
none
Conf
Ac.AL
Conf
Part No HA028651
Issue 13.0
Apr-14