9.3 Grant Hybrid System
This vertical option allows the use of
an existing chimney using part of the
'Green' system and the flexible liner and
terminal of the Grant 'Orange' system.
See Figure 9-3. This is only available for
boilers up to 46 kW.
If an existing chimney is to be used,
it must be lined with a smooth bore
stainless steel liner suitable for use with
oil fired condensing boilers. The top and
bottom of the annular space must be
sealed.
Grant recommends the use of the
Grant ‘Orange’ flue system, specifically
designed for the VORTEX range of
condensing boilers.
The internal flue and liner diameter for all
models up to 46 kW output must be 100
mm (4 in).
The maximum vertical height (from the
top of the boiler to the terminal) for the
‘Orange’ system is 19 metres.
! NOTE
The Grant Orange system flexible
stainless steel liner is directional. The
arrows marked on the liner MUST be
pointing vertically upwards, following
the direction of the flue gases. Failure to
comply with this instruction could lead
to a leakage of condensate from the flue
liner.
Flaunching
! NOTE
In order to correctly connect the Grant
hybrid system, it will be necessary to
purchase the Grant Starter Elbow.
This insulated Starter elbow includes
the boiler connector, complete with test
point, replacing the low level terminal
and flue guard supplied with the boiler.
Terminal
Clamp
Top plate
Brick chimney
Flexible stainless steel liner
Note: The flue liner is directional
Rigid to flexible flue connector
(supplied in Orange system kit)
Note: This component must be
installed vertically
45° Elbow
(Green system)
Twin-wall to single-wall adaptor
Flue extension (Green system)
Adjustable extension (Green system)
45° Elbow (Green system)
Flue extension (Green system)
Outdoor module
Flue System
Outdoor module Starter elbow
Figure 9-3: Vertical hybrid flue (Green to Orange system)