Download vacon 100 ethernet/ip user manual
Transcript
vacon • 46 Communications In the Vacon 100 drive, when the following values are set to the Motor Control Mode Object “ControlMode” and “FeedbackMode” attributes, the AC/DC Drive Object “DriveMode” attribute is set as follows: Table 42. Set Motor control Mode Object values DriveMode value ControlMode Feedback Mode 0d (Frequency) 0d (Open loop) 1d (Open loop speed/frequency) 1d (Speed) 0d (Open loop) 1d (Open loop speed/frequency) 2d (Torque) 0d (Open loop) 3d (Torque control) 6.2.3.4 Fault History Object, class 0xA2 The Fault History Object is a vendor-specific object available in the Vacon 100 drive which allows access to the contents of the fault history over the EtherNet/IP network. Each entry in a fault history is represented by an instance of the Fault History Object. Low instance numbers correspond to the most recent fault entries. Table 43. Class Name Fault History Object Class Identifier A2h Class Attributess Id Name Data Type Access Rule 01h Revision Unsigned8 Read-only 02h Max instance Unsigned8 Read-only 03h Number of Instances Unsigned8 Read-only Id Name 01h Get_Attributes_All 05h Reset 0Eh Get_Attribute_Single Class Services Instance Attributess Id Instance Services 6 Name 01h FaultCode Unsigned8 Read-only 02h FaultID Unsigned16 Read-only 03h FaultYear Unsigned16 Read-only 04h FaultMonth Unsigned8 Read-only 05h FaultDay Unsigned8 Read-only 06h FaultMillisAfterMidnight Unsigned32 Read-only Id Name 01h Get_Attributes_All 0Eh Get_Attribute_Single Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205