fAUlt
f indinG
f INDING
78F l ame L o ss
If the boiler is Reset, does the boiler Ignite for a
short time and then Extinguish
Yes
No
Check the Detection Electrode and associated Harness for
continuity, visual condition and position (refer to Frame 64).
Check if the Condensate Pipe is blocked. Check if the Flue
is blocked. Replace as necessary
No
f INDING f AULT
Is the Gas Pressure available at the boiler > 18 mbar?
Check Gas Supply and rectify fault
Yes
Is 215Vdc available at the Gas Valve during
ignition? (* See note)
No
Check wiring from Gas Valve to PCB and replace if
necessary, otherwise replace the main PCB
Yes
Check Spark Generator and associated Harness
for continuity, visual condition and position (refer to
Frame 65). Are these functioning correctly?
No
Replace Spark Generator and Harness
as necessary
No
Replace Ignition Electrode and
associated Harness as necessary
Check Ignition Electrode and associated Harness
for continuity, visual condition and position (refer to
Frame 58). Are these functioning correctly?
Yes
Check Syphon and condensate drain pipework
for blockage and rectify if necessary. Boiler now
working OK?
No
Replace Gas Valve
* Note: due to the wave form of the rectified voltage, the reading will vary depending on the type of meter used to measure
the value. In general terms a reading of greater than 150V indicates that the correct voltage is supplied to the gas
valve
79Th e rmal Fus e L o cko ut
Isolate the electrical supply to the boiler and system
Ensure that the electrical connection to the thermal
fuse is pushed fully home and that the 6 way connector
is properly connected to the primary PCB.
Press r, is the fault still present?
f INDING f AULT
f INDING f AULT
f INDING f AULT
Yes
Yes
Disconnect the 6 way connector to the thermal fuse.
Is there continuity across the black and yellow wires
in pins 1 and 2?
Yes
Replace the primary PCB
Yes
Replace the wiring from the PCB to the
thermal fuse
No
Disconnect the electrical connection to the thermal
fuse. Is there continuity across the fuse?
f AULT
No
Replace the heat exchanger