PCM360DW Condition Management System
related edit box. Finally, click Download button.
7.
Click Stop Calibration button to finish the channel 1 calibration.
8.
Repeat the steps above to calibrate channel 2. After two channels were calibrated, click Exit button.
Calibration for DTM
Zero Calibration
The 4mA zero calibration process is below:
1.
Run DTM-CFG software, and connect the software and DTM device. Ensure they can normally
communicate with each other.
2.
Connect the ammeter and DTM device. To perform step 1 and step 2, please refer to DTM System
Wiring Diagram for Configuration (Consult DTM-CFG User Manual).
3.
Directly click Calibration button on main window or select 4mA Calibration command from Operation
menu. Window below is launched. To start zero calibration, you should activate it by configuration
password.
4.
Click Start Calibration button on the window.