efesotomasyon.com -Toshiba inverter,drive,servo,plc F402 F409 Autotuning 2 Direct Access Number — F402 Program Motor Vector Motor Model Parameter Type — Selection List This parameter introduces a thermal element into the autotuning equation and is used to automatically adjust the Autotune parameter values as a function of increases in the temperature of the motor. Factory Default — Off Changeable During Run — No Settings: 0 — Off 1 — Self-Cooled Motor Tuning 2 — Forced Air Cooled Motor Tuning Motor Rated Capacity Direct Access Number — F405 Program Motor Vector Motor Model Parameter Type — Numerical This parameter is used to set the (nameplated) rated capacity of the motor being used. Factory Default — 11.0 Changeable During Run — Yes Minimum — 0.1 Maximum — 500.00 Units — kW Motor Rated Current Direct Access Number — F406 Program Motor Vector Motor Model Parameter Type — Numerical This parameter is used to set the (nameplated) current rating of the motor being used. Factory Default — 20.3 Changeable During Run — Yes Minimum — 0.1 Maximum — 2000.0 Units — Amps Motor Rated RPM Direct Access Number — F407 Program Motor Vector Motor Model Parameter Type — Numerical This parameter is used input the (nameplated) rated speed of the motor. Factory Default — 1730 Changeable During Run — Yes Minimum — 100 Maximum — 60000 Units — RPM Base Frequency Voltage 1 Direct Access Number — F409 Program Vector Vector Motor Model Parameter Type — Numerical The Motor 1 Base Frequency Voltage 1 is the Motor 1 output voltage at the Base Frequency (F014). Regardless of the programmed value, the output voltage cannot be higher than the input voltage. The actual output voltage will be influenced by the input voltage of the ASD and the Supply Voltage Correction setting (F307). 152 Factory Default — (ASD-Dependent) Changeable During Run — Yes Minimum — 50.0 Maximum — 660.0 Units — Volts G9 ASD Installation and Operation Manual