Download Ultrasonic Flowmeter Model UFP-10
Transcript
Display (9) CAL ZERO Explanation CORRECTION 1 1:0.00 % Input the zero correction value. Zero correction sets the offset value at some percent of the maximum flow rate. Input the value here. The input range is -20.00 ? 20.00. Input Operation Press [? ] to move the cursor right. Press [? ] to backspace. Press number keys to input a number. Press [CLR ] to clear the display. Press [ENT] to set. #01 FILE 01 CAL SPAN CORRECTION 1 1:1.000 #01 FILE (10) Input the span correction value. The span correction is the coefficient that is multiplied by the calculated flow rate. The flow rate is displayed as the value after the coefficient has been multiplied. Press [? ] to move the cursor right. Press [? ] to backspace. Press number keys to input a number. The input range is Press [CLR ] to clear the display. 0.500 ? 2.000. Press [ENT] to set. 01 (11) Input the zero cut value. CAL The zero cut is the boundary value to output 0 when the flow rate falls below a set level. The maximum flow rate is expressed as a percentage. ZERO CUT 1 1:0.00 % The input range is 0.00 ?10.00. Press [? ] to move the cursor right. Press [? ] to backspace. Press number keys to input a number. Press [CLR ] to clear the display. Press [ENT] to set. #01 FILE 01 4 – 34