Download User manual
Transcript
BLCDN-4M12S-2AI2AO-VI 9 Mapping and diagnostics 9.1 I/O- and Diagnostic Data mapping INPUT BYTE Bit 7 Ch 0 0 1 2 3 AI 0 LSB AI 0 MSB AI 1 LSB AI 1 MSB Bit 3 Bit 2 Bit 1 Diag. 4 5 Module number reporting diagnostic data Replace N/A Diag. Reserved station active Hardware Reserved Failure AI Ch 0 6 Overflow / Underflow Reserved 7 Hardware Failure Reserved Overflow / Underflow Reserved AI Ch 1 8 Hardware Failure Reserved Overflow / Underflow Reserved AO Ch 3 9 Hardware Failure Reserved Overflow / Underflow Reserved Wire Break Measuring (4...20 mA Range range only) Exceeded Measuring Range Exceeded Wire Break Measuring (4...20 mA Range range only) Exceeded Measuring Range Exceeded AO Ch 2 OUTPUT BYTE Bit 7 Bit 6 Bit 3 Bit 2 Ch 2 0 1 2 3 AO 0 LSB AO 0 MSB AO 1 LSB AO 1 MSB Ch 1 Ch 3 Bit 6 Bit 5 Bit 5 Bit 4 Bit 4 Bit 1 Bit 0 Bit 0 9.2 xAIxAO – Diagnostic messages Edition • 2011-3-15 Diagnostic message Measuring Range Exceeded CH x Wire Break CH x Overflow / Underflow CH x Hardware Failure CH x 13 / 32011 Meaning The generation of this diagnostic message depends on the parameterised measurement range. A wire break diagnosis is only possible in the operation mode 4 to 20mA. The generation of this diagnostic message depends on the parameterised measurement range. Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ [email protected] ñ www.turck.com