Download Operating Manual
Transcript
TM 40/40M, Rev (9) August 2015 D.1.3 Range Table 28: Sensitivity Ranges Sensitivity Detection Range (ft. / m) Standard Test Range (ft. / m) 1 (Low) 50 / 15 7 / 2.2 2 100 / 30 14.5 / 4.5 3 150 / 45 22 / 7 4 (High) 215 / 65 29 / 9 Notes: The minimum distance from the detector is 20 inches (50 cm). At extreme temperatures, there is a 15% maximum reduction in the range. Important: Keep the Flame Simulator in a safe place when not in use. D.1.4 Charging the Battery The Flame Simulator uses NiCd batteries as a rechargeable power source. When the batteries are fully charged, the simulator operates for at least 60 times without recharging. An internal buzzer is sounded when the voltage from the batteries is lower than the required operational level. ➣ To charge the battery: 1 Place the Flame Simulator on a table in a safe area. 2 Turn the sealed plug (next to the operation button) counter-clockwise with a suitable wrench. 3 Connect the battery charger. 4 Charge for a maximum of 14 hours. 5 Disconnect the charger. 6 Tighten the sealed plug clockwise. Warning: Charge the simulator only when the battery is fully discharged. During activation of the flame simulator, buzzer activation indicates that the battery is discharged. Long Range Multi IR Flame Simulator 63