Download High -Performance AC Drive
Transcript
MD380 User Manual Function Code Function Code Table Setting Range Parameter Name Default Property 0 ☆ 0 ☆ 1000 ☆ 0: AI1 1: AI2 2: AI3 3: AI1 – AI2 FA-02 PID feedback source 4: Pulse setting (DI5) 5: Communication setting 6: AI1 + AI2 7: MAX (|AI1|, |AI2|) 8: MIN (|AI1|, |AI2|) 0: Forward action FA-03 PID action direction FA-04 PID setting feedback range 0–65535 FA-05 Proportional gain Kp1 0.0–100.0 20.0 ☆ FA-06 Integral time Ti1 0.01–10.00s 2.00s ☆ FA-07 Differential time Td1 0.00–10.000 0.000s ☆ FA-08 Cut-off frequency of PID reverse rotation 0.00 to maximum frequency 2.00 Hz ☆ FA-09 PID deviation limit 0.0%–100.0% 0.0% ☆ FA-10 PID differential limit 0.00%–100.00% 0.10% ☆ 1: Reverse action FA-11 PID setting change time 0.00–650.00s 0.00s ☆ FA-12 PID feedback filter time 0.00–60.00s 0.00s ☆ FA-13 PID output filter time 0.00–60.00s 0.00s ☆ FA-14 Reserved - - ☆ FA-15 Proportional gain Kp2 0.0–100.0 20.0 ☆ FA-16 Integral time Ti2 0.01–10.00s 2.00s ☆ FA-17 Differential time Td2 0.000–10.000s 0.000s ☆ FA-18 PID parameter switchover condition 0 ☆ FA-19 PID parameter switchover deviation 1 0.0% to FA-20 20.0% ☆ FA-20 PID parameter switchover deviation 2 FA-19 to 100.0% 80.0% ☆ FA-21 PID initial value 0.0%–100.0% 0.0% ☆ FA-22 PID initial value holding time 0.00–650.00s 0.00s ☆ FA-23 Maximum deviation between 0.00%–100.00% two PID outputs in forward direction 1.00% ☆ 0: No switchover 1: Switchover via DI 2: Automatic switchover based on deviation - 107 -