Download Display - Service, Support

Transcript
PCS 7 BRAUMAT Library – process tag types
BlVlvL
2.10 BlVlvL
Valve with one control output (open/close) and two feedbacks
This process tag type can be used for valves with Open/Close position with the APL block VlvL.
•
The feedback signal of the valve is read from the I/O through Pcs7DiIn driver blocks.
•
The interlock signals of VlvL are connected to the IntLk02 interlock blocks. These interlock blocks in
turn are connected to other blocks, for example, to digital process tags via Pcs7DiIn.
•
The digital output signals are sent to the I/O through the PCS7DiOu blocks.
•
In unit simulation mode, the feedback signal is generated from the adapter block (delayed on
demand)
Used Block types
Block type
Library
Comment
Pcs7DiIn
PCS 7 APL-Library
Standard-driver block for digital input
Pcs7DiOu
PCS 7 APL-Library
Standard-driver block for digital output
BlVlvL
PCS 7 BRAUMAT Library
BRAUMAT adapter block for valve controls
VlvL
PCS 7 APL-Library
APL valve control block
IntLk02
PCS 7 APL-Library
APL interlock with 2 inputs
Signal connections in CFC-Chart
Block
Connector
Comment
Pcs7DiIn
PV_In
Feedback open
Pcs7DiIn
PV_In
Feedback close
BlVlvL
CMData
EQM status information
Intlk02
In01
Activation enable ("Permission"):
Intlk02
In01
Interlock without reset ("Interlock"):
Intlk02
In01
Interlock with reset ("Protection"):
Pcs7DiOu
PV_Out
PCS 7 BRAUMAT Library V7.1
User Manual, 04/2012, A5E03447308-02
Command valve open/close