Download G9 ASD Installation and Operation Manual
Transcript
efesotomasyon.com -Toshiba inverter,drive,servo,plc F242 F251 Run Frequency Hysteresis Direct Access Number — F242 Program Special Frequency Control Parameter Type — Numerical This parameter provides a plus-or-minus value for the Run Frequency (F241) setting. Factory Default — 0.00 Changeable During Run — Yes Minimum — 0.00 Maximum — 30.0 Units — Hz End Frequency Direct Access Number — F243 Program Special Frequency Control Parameter Type — Numerical This parameter sets the lowest frequency that the drive will recognize during deceleration before the drive goes to 0.00 Hz. Factory Default — 0.00 Changeable During Run — Yes Minimum — 0.00 Maximum — 30.0 Units — Hz 0 Hz Dead Band Signal Direct Access Number — F244 Program Special Special Parameters Parameter Type — Numerical This parameter sets an output frequency threshold that, until the commanded frequency surpasses this setting, the ASD will output 0.00 Hz to the motor. This setting will override the Start Frequency (F240) setting if this setting has a higher value. Factory Default — 0.00 Changeable During Run — Yes Minimum — 0.00 Maximum — 5.00 Units — Hz DC Injection Braking Start Frequency Direct Access Number — F250 Program Protection DC Braking Parameter Type — Numerical During deceleration this is the frequency at which DC Injection Braking will start. Factory Default — 0.00 DC Injection Braking Minimum — 0.00 DC Injection Braking is a braking system used with 3-phase motors. Unlike conventional brakes, there is no physical contact between the rotating shaft and a stationary brake pad or drum. When braking is required, the drive outputs a DC current that is applied to the windings of the motor to quickly brake the motor. The braking current stops when the time entered in F252 times out. Changeable During Run — Yes Maximum — 120.00 Units — Hz The intensity of the DC current used while braking determines how fast the motor will come to a stop and may be set at F251. The intensity setting is entered as a percentage of the full load current of the ASD. DC Injection Braking is also used to preheat the motor or to keep the rotor from spinning freely when the motor is off by providing a pulsating DC current into the motor at the Carrier Frequency. This feature may be enabled at F254. DC Injection Braking Current Direct Access Number — F251 Program Protection DC Braking Parameter Type — Numerical This parameter sets the percentage of the rated current of the drive that will be used for DC Injection Braking. A larger load will require a higher setting. Factory Default — 50 Changeable During Run — Yes Minimum — 0 Maximum — 100 Units — % 124 G9 ASD Installation and Operation Manual