Download "user manual"

Transcript
PLC
(* Set CAN node number *)
TargetID := 50,
(* Select PDO (Standard for PDO2 setpoint4, setpoint5 SK540E) *)
PDO := 2,
(* Specify length of data (Standard for PDO2 is 4 *)
LENGTH := 4,
(* Transmit *)
Dir := 1);
(* Configure PDO *)
PDOConfig(
Execute := TRUE,
(* Configure Messagebox 2 *)
Number := 2,
(* Set CAN node number *)
TargetID := 50,
(* Select PDO (Standard for PDO1 status word, actual value1, actual value2, actual
value3) *)
PDO := 1,
(* Specify length of data (Standard for PDO1 is 8 *)
LENGTH := 8,
(* Receive *)
Dir := 0);
9.8.7.4 FB_PDOSend
With this FB, PDOs can be transmitted on a previously configured channel. This is possible either as a one-off or
cyclical transmission. The data to be transmitted is entered in WORD1 to WORD4. Transmission of the PDO is
possible regardless of the CANopen state of the frequency inverter. The previously configured PDO channel is
selected via NUMBER. The data to be transmitted is entered into WORD1 to WORD4. Via CYCLE one-off
transmission (setting = 0) or cyclical transmission can be selected. The PDO is sent with a positive flank on
EXECUTE. IF DONE = 1 all entries were correct and the PDO is sent. IF ERROR = 1 there was a problem. The
precise cause is saved in ERRORID. All outputs are reset with a negative flank on EXECUTE. The time base of the
PLC is 5ms; this also applies for the CYCLE input. Only transmission cycles with a multiple of 5ms can be
implemented.
VAR_INPUT
Input
Type
Output
Description
Type
EXECUTE Execute
BOOL
DONE
PDO transmitted = 1
BOOL
NUMBER
Messagebox number
Value range = 0 to 19
BYTE
ERROR
Error in FB
BOOL
CYCLE
Transmission cycle
BYTE
Value range = 0 to 255
0 = Disabled
1 to 255 = Transmission cycle
in ms
ERRORID
Error code
INT
WORD1
Transmission data Word 1
INT
WORD2
Transmission data Word 2
INT
WORD3
Transmission data Word 3
INT
WORD4
Transmission data Word 4
INT
BU 0000 GB
Description
VAR_OUTPUT
165