Section 5 Functions and Operations
5.3 Setting Scaling Values
Initial setting level
Set scaling to convert and display input values as any value. Inputs A
and B are set separately.
One point *
L0
<Setting parameter for input A>
inp. a1
(INP.A1)
L0
inp. a2
(INP.A2)
L0
inp. b1
Parameter
Set value
Meaning of set value
Scaling input value A1
inp. a1
-9999 to
1
99999 *
Input value corresponding
to dsp. a1
Scaling display value A1
dsp. a1
-9999 to
1
99999
Display value
corresponding to inp. a1
Scaling input value A2
inp. a2
-9999 to
1
99999 *
Input value corresponding
to dsp. a2
Scaling display value A2
dsp. a2
-9999 to
1
99999
Display value
corresponding to inp. a2
<Setting parameter for input B>
(INP.B1)
L0
inp. b2
(INP.B2)
L0
dsp. a1
Functions and Operations
(DSP.A1)
L0
dsp. a2
(DSP.A2)
L0
dsp. b1
(DSP.B1)
L0
dsp. b2
(DSP.B2)
L0
Parameter
Set value
Meaning of set value
Scaling input value B1
inp.b1
-9999 to
1
99999 *
Input value corresponding
to dsp.b1
Scaling display value B1
dsp.b1
-9999 to
1
99999
Display value
corresponding to inp.b1
Scaling input value B2
inp.b2
-9999 to
1
99999 *
Input value corresponding
to dsp.b2
Scaling display value B2
dsp.b2
-9999 to
1
99999
Display value
corresponding to inp.b2
The decimal point position for scaling input values depends on the
input type.
Input type
Set value
0.000 to 20.000 mA
0. 000 to 20. 000
4.000 to 20.000 mA
4. 000 to 20. 000
0.000 to 5.000 V
0. 000 to 5. 000
1.000 to 5.000 V
1. 000 to 5. 000
±5.000 V
-5. 000 to 5. 000
±10.000 V
10. 000 to 10. 000
-
dp
(DP)
L0
k
(K)
* Use the teaching function to use actual inputs to set scaling input values "inp. a1", "inp. a2", "inp.
b1", and "inp. b2".
Refer to Teaching (P.5-15) for details.
5-12