Properties of Simulator Objects
Transformer AVR Dialog
The Transformer AVR Dialog is used to view the control parameters associated with load-tapchanging (LTC) transformers when they are used to control bus voltage magnitudes. To view
this display, click the Automatic Control Options button on the Line/Transformer Information
Dialog.
This dialog has the following fields:
Automatic Control Type
This section is only visible on the dialog in edit mode. The control type of the transformer
can be changed between no control, voltage regulation, reactive power control, or phase
shifter control.
Regulated Bus Number
The number of the bus whose voltage is regulated by the control.
Present Regulated Bus Voltage
The present voltage of the regulated bus.
Voltage Error
If the regulated bus' voltage falls outside the regulating range of the transformer (as defined
by the Minimum Voltage and Maximum Voltage fields), the Voltage Error field indicates by
how much the voltage deviates from the control range.
Regulation Minimum Voltage
The minimum acceptable voltage at the regulated bus.
Regulation Maximum Voltage
The maximum acceptable voltage at the regulated bus.
Regulation Target Type
As long as the regulated voltage is inside the regulation minimum and maximum, then the
transformer will not change its tap ratio. When the regulated voltage moves outside of this
regulation range, then Simulator will calculate a new tap ratio in an attempt to bring the
regulated voltage back inside of its range. The Regulation Target Type determines what
value is used as a target when calculating this change in tap ratio. Middle is the default and
means that the target is the average of the regulation minimum and maximum regardless of
whether the voltage is high or low. Max/Min means that the regulation maximum is used
as the target when the regulated voltage is above the maximum, and regulation minimum is
used as the target value when the regulated voltage is below the minimum.
Present Tap Ratio
The tap ratio of the transformer for the current system state.
Minimum Tap Ratio, Maximum Tap Ratio
Minimum and maximum allowable off-nominal tap ratios for the LTC transformer. Typical
values are 0.9 and 1.1.
Tap Step Size
Transformer off-nominal turns ratio increment. The off-nominal turns ratio is either
incremented or decremented from 1.0 in integer multiples of this value. Default value is
0.00625.