PowerLogic® Circuit Monitor Series 4000 Reference Manual
Appendix C—Abbreviated Register Listing
63230-300-212B1
12/2005
Table C–3: Abbreviated Register List (continued)
Reg
1164
1165
1166
Name
Alternate True
Power Factor,
Phase A
Alternate True
Power Factor,
Phase B
Alternate True
Power Factor,
Phase C
Size
1
1
1
Type
Integer
Integer
Integer
Access
RO
RO
RO
NV
N
N
N
Scale
xx
xx
xx
Units
0.001
0.001
0.001
Range
Notes
0 – 2,000
(-32,768 if N/A)
Derived using the complete harmonic
content of real and apparent power (4wire system only). Reported value is
mapped from 0-2000, with 1000
representing unity, values below 1000
representing lagging, and values
above 1000 representing leading.
0 – 2,000
(-32,768 if N/A)
Derived using the complete harmonic
content of real and apparent power (4wire system only). Reported value is
mapped from 0-2000, with 1000
representing unity, values below 1000
representing lagging, and values
above 1000 representing leading.
0 – 2,000
(-32,768 if N/A)
Derived using the complete harmonic
content of real and apparent power (4wire system only). Reported value is
mapped from 0-2000, with 1000
representing unity, values below 1000
representing lagging, and values
above 1000 representing leading.
Derived using the complete harmonic
content of real and apparent power.
Reported value is mapped from 02000, with 1000 representing unity,
values below 1000 representing
lagging, and values above 1000
representing leading.
1167
Alternate True
Power Factor,
Total
1
Integer
RO
N
xx
0.001
0 – 2,000
1168
Displacement
Power Factor,
Phase A
1
Integer
RO
N
xx
0.001
1,000
-100 to 100
(-32,768 if N/A) ➀
Derived using only fundamental
frequency of the real and apparent
power.
4-wire system only
1169
Displacement
Power Factor,
Phase B
1
Integer
RO
N
xx
0.001
1,000
-100 to 100
(-32,768 if N/A) ➀
Derived using only fundamental
frequency of the real and apparent
power.
4-wire system only
1170
Displacement
Power Factor,
Phase C
1
Integer
RO
N
xx
0.001
1,000
-100 to 100
(-32,768 if N/A) ➀
Derived using only fundamental
frequency of the real and apparent
power.
4-wire system only
1171
Displacement
Power Factor,
Total
1
Integer
RO
N
xx
0.001
1,000
-100 to 100 ➀
Derived using only fundamental
frequency of the real and apparent
power
1172
Alternate
Displacement
Power Factor,
Phase A
0 – 2,000
(-32,768 if N/A)
Derived using only fundamental
frequency of the real and apparent
power (4-wire system only). Reported
value is mapped from 0-2000, with
1000 representing unity, values below
1000 representing lagging, and values
above 1000 representing leading.
1173
Alternate
Displacement
Power Factor,
Phase B
0 – 2,000
(-32,768 if N/A)
Derived using only fundamental
frequency of the real and apparent
power (4-wire system only). Reported
value is mapped from 0-2000, with
1000 representing unity, values below
1000 representing lagging, and values
above 1000 representing leading.
1174
Alternate
Displacement
Power Factor,
Phase C
0 – 2,000
(-32,768 if N/A)
Derived using only fundamental
frequency of the real and apparent
power (4-wire system only). Reported
value is mapped from 0-2000, with
1000 representing unity, values below
1000 representing lagging, and values
above 1000 representing leading.
1
1
1
Integer
Integer
Integer
RO
RO
RO
N
N
N
xx
xx
xx
0.001
0.001
0.001
RO = Read only.
R/CW = Read configure writeable if in a setup session.
NV = Nonvolatile.
➀See “How Power Factor is Stored in the Register” on page 178.
➁See “How Date and Time Are Stored in Registers” on page 178.
184
© 2005 Schneider Electric All Rights Reserved