User Manual DC/DC Module PM3K350-1x Operation 5.1.8 Empty DC Link If the module is switched on with an empty DC link and a voltage is connected to the VS side, so firstly it takes place a precharging of the DC link by pre-charging PTC resistors. If the precharging is successful, the main relais is switched on and the converter is startet with a reduced current of 1A. Is the DC link charged and the desired DC link voltage is reached, this limitation is cancelled. If the precharging of the DC link is not successful, because the PTC resistors overheat due to large capacities or a load at the DC link, the module switches off with an error after 10s. The error is “U_ZK too low”. 5.2 Basic Parameterization The module can only be parameterized by means of the serial interface. It is, however, more convenient to do this by means of the software belonging to it. 5.2.1 R readable W writable (parameterizable) E stored in the EEPROM (EEP) B can be changed in switched-on state (mod_on=1) Currents: variable voltage Side (VS side) Type of module 350V2 Scalings Communication Range of values values -10…10A -1000…1000 Resolution 10mA parameter description explanation instruction vs_imin current, minimum minimum of the desired current RW B wj parameter description explanation instruction vs_imax current, maximum minimum of the desired current RW B wi parameter description explanation vs_imin_f current, minimum, initial value in EEPROM vs_imin receives this value directly after initial operation of the module through connection of the operation voltage RW E wl instruction Flexiva automation & Robotik GmbH Weißbacher Straße 3 D – 09439 Amtsberg 25