As your electrical demand approaches the demand limit, the Energy Sentry
demand controller sheds the “2nd Floor Exhaust Fan” first because it has a
load priority of 3, which, in this example, is the lowest load priority.
If your electrical demand continues to approach the demand limit, Energy
Sentry begins shedding loads with a priority of 2. Loads with equal
priority take turns being shed first.
Finally, if your electrical demand still continues to approach the demand
limit, Energy Sentry begins shedding loads with a priority of 1. In this
example, the “Basement Heat Pump” has a load priority of 1, so it is the
last load to be shed.
After your electrical demand is reduced, Energy Sentry begins restoring
the loads in the reverse order that they were shed. So the first load to be
restored is the “Basement Heat Pump” because it has a load priority of
1. Next, loads with priorities of 2 are restored. Finally the “2nd Floor
Exhaust Fan” load is restored.
 To edit a load priority
1 Make the Configuration window active.
To open the Configuration window, choose Upload Configuration
from the File or Controller menu.
2 Double click on one of the entries of the priority column in the load
information section of the configuration window.