Parameters PID Controller (P9) The VSM II series frequency inverters are provided with a PID controller that you activate with P9.1 = 1. The controller can be deactivated via a digital input (P3.12). PID control is superimposed on the frequency inverter function. You should therefore set all of the frequency inverter’s drive-related parameters, such as maximum output frequency (motor speed), acceleration and deceleration ramps (mechanical load, belts). Frequency inverter and motor are process-integrated actuators. The output frequency to the motor (which determines the speed) is specified as manipulated variable from the PID controller. When the PID controller is activated, the setpoints and actual values become process variables and are normalized automatically into percentages (%). For example, the specified setpoint (0–100%) here is the same as a volume flow (0–50 m3/h). The actual value here is the volume flow (m3/h) from a suitable sensor, which is evaluated again as a percentage (0–100%). If this process data is to be displayed in the physical variable (m3/h), you can set the conversion with parameter P9.19 (see “Display factor (P9.19)”). PID Controller PNU ID P9.1 163 P9.2 118 Access RUN Value/Range Description Factory Setting (P1.3) — PID Controller 0 0 Deactivated 1 Activated for drive control 2 Activated for external application — PID controllers, P gain 0–1000% Proportional Gain (KP) 100 Low values attenuate the control action High values can cause oscillation P9.3 119 — 0–320s Integral time constant P9.4 167 — PID controller setpoint, keypad reference 0–100% Setpoint setting range utilizing keypad as reference P9.5 = 0 — PID controller, setpoint source — The setting range is limited by P6.3 (raised starting frequency) and P6.4 (end frequency) 0 Keypad (P9.4) 1 Fieldbus 2 AI1 3 AI2 P9.5 332 PID controller, I reset time VSD Series II Variable Speed Micro Drives (VSM II) LIT-12011835—May 2013 www.johnsoncontrols.com 10.0 0.0 0 93