Liebert® iCOM® Control—Firmware Version XP1.00.010.STD
Figure 55 Set Alarms screen, page 1 of 7
SET ALARMS (page 1 of 7)
S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211
UNIT 01
PASSWORD (Actual Level 0)
High Room Air Temperature
Low Room Air Temperature
High Room Dewpoint
High Refrigerant Temperature
????
88.0°F
55.0°F
65.0°F
80.0°F
High Chilled Water Temperature
60.0°F
for next/previous unit
to change parameter
then
to select parameter
to confirm
High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The
range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F
(26.7°C).
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range
for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the
high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold for a high a refrigerant temperature alarm.
The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the
default is 80°F (26.7°C).
High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high
chilled water temperature alarm. The range for the high supply fluid temperature alarm is from 33.8
to 95°F (1 to 35°C); the default is 60°F (15.6°C).