Download 1732E-UM004 - Rockwell Automation
Transcript
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules 1732E-IR4IM12R – Produced Data Structure for RTD Input Configuration Bit 7 Byte Bit 6 Bit 5 0…3 Reserved (must be zero) 4…5 Channel 0 Data 6…7 Channel 1 Data 8…9 Channel 2 Data 10…11 Channel 3 Data 12 Channel 0 Status(1) 13 Channel 1 Status(1) 14 Channel 2 Status(1) 15 Channel 3 Status(1) Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 (1) This parameter is in Byte and has the following structure: Bit 0 = Fault; Bit 1 = Calibration; Bit 2 = Low Alarm; Bit 3 = High Alarm; Bit 4 = Low Low Alarm; Bit 5 = High High Alarm; Bit 6 = Underrange; Bit 7 = Overrange Chapter Summary 44 This chapter discussed the different configurable features and their effect on all input channels for both Thermocouple and RTD modules. Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012