Spec--HT TVM (DLMS) - 21 - Annexure- B Tamper Logics for HT-TVM Persistence time: 5 Min. Restoration Time : 1 Min. (60 Sec.) Tamper Events 1. Missing Potential a. Voltage b. Current 2. CT Polarity Reversal a. Line Current in tampered phase b. Power Factor. 3. CT Open a. Line current in tampered phase b. Line current in other phases c. Load current in tampered phase 4. CT Bypass a. By Pass Current 5. Current unbalance a. Maximum current – Minimum current 6. Neutral Disturbance a. DC current injected on neutral from load side by mean of electronic circuit using diodes after removal/ disconnection of neutral. 7. Interference of Magnetic field a. Presence of Magnetic field Occurrence Restoration < 20% Vb > 10% Ib > 40% Vb Ignored. > 5% Ib (in reverse > 10% Ib (in direction) forward direction) >0.1 >0.1 < 2% Ib > 10% Ib > 10% Ib > 5% Ib. >5% Ib. Ignore > 20% Ib < 10% Ib (current in tampered phase) > 30% Ib < 10% Ib If meter detect removal voltage greater than injection 1.25 times of Vref. of Magnetic field which removal affects accurate magnetic field. Meter recording. DC of