PowerLogic® Circuit Monitor Series 4000 Reference Manual
Appendix C—Abbreviated Register Listing
ABBREVIATED REGISTER LISTING
63230-300-212B1
12/2005
Table C–3 contains an abbreviated register list for the circuit monitor.
Table C–3: Abbreviated Register List
Reg
Name
Size
Type
Access
NV
Scale
Units
Range
Notes
100 ms Metering—Current
1000
Current, Phase A
1
Integer
RO
N
A
Amperes/Scale
0 – 32,767
1001
Current, Phase B
1
Integer
RO
N
A
Amperes/Scale
0 – 32,767
RMS
RMS
1002
Current, Phase C
1
Integer
RO
N
A
Amperes/Scale
0 – 32,767
RMS
1003
Current, Neutral
1
Integer
RO
N
B
Amperes/Scale
0 – 32,767
(-32,768 if N/A)
RMS
4-wire system only
1004
Current, Ground
1
Integer
RO
N
C
Amperes/Scale
0 – 32,767
(-32,768 if N/A)
RMS
4-wire system only
1005
Current, 3-Phase
Average
1
Integer
RO
N
A
Amperes/Scale
0 – 32,767
Calculated mean of Phases A, B & C
1006
Current,
Apparent RMS
1
Integer
RO
N
A
Amperes/Scale
0 – 32,767
Peak instantaneous current of Phase
A, B or C divided by √2
100 ms Metering—Voltage
1020
Voltage, A-B
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
Fundamental RMS Voltage measured
between A & B
1021
Voltage, B-C
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
Fundamental RMS Voltage measured
between B & C
1022
Voltage, C-A
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
Fundamental RMS Voltage measured
between C & A
1023
Voltage, L-L
Average
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
Fundamental RMS 3 Phase Average
L-L Voltage
1024
Voltage, A-N
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
(-32,768 if N/A)
Fundamental RMS Voltage measured
between A & N
4-wire system only
1025
Voltage, B-N
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
(-32,768 if N/A)
Fundamental RMS Voltage measured
between B & N
4-wire system only
1026
Voltage, C-N
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
(-32,768 if N/A)
Fundamental RMS Voltage measured
between C & N
4-wire system only
1027
Voltage, N-G
1
Integer
RO
N
E
Volts/Scale
0 – 32,767
(-32,768 if N/A)
Fundamental RMS Voltage measured
between N & G
4-wire system with 4 element
metering only
1028
Voltage, L-N
Average
1
Integer
RO
N
D
Volts/Scale
0 – 32,767
(-32,768 if N/A)
Fundamental RMS 3-Phase Average
L-N Voltage
4-wire system only
100 ms Metering—Power
1040
Real Power,
Phase A
1
Integer
RO
N
F
kW/Scale
-32,767 – 32,767
(-32,768 if N/A)
Real Power (PA)
4-wire system only
1041
Real Power,
Phase B
1
Integer
RO
N
F
kW/Scale
-32,767 – 32,767
(-32,768 if N/A)
Real Power (PB)
4-wire system only
1042
Real Power,
Phase C
1
Integer
RO
N
F
kW/Scale
-32,767 – 32,767
(-32,768 if N/A)
Real Power (PC)
4-wire system only
1043
Real Power, Total
1
Integer
RO
N
F
kW/Scale
-32,767 – 32,767
4-wire system = PA+PB+PC
3 wire system = 3-Phase real power
1044
Reactive Power,
Phase A
1
Integer
RO
N
F
kVAr/Scale
-32,767 – 32,767
(-32,768 if N/A)
Reactive Power (QA)
4-wire system only
1045
Reactive Power,
Phase B
1
Integer
RO
N
F
kVAr/Scale
-32,767 – 32,767
(-32,768 if N/A)
Reactive Power (QB)
4-wire system only
RO = Read only.
R/CW = Read configure writeable if in a setup session.
NV = Nonvolatile.
➀See “How Power Factor is Stored in the Register” on page 178.
➁See “How Date and Time Are Stored in Registers” on page 178.
180