Download Programming Manual, PowerFlex 700S AC Drive
Transcript
Programming and Parameters Chapter 2 2 3 4 5 6 Name Description Motor NP Volts Values Default: Calculated (1) Min/Max: 75/705 Units: V Set to the motor nameplate rated volts. Read-Write Data Type No. 1 Linkable Parameter Data in Linear List Format RW 16-bit Integer Default: Calculated (1) Motor NP FLA Set to the motor nameplate rated full load amps. Range limited by three-second inverter rating. Min/Max: Calculated/Calculated Units: A RW Real Motor NP Hertz Default: Calculated (1) Min/Max: 2.0000/500.0000 Units: Hz RW Real Motor NP RPM Default: Calculated (1) Min/Max: 1/30000 Units: rpm RW 16-bit Integer Set to the motor nameplate rated frequency. Set to the motor nameplate rated rpm. Default: Calculated (1) Motor NP Power Set to the motor nameplate rated power. Min/Max: 0.2500/3500.0000 Note: The unit of measure for this parameter was changed from kW to Hp for firmware version Units: Hp 2.003. Mtr NP Pwr Units The power units shown on the motor nameplate. RW 32-bit Integer Default: 0 = “Hp” Options: 0 = “Hp” 1 = “kW” 7 Default: 4 Motor Poles Set the number of motor poles indicated on the motor nameplate or manufacturer's motor data Min/Max: 2/128 sheet. Only even numbers of poles are allowed. Units: Pole Calculation: (120 * NP Hz) / NP rpm = Poles [round down] Note: The maximum value was changed from 60 to 128 for firmware version 4.002. 9 Total Inertia Default: 2.0000 Time, in seconds, for a motor coupled to a load to accelerate from zero to base speed, at rated Min/Max: 0.0100/655.0000 motor torque. Calculated during auto-tune. Units: s ✓ RW Real 10 Default: 0.0000 Speed Ref 1 Sets the speed reference that the drive should use when selected by Par 27 [Speed Ref A Sel] or Min/Max: -/+2200000000.0000 Par 28 [Speed Ref B Sel]. A value of 1.0 represents base speed of the motor. ✓ RW Real 11 Default: 1.0000 Spd Ref1 Divide Par 10 [Speed Ref 1] is divided by this number. This number can be used to scale the value of Par Min/Max: -/+2200000000.0000 10 [Speed Ref 1]. ✓ RW Real 12 Default: 0.0000 Speed Ref 2 Sets the speed reference that the drive should use when selected by Par 27 [Speed Ref A Sel] or Min/Max: -/+2200000000.0000 Par 28 [Speed Ref B Sel]. A value of 1.0 represents base speed of the motor. ✓ RW Real 13 Spd Ref2 Multi Default: 1.0000 Par 12 [Speed Ref 2] is multiplied by this number. This number can be used to scale the value of Min/Max: -/+2200000000.0000 Par 12 [Speed Ref 2]. ✓ RW Real 14 Preset Speed 1 Default: Min/Max: Units: Preset Speed 7 Provides an internal fixed speed command value. The preset speeds may be selected with Par Scale: 27 [Speed Ref A Sel] or Par 28 [Speed Ref B Sel]. 0.0000 -/+8.0000 P.U. rpm Par 4 [Motor NP RPM] = 1.0 P.U. ✓ RW Real Speed Trim 1 0.0000 -/+14112.0000 rpm Par 4 [Motor NP RPM] = 1.0 P.U. ✓ RW Real Default: 0.0000 Speed Trim 2 Provides an additive speed trim value to Par 47 [SpdRef + SpdTrm1] with a Lead/Lag filter. The Min/Max: -/+14112.0000 Position regulator output is linked to this parameter by default. This speed trim value affects the Units: rpm speed reference input to the speed regulator. Scale: Par 4 [Motor NP RPM] = 1.0 P.U. ✓ RW Real Speed Trim 3 ✓ RW Real through through 20 21 22 23 RW 16-bit Integer Provides an additive trim value to Par 38 [Speed Ref Scale]. Provides a scalable speed trim value that will be added to Par 47 [SpdRef + SpdTrm1]. Par 24 [SpdTrim 3 Scale] scales this value prior to the trim value affecting the speed reference. Default: Min/Max: Units: Scale: Default: Min/Max: Units: Scale: 0.0000 -/+14112.0000 rpm Par 4 [Motor NP RPM] = 1.0 P.U. (1) The calculation is based on the drive frame size and input voltage. Rockwell Automation Publication 20D-PM001B-EN-P - July 2011 35