Download User Manual, M-Max Series Adjustable Frequency Drive
Transcript
Installation Digital Outputs (Relays) The following figure shows the arrangement of the connection terminals for both relay contacts. 24 R24 I 26 Error 25 R22 23 R21 R14 22 Run R13 Relay Outputs with Connection Examples, Control Relay with Suppressor Circuit 250V ~ : 2A 250V: 0.4A (-) (+) Varistor AC DC AC The two relay outputs (control signal terminals 22 to 26) enable the frequency inverter to generate galvanically isolated feedback signals in control circuits with other potentials: ● maximum switching capacity: 250 Vdc, 0.4A (DC voltage), ● maximum switching capacity: 250 Vac, 2A (AC voltage). With voltages greater than 48V, you should fasten the connection cables of the relay in the opening on the right (housing). Fixed Connection Cables at U >48V (Relay) 44 RC Filter AC Diode DC The functions for which parameters can be defined are described in “Digital Outputs (P5)” on Page 78. The factory setting causes N/O contact R13/R14 (control signal terminal 22/23) of relay RO1 to indicate operation (RUN). N/O contact R21/R24 (control signal terminal 25/26) of relay RO2 indicates a detected fault (ERROR = FAULT). If the supply voltage of the frequency inverter is switched off upon the occurrence of an error message, the N/O R21/R24 opens again (relay drops out). The functions for which parameters can be defined for both relays RO1 and RO2 are described in “Digital Outputs (P5)” on Page 78. M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com