4-3 Functions When PG Option Board (3G3AX-PG01) Is Used
Pulse Train Frequency Input
This function allows you to use a pulse train input to the SAP-SAN terminals as frequency reference
or PID feedback value in each control mode.
(This function can be used in all control modes.)
Set the input frequency at the maximum frequency in pulse train frequency scale P055.
The analog input start/end function cannot be used. To limit the input frequency, use pulse train frequency bias amount P057 and pulse train frequency limit P058.
Function name
Data
Default setting
Unit
P055
Pulse train frequency scale
1.0 to 50.0: Set the input frequency at the
maximum frequency.
25.0
kHz
P056
Pulse train frequency filter
time constant
0.01 to 2.00: Set a filter time constant for
pulse train input.
0.10
s
P057
Pulse train frequency bias
amount
-100 to 100
0
%
P058
Pulse train frequency limit
0 to 100
100
%
A001
Frequency reference
selection
06: Pulse train frequency
01
A076
PID feedback selection
03: Pulse (Pulse train frequency)
00
A141
Operation frequency input
A setting
07: Pulse (Pulse train frequency)
02
A142
Operation frequency input
B setting
07: Pulse (Pulse train frequency)
03

Pulse train frequency processing block
Bias/Limit
Limit
Frequency
measurement
Hz
%
%
1
1+sT
Hz
Frequency
reference
Bias
Frequency scale (P055)
(1.0 to 50.0 kHz)
First-order lag filter (P056)
Maximum
frequency
(A004)
Note: The SWENC switch on PG Board is available for "OFF: encoder disconnection detection disabled".
4-144
4
Functions
Parameter No.