REHABILITATE CAUDELL HALL BUILDING 18 STATE UNIVERSITY OF NEW YORK BUFFALO STATE COLLEGE SUCF PROJECT NO. 03421 DIVISION 23 – HVAC EXHIBIT "II" - DUCT INSULATION MATERIALS MINIMUM INSULATION THICKNESS MINIMUM REQUIRED R VALUE SERVICE & LOCATION INSULATION MATERIAL Air conditioning & heating supply (within building envelope) Exposed: Rigid fiberglass 1-1/2 in. R-5 Concealed: Flexible fiberglass 2 in. R-5 Rigid board duct insulation with VentureClad 1577CW jacketing system. 2-1/2 in. R-8 Air conditioning & heating supply (exterior to building envelope) Air conditioning & heating return REMARKS Not insulated Air conditioning & heating return (exterior to building envelope) Rigid board duct insulation with VentureClad 1577CW jacketing system. 2-1/2 in. Outside air ducts and plenums, connections, and mixing boxes Rigid fiberglass 2 in. Provide neat fit at intake plenum Exhaust, relief, or vent ducts and plenums Exposed: Rigid fiberglass 1 in. Concealed: Flexible fiberglass 1-1/2 in. Insulate 15 ft. from exterior opening and plenums or 5 ft. beyond damper, whichever is greater. Kitchen hood exhaust Dishwasher exhaust INSULATION R-8 Refer to specification section 230714 – Fire Rated Duct Insulation. SEE NOTE 1 Exposed: Rigid fiberglass 1 in. Concealed: Flexible fiberglass 1-1/2 in. 230700 - 7