Download STC-DAIKIN A/C - REM
Transcript
3. Configuration The STC-DAIKIN A/C (Figure 3.1) has two switches, a button and a profile selector to execute the Learning and Teach-in procedures from the EnOcean technology (explained in Table 3.1 and the following sections) CON1 LEDO PB1: Button LEDM 1 MOD1: EnOcean module enocean ® <- TEACH / LEARN -> <- NORMAL / ERASE -> ROT1: Profile selector ON 2 SWITCH1: switches - 1 SW1-1 - 2 SW1-2 0 1 EF 2 D 3 C 4 B 5 A 6 9 8 7 PB1 ROT1 PROFILES MOD1 SWITCH1 (SW1) CON1: AC connector LEDM: AC LED Intesis software IS1-AC-ENO-1-v11-REV0 Antenna LEDO: EnOcean LED Figure 3.1 Device diagram The switches in SW1 configure the behavior of the interface. The different working modes are explained in Table 3.1. Mode Normal operation Teach-in Switch 1 (SW1-1) Off Switch 2 (SW1-2) Off EnOcean LED state Off Off On Off On On Off On On Flashing: 100 ms On / 100 ms Off / EnOcean transmission disabled. Only allows Teach-in Learning Erase Button PB1 function Send a Teach-in telegram or activate monitor mode (pressing it during 5 seconds) Send a Teach-in telegram or activate monitor mode (pressing it during 5 seconds) No function Delete the devices in the selected profile (pressing it during 5 seconds) Table 3.1 Interface working modes. Selector ROT1 it is used to select the desired profile. The transmission profile is used when the device is in Teach-in mode and the reception one when in Learning or erase mode. Thermokon Sensortechnik GmbH - Aarstrasse 6 - 35756 Mittenaar - Tel.: 02772/65010 - Fax: 02772/6501400 - www.thermokon.de - [email protected] produktblatt_stc_daikin_ac_eng ©2011 Page 9 of 30