Download High -Performance AC Drive
Transcript
Description of Function Codes MD380 User Manual Figure 6-25 Diagram of the overcurrent stall protection function Output current Overcurrent stall protective current Time (t) Output frequency (Hz) Set frequency Time (t) Acceleration ConstantDeceleration process speed process process Function Code F9-07 Parameter Name Setting Range Short-circuit to ground upon poweron Default 0: Disabled 1 1: Enabled It is used to determine whether to check the motor is short-circuited to ground at power-on of the AC drive. If this function is enabled, the AC drive's UVW will have voltage output a while after power-on. Function Code Parameter Name Setting Range Default F9-09 Fault auto reset times 0–20 0 It is used to set the times of fault auto resets if this function is used. After the value is exceeded, the AC drive will remain in the fault state. Function Code F9-10 Parameter Name Setting Range DO action during fault auto reset 0: Not act 1: Act Default 0 It is used to decide whether the DO acts during the fault auto reset if the fault auto reset function is selected. Function Code Parameter Name Setting Range Default F9-11 Time interval of fault auto reset 0.1s–100.0s 1.0s It is used to set the waiting time from the alarm of the AC drive to fault auto reset. - 200 -