Direct Access Number — F402
Program Motor Vector Motor Model
Parameter Type — Selection List
This parameter introduces a thermal element into the autotuning equation and is
used to automatically adjust the Autotune parameter values as a function of
increases in the temperature of the motor.
Factory Default — Off
Changeable During Run — No
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Motor Rated Capacity
Direct Access Number — F405
Program Motor Vector Motor Model
Parameter Type — Numerical
This parameter is used to set the (nameplated) rated capacity of the motor being
used.
Factory Default — 11.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 500.00
Units — kW
Motor Rated Current
Direct Access Number — F406
Program Motor Vector Motor Model
Parameter Type — Numerical
This parameter is used to set the (nameplated) current rating of the motor being
used.
Factory Default — 20.3
Changeable During Run — Yes
Minimum — 0.1
Maximum — 2000.0
Units — Amps
Motor Rated RPM
Direct Access Number — F407
Program Motor Vector Motor Model
Parameter Type — Numerical
This parameter is used input the (nameplated) rated speed of the motor.
Factory Default — 1730
Changeable During Run — Yes
Minimum — 100
Maximum — 60000
Units — RPM
Base Frequency Voltage 1
Direct Access Number — F409
Program Vector Vector Motor Model
Parameter Type — Numerical
The Motor 1 Base Frequency Voltage 1 is the Motor 1 output voltage at the
Base Frequency (F014). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Correction setting (F307).
152
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 50.0
Maximum — 660.0
Units — Volts