Download SuperStack II Switch 3900 Getting Started Guide
Transcript
Distribution Rack Requirements Figure 15 Recommended Service Access ■ 51 In countries other than the United States, comply with IEC Standard 297: Dimensions of Panels and Racks. In addition, 3Com recommends that your distribution racks meet these requirements: ■ Use an open style, 19-inch rack. The rack styles shown in Figure 16 facilitate easy maintenance and provide excellent ventilation. ■ Use a rack that has the universal mounting rail hole pattern identified in IEC Standard 297. See Figure 7 for a description of the universal mounting hole pattern. ■ Use a rack that is made of steel. ■ Install equipment in the lower half of the distribution rack to avoid making it top heavy. ■ Use a rack that supports approximately 272 kg (600 lb) ■ Use a rack that has adequate electrical grounding, for instance, with a distribution rack grounding kit. ■ Verify that the floor under the rack is level within 5 mm ( 3/16 in.). Use a floor-leveling cement compound or bolt the racks to the floor. ■ Attach the rack to the wiring closet floor with 9.5 mm ( 3/8 in.) lag screws or equivalent hardware. ■ Brace open distribution racks if the channel thickness is less than 6.4 mm ( 1/4 in.). 76 cm (30 in.) 76 cm (30 in.) Mechanical Requirements for the Rack Verify that your racks comply with the standards and requirements in your cabling system plan and conform to these conventional standards: ■ In the United States, comply with EIA Standard RS-310C: Racks, Panels, and Associated Equipment.