3.2.3 For Current Input Wiring Diagram and Internal Circuit Diagram In case of the current input, connect In terminals each other. Terminal layout (Note) Do not connect anything to N.C terminals. • Use double-core twisted-pair shielded wires. It is recommended to ground them. However, depending on the conditions of the external noise, it may be better not to ground the shielding. • Do not have the analog input wiring close to AC wires, power wires, or load line from a device other than PLC. Also, do not bundle it with them. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]