Download WatchDog 1108 Manual
Transcript
Chapter 7: Operation III. Dial-out Begins Variable Factors • The dial-out process is activated as soon as the Call Delay time expires (if the alarm has not been cancelled at the Model 1108’s installation site.) The dial-out begins with telephone number 1 and proceeds sequentially, through the remaining telephone numbers. Call Delay: Expired • If the alarm is not acknowledged with the first dial-out telephone call, the Model 1108 waits the duration of Intercall Time before dialing the next telephone number. Intercall Time is the programmed waiting period in between each dial-out telephone call. Intercall Time: Activated • When the telephone is answered, the programmed Voice Repetitions determine the number of times per call the Model 1108 recites the alarm message. Voice Repetitions: Activated • Call Progress, an automatic feature, enables the Model 1108 to detect whether or not the telephone call is answered. After 8 rings, or if a busy signal is encountered, the Model 1108 will hang up, wait the programmed Intercall Time, and proceed to dial the next telephone number. Call Progress: Activated • If no telephone calls are answered, the Model 1108 dials out sequentially, through the remaining telephone numbers and continues to cycle until the programmed Maximum Number of Calls is reached. Max Calls: Activated • When the telephone is answered, the Model 1108 will immediately begin reciting a message that indicates which of the inputs is in alarm. At the same time, the alarm message is repeating at the Model 1108’s installation site. The Model 1108 will request acknowledgment, if it has not yet occurred. Alarm Messages: By Telephone and On site 89