1.15 Derivative Action Selection Function This function improves dynamic characteristics by selecting a suitable derivative action for fixed value actions or ramp actions. Action Each type of derivative action operates as shown below. Setting of "Derivative action selection" Measured Value Derivative (0) Action Fixed value action Ramp action Set value (SV) Disturbance This setting effectively prevents the temperature from being affected by a disturbance. However, the performance to follow the set value can be low. Temperature process value (PV) Deviation Derivative (1) Fixed value action Ramp action Set value (SV) Disturbance This setting allows the temperature to follow the set value well. However, the temperature get affected by a disturbance greatly. Temperature process value (PV) Setting method Configure the setting as follows. [Navigation window] [Parameter] Target module [Module Parameter] [Application Setting] [Derivative action selection] 50 1 FUNCTIONS 1.15 Derivative Action Selection Function