Download CD3000E-2PH Thyristor Unit
Transcript
CD Automation srl P112 (H70) Function: Value: Digital output configuration (terminal 16) This parameter selects the function of the digital output. 0 = Thyristor Failure 1 = Heater Break Alarm (HB) 2 = Unbalanced Load 3 = Current limit active 1 R/W Digital output configuration (terminal 11 and 12) This parameter selects the function of the digital output. 0 = Thyristor Failure 1 = Heater Break Alarm (HB) 2 = Unbalanced Load 3 = Low voltage 0 Not available for size S09/S10 R/W Baud Rate This parameter selects the Baud rate on the serial port. 0 = 4800 1 = 9600 2 = 19200 2 R/W Address R/W This parameter selects the Address on the serial port for the thyristor unit. 1 ÷ 127 1 Default: Note: P114 (H72) Function: Value: Default: P115 (H73) Function: Min/Max: Default: User’s Manual Default: P113 (H71) Function: Value: CD3000E-2PH from 25A to 700A 51