Spec--HT TVM (DLMS) -3- h) Maximum attitude above mean sea level i) Average rain fall. j) Maximum wind pressure k) Isoceranic level (days/ year) l) Seismic level ( Horizontal Accn.) m) Permitted noise level :1000 Meters. : 10-100 cms. : 200Kg/ Sq. meter. : 40 : 0.30 g. : 45 db. 3.04 SUPPLY SYSTEM: Rated Voltage (Vref) (For HTTVM) (Through PT) Ph.) Rated current (Ib) (Connected through CT) 3 x 63.5 V - Phase to Neutral (3 phase 4 wire system) 3 x 110 V - Phase to Phase Meter shall be programmed for PT ratio 11KV/110V (Ph.to 3 x -/5 Amps. Multiplying factor to arrive at actual primary values wherever applicable shall be calculated from the CT and PT ratio of the installed CTs and PTs/CT ratio of the installed CT’s. 3.05 POWER FACTOR RANGE: The meter shall be suitable for full power factor range from zero (lagging) through unity to zero (leading). The meter should work as an active energy import and export and reactive (lag and lead) energy meter. 3.06 POWER SUPPLY VARIATION: The supply system shall be 3x110V Phase to Phase,3 phase 4 wires. The extreme power supply variations for which an operating meter should withstand without damage and without degradation of its meteorological characterstatics when it is subsequently operated under its normal operating conditions shall be as follows: Specified operating range Limit range of operation Frequency - 0.8 to 1.15 V ref. - 0.7 to 1.20 V ref. - 50 Hz. +/- 5% However, the bidder can offer meter, which can withstand higher variations. The limit of power supply variations should be as per IS: 14697-1999. 3.07 ACCURACY: Class of accuracy of the meter shall be 0.5S. The accuracy should not drift with time.