Download ignis 1520m automatic fire extinguishing system controller
Transcript
18 ID‐E294‐011GB where: - 0’ 23 – current time left until the extinguishing agent is released (counted in seconds), Discharge state (fire extinguishing stage) EXTINGUISH‐00 ’ 04 where: - 00’ 04 – counted in seconds the extinguishing agent discharge time (control impulse time, in sequence from the P6, P7 and P8 relays, when the extinguishing agent additional reserve is activated). 5.4.1.3 External alarm devices disablement/re‐enablement ALARM DEV. ON ALARM DEV. OFF 5.4.1.4 Alarm signal transmission disablement/re‐enablement TRANSMISSION ON TRANSMISSION OFF 5.4.1.5 Control panel operation mode information: manual control or automatic and manual control CONTROL MANUAL CONTROL AUTO/MAN 5.4.1.6 Fire alarm reset RESET 5.4.1.7 Testing or disablement TEST or DISABL. This information is displayed: - when the ZW10 jumper (item 2‐3) has been switched to the monitoring and controlling lines testing mode, - at an attempt of fire extinguishing manual activation with the control panel open door. 5.4.1.8 EXTINGUISHING STOP line fault FAULT STOP LINE Information displayed at an attempt of fire extinguishing activation with the EXTINGUISHING START push button when the EXTINGUISHING STOP push buttons line is in a fault mode.