Download PI Interface for Modbus Ethernet PLC

Transcript
Chapter 11.
UniInt Failover Configuration
Introduction
To minimize data loss during a single point of failure within a system, UniInt provides two
failover schemas: (1) synchronization through the data source and (2) synchronization
through a shared file. Synchronization through the data source is Phase 1, and
synchronization through a shared file is Phase 2.
Phase 1 UniInt Failover uses the data source itself to synchronize failover operations and
provides a hot failover, no data loss solution when a single point of failure occurs. For this
option, the data source must be able to communicate with and provide data for two interfaces
simultaneously. Additionally, the failover configuration requires the interface to support
outputs.
Phase 2 UniInt Failover uses a shared file to synchronize failover operations and provides for
hot, warm, or cold failover. The Phase 2 hot failover configuration provides a no data loss
solution for a single point of failure similar to Phase 1. However, in warm and cold failover
configurations, you can expect a small period of data loss during a single point of failure
transition.
Note: This interface supports only Phase 2 failover.
You can also configure the UniInt interface level failover to send data to a High Availability
(HA) PI Server collective. The collective provides redundant PI Servers to allow for the
uninterrupted collection and presentation of PI time series data. In an HA configuration,
PI Servers can be taken down for maintenance or repair. The HA PI Server collective is
described in the PI Server Reference Guide.
When configured for UniInt failover, the interface routes all PI data through a state machine.
The state machine determines whether to queue data or send it directly to PI depending on the
current state of the interface. When the interface is in the active state, data sent through the
interface gets routed directly to PI. In the backup state, data from the interface gets queued
for a short period. Queued data in the backup interface ensures a no-data loss failover under
normal circumstances for Phase 1 and for the hot failover configuration of Phase 2. The same
algorithm of queuing events while in backup is used for output data.
PI Interface for Modbus Ethernet PLC
89