Download SILENT KNIGHT MODEL 5207
Transcript
Model 5207 Installation and Operation Manual 4.7.2 NFPA 72 Polarity Reversal When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the 5207 panel is reset. If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. To install the 5220 for polarity reversal, follow the steps below: 1. Locate the knockout on the right side of the 5207 cabinet to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length). 2. Wire the 5220 to the 5207 using the four-wire pigtail provided as shown in Figure 4-8 (next page). This diagram also shows how to connect the 5220 to the remote indicator. 3. Program relays as shown in the chart below: Step Option Select 23.4 23.5 23.6 Fire Alarm Trouble No Silence Relay 2 Relay 3 Relay 3 and Bell 4 4. Program notification circuit 4 to be non-supervised (Step 5) and non-silencing (Step 23.6, Bell #4). Do not select pulsing bells. 5. If necessary, adjust loop current using potentiometer R10 on the 5220 board. Normal loop current is 4-to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm. Figure 4-8 Polarity Reversal Connection 4-8 150865