Download Modbus Map - Meters USA
Transcript
This chapter will mainly discuss how to handle the meter via the communication port using software. To master this chapter, you should be familiar with Modbus and have read other chapters of this manual, and you have generously mastered the function and application of this product. This chapter includes: Modbus protocol, format of communication and data address table and Acuvim II application details. 5.1 Introducing Modbus Protocol The Modbus RTU protocol is used for communication in Acuvim II. The data format and error check met hods are defined in Modbus protocol. The half duplex query and respond mode is adopt ed in Modbus protocol. There is only one master device in the communication net. The others are slave devices, waiting for the query of the master. Transmission mode which is compatible with Modbus RTU Mode*. Coding System Start bit 8-bit binary 1 Data bits Parity Stop bit 8 no parity 1 Error checking CRC check Framing Address 8-Bits Function 8-Bits Data N×8-Bits Table5.1 Data Frame Format 74 Check 16-Bits