16. ALARM DRY CONTACTS
The rear panel of the UPS contains a standard RS232 port labeled ALARM. This port
is an interface to the Alarm Dry Contacts. The Alarm Dry Contact port is shown
below.
The Alarm Dry Contacts can be used to notify a computer or another system when
certain events take place on the POWER + SA UPS system.
The Alarm Dry Contacts can report any of three conditions, as described in the
following table.
74
Alarm Condition
State of Dry Contacts
No input voltage to the
rectifier
There is a voltage between
This circuit is normally open.
pin
3
and
pin
4.
Battery voltage is low
There is a voltage between
This circuit is normally open.
pin
5
and
pin
4.
Any alarm
exists
There is a voltage between
This circuit is normally open.
pin
7
and
pin
8.
condition
POWER+ SA User Guide (UL), Release 1.8