Classification
8.4 Terminal Specifications
Command
Command name
Functions
(BX)
Coast-to-stop
command
[X3] - [CM] ON:
The inverter output is stopped E03 = 7
immediately and the motor will
coast-to-stop.
(No alarm signal will be output.)
(e.g.) Assigns the command (BX) to terminal [X3].
(RST)
Alarm reset
[X1] - [CM] ON:
Alarm status is reset.
(ON signal should be held for 0.1 s or longer.)
(e.g.) Assigns the command (RST) to terminal [X1].
E01 = 8
(THR)
Alarm from
external
equipment
[X2] - [CM] OFF:
E02 = 9
(JOG)
Jogging operation [X3] - [CM] ON:
The inverter output is stopped
and the motor coasts-to-stop.
Alarm signal for the alarm code OH2 will be output.
(e.g.) Assigns the command (THR) to terminal [X2].
Jogging operation is effective.
(FWD) or (REV) ON: The inverter runs the motor
with jogging frequency.
(e.g.) Assigns the command (JOG) to terminal [X3].
Freq. set2/
Freq. set1
[X1] - [CM] ON:
Frequency command source 2
is effective.
(e.g.) Assigns the command (Hz2/Hz1) to terminal
[X1].
C20 =
0.00 to
400.0
Hz
H54 =
0.00 to
3600 s
E01 = 11
F01 = 0
to 4
C30 = 0
to 4
(WE-KP)
Write enable for
keypad
[X2] - [CM] ON:
The function code data can be
changed from the keypad.
(Data can be changed when this function is not
allocated.)
(e.g.) Assigns the command (WE-KP) to terminal
[X2].
E02 = 19
(Hz/PID)
PID control
cancel
[X3] - [CM] ON:
E03 = 20
The PID control is cancelled,
and the set frequency is set by
the Multistep frequency,
keypad or analog input.
(e.g.) Assigns the command (Hz/PID) to terminal
[X3].
(IVS)
Inverse mode
changeover
J01 to
J06
F01 = 0
to 4
C30 = 0
For details about J01 to J06 data, refer to Chapter 9, to 4
"FUNCTION CODES."
[X1] - [CM] ON:
Normal mode operation or
inverse mode operation can be
changed in the frequency
command and PID control.
(e.g.) Assigns the command (IVS) to terminal [X1].
8-17
E01 = 21
SPECIFICATIONS
(Hz2/Hz1)
E03 = 10
Chap. 8
Commands assigned on digital input terminals
Related
function