Download "user manual"
Transcript
Mandatory Provisions HVAC Example 6-M—Data Processing Rooms Q An office housing both workers and data processing equipment is cooled by HVAC equipment that is provided primarily to maintain space conditions for the data processing equipment. Does the equipment have to comply with the Standard or is it exempt because its purpose is primarily to cool process equipment? A Determining whether a system is serving a process role or comfort conditioning role can be complicated when the space is occupied by both workers and process equipment. In general, if the HVAC system is no different than it would be for comfort applications, then it must comply with the Standard. However, if the equipment includes special humidification and dehumidification systems designed to maintain tight humidity and temperature control not normally required for comfort applications, then it is considered a process application and need not comply with the Standard. User’s Manual for ANSI/ASHRAE/IESNA Standard 90.1-2007 Copyright ASHRAE Provided by IHS under license with ASHRAE No reproduction or networking permitted without license from IHS Licensee=AECOM/5906698001, User=li, xiaoxiao Not for Resale, 07/02/2009 03:02:18 MDT 6-19 --`,``,``,`,,,,,`````,`,```,```,-`-`,,`,,`,`,,`--- walls are considered to have different orientations if the directions they face differ by more than 45 degrees. For example, in Figure 6-C, a zone must be provided for each of the exposures that exceed 50 feet in length, while the shorter exposures on the serrated side of the building need not have individual zones. These shorter exposures may be served by adjacent zones serving other exposures. ▪ Each perimeter system zone is controlled by one or more thermostats located in the zones served. In the past, perimeter systems were often controlled by outdoor air sensors that would reset the output of the system proportional to outdoor air temperature. But since solar loads can offset some of the heat loss from a space, this type of control inevitably causes overheating by the perimeter system when the sun is shining and subsequent fighting with the cooling system. Even when this control is improved by solar compensation, it still can result in wasteful fighting between interior and perimeter systems due to varying internal loads. Therefore, only controls that respond to temperature within the zones served are allowed.