Transcript
User Manual 3200 Series 9.1 Input/Output Parameters 9.1.1 Input/Output 1 List (IO-1) May be configured as relay, logic or DC output or to accept a digital input from external switch contacts. Connections are made to terminals 1A and 1B. OP1 beacon is operated from the IO-1 channel when it is configured as an output. INPUT/OUTPUT LIST 1 ‘ I O -1 ’ Name 1. i d 1. FUNC Scrolling Display I/O 1 TYPE I/O 1 FUNCTION Parameter Description I/O channel 1 hardware type defined by the hardware fitted I/O channel function. If the instrument is ordered as valve positioner (codes VC or VP), only options available are , none, d.out, UP, or dwn Note: If output 1 is set to Up ensure the other valve position output is set to dwn and vice versa 1.SRC.A I/O 1 SOURCE A 1.SRC.B I/O 1 SOURCE B 1.SRC.C I/O 1 SOURCE C 1.SRC.D I/O 1 SOURCE D 1 . D . IN 44 DIGITAL INPUT FUNCTION These parameters only appear when the channel function is a Digital output, i.e. 1.FUNC = d.out Value Default none No input or output fitted dC.OP DC output - non-isolated (see note 1) ReLy Relay output L.IO Logic Input/Output SSR Triac output none Disabled. If disabled no further parameters are shown d.out Digital output UP Valve open codes VC and VP only dwn Valve close codes VC and VP only Heat Heat output CooL Cool output d.in Digital input if ‘1. i d ’ = ‘L.IO’ w.SP Working setpoint re-transmission PV Process variable re-transmission OP Output power demand retransmission none No event connected to the output AL1 Alarm 1 AL2 Alarm 2 AL3 Alarm 3 AL4 Alarm4 Selects an event status to be connected to the output channel. ALL.A All alarms nw.AL Any new alarm Ct.AL CT alarm, load, leak & overcurrent The output status is the result of an OR of Src A, Src B, Src C, and Src D Lbr Loop break alarm Sbr Sensor break alarm t.End Timer end status Up to four events can, therefore, operate the output t.run Timer run status mAn Manual status rmt.F Remote fail - see section 9.1.2 See section 9.1.4 Pwr.f Power fail prg.e Programmer event. See also section 13.2.3 This parameter is only applicable to I/O 1 and only appears if the channel function is a Digital IP none Input not used Ac.AL Alarm acknowledge SP2 Setpoint 2 select Loc.b Front keypad disable (keylock) i.e. 1.FUNC = d.in t.res Timer/programmer reset Only one function may be activated by a physical input t.run Timer/programmer run t.rrS Timer/programmer run/reset. Make to run, break to reset t.HLd Timer/programmer hold Man Manual status Sby Standby mode. In this mode control outputs go to zero demand rmt Remote digital setpoint select rec Recipe select through IO1 digital input UP Remote key ‘Up’ dwn Remote key ‘Down’ Access Level As ordered Read only HEAt Conf Shown if I/O 1 TYPE = dc.OP Retransmission none Conf Ac.AL Conf Part No HA028651 Issue 13.0 Apr-14