Operation Seasonal start-up • Check water flows and interlocks. • Check Ethylene glycol concentration in the chilled water circuit if glycol presence is required • Check operational set points and performance • Calibrate controls • Check operation of all safety devices • Inspect contacts and tighten terminals • Megger the motor compressor windings • Record operating pressures, temperatures, amperages and voltage • Carry out leak test • Check configuration of unit control module • Change the oil as required based upon results of the oil analysis made during seasonal shutdown. Get the 8 condition measurements at the same time, on each circuit. • HP • LP • Suction temperature • Discharge temperature • Liquid temperature • Water entering temperature • Water leaving temperature • Outdoor ambient temperature Then calculate the sub-cooling and superheat. No diagnosis can be accurate with one of these records missing. • Check operation of machines/ compare conditions of operation against original commissioning data. • Fill out the visit log sheet and review with the operator CG-SVX06E-E4 51