Download User`s manual MicroFlex e150 servo drive
Transcript
30 Mechanical installation Effects of mounting surface and proximity Warm 1 mm 15 If the MicroFlex e150 is mounted above or below another MicroFlex e150 (or other obstruction), there should be a minimum space of 90 mm (3.5 in) to maintain effective cooling. Remember that a MicroFlex e150 will be receiving air that has been already heated if it is mounted above another MicroFlex e150 or heat source. Multiple MicroFlex e150 units mounted above each other should be aligned, not offset, to promote air flow across the heat sinks. 90 mm 15 mm 1 Forced air flow It is recommended to allow approximately 60 mm (2.4 in) at the front to accommodate wiring and connectors. Hot Metal backplane Cool The proximity of the MicroFlex e150 to other components could affect cooling efficiency. If the MicroFlex e150 is mounted beside another MicroFlex e150 (or other obstruction), there should be a minimum space of 15 mm (0.6 in) to maintain effective cooling. Fan Fan