Download 20D-UM003 - Rockwell Automation
Transcript
DriveLogix™ 5730 Controller for PowerFlex® 700S Drives with Phase II Control Firmware Version 15.04 User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http:// www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual, when necessary we use notes to make you aware of safety considerations. ! WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product. ! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid the hazard • recognize the consequences Shock Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present. Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures. PowerFlex is a registered trademark of Rockwell Automation, Inc. DriveExplorer, DriveExecutive, and SCANport are trademarks of Rockwell Automation, Inc. PLC is a registered trademark of Rockwell Automation, Inc. Summary of Changes Manual Updates This information summarizes the changes to the DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control, publication 20D-UM003, since the July 2004 release. Change Added information for contacting Technical Support and updated Controller Firmware Revision information Updated information and example for specifying task priorities Updated information on controller fault response settings See Page... Preface-2 1-7 3-2, 3-6, 3-8, and 3-12 Updated the System Requirements for configuring DriveLogix Motion 4-1 Updated the Coarse Update Period setting from 4ms to 2ms 4-9 Updated the tables for parameter links and parameter settings for configuring 4-18 and DriveLogix Motion 4-19 Updated the Communicating with Devices on an EtherNet/IP Link procedures to reflect 6-4 the support of duplicate IP address detection. Added information regarding updated MSG packet size. 6-19 Added information regarding updated MSG packet size. 7-9 Added a new Appendix for application restrictions C-1 soc-2 Table of Contents Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Summary of Changes Manual Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i-1 Preface Overview Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contacting Tech Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Firmware Revision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 1 P-1 P-1 P-2 P-2 P-3 P-3 What is DriveLogix5730? Loading Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Using CompactFlash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 Developing Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6 Selecting a System Overhead Percentage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 Understanding the Virtual Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12 Chapter 2 Placing and Configuring the Drive De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 2-1 Understanding the Interface to the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Determining When the Controller Updates the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Placing and Configuring the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Inhibiting the Drive Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11 Using DriveExecutive Lite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Accessing Drive Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21 Monitoring Drive Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21 Configuring the Controller’s Response to a Connection Failure . . . . . . . . . . . . . . . . . . 2-22 Recommended Programming Techniques. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25 Chapter 3 Placing and Configuring Local I/O De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 3-1 Understanding How the DriveLogix5730 Supports I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Placing Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Validating I/O Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Estimating RPI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Determining When the Controller Updates I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Configuring the CompactBus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 Configuring Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 Accessing I/O Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 Direct Connections for I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14 Monitoring I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 Configuring I/O Modules Using the Generic 1769-MODULE . . . . . . . . . . . . . . . . . . . 3-17 ii Chapter 4 Configuring DriveLogix Motion De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 4-1 About this Chapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Programming the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 Launching DriveExecutive from RSLogix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14 Configuring the Drive with DriveExecutive Software. . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Downloading the Settings and Links to the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20 Additional Testing and Programming is Necessary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20 Supported Motion Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21 Chapter 5 Communicating with Devices on a Serial Link De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 5-1 Configuring Your System for a Serial Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Example 1: Workstation Directly Connected to a DriveLogix Controller. . . . . . . . . . . . . 5-6 Example 2: Workstation Remotely Connected to a DriveLogix Controller . . . . . . . . . . . 5-7 Example 3: DriveLogix Controller to a Bar Code Reader. . . . . . . . . . . . . . . . . . . . . . . . 5-10 Chapter 6 Communicating with Devices on an EtherNet/IP Link De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 6-1 Communicating Through the Embedded EtherNet/IP Option. . . . . . . . . . . . . . . . . . . . . . 6-2 Controller Connections Over EtherNet/IP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 Configuring Distributed I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12 Adding a Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15 Producing and Consuming Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15 Using a MSG Instruction to Send an Email. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24 Example 1: DriveLogix5730 Controller and Distributed I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-31 Example 2: Controller to Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-32 Chapter 7 Communicating with Devices on a ControlNet Link De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 7-1 Configuring Your System for a ControlNet Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Configuring Distributed I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4 Scheduling the ControlNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7 Sending Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9 Producing and Consuming Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14 Guidelines for Configuring Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17 Example 1: DriveLogix Controller and Remote I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18 Example 2: DriveLogix5730 Controller to DriveLogix5730 Controller . . . . . . . . . . . . . 7-19 Example 3: DriveLogix Controller to Other Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22 Chapter 8 Communicating with Devices on a DeviceNet Link De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . 8-1 Example: Controlling I/O Over DeviceNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2 iii Chapter 9 Communicating with Devices on a DH485 Link De-energizing the Drive to Connect or Disconnect a Cable . . . . . . . . . . . . . . . . . . . . . . . Understanding How the DriveLogix5730 Controller Supports DH485 Communications Configuring Your System for a DH-485 Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Planning a DH-485 Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing a DH-485 Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Browsing a DH-485 Network Remotely . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix A DriveLogix5730 Controller Specifications DriveLogix5730 Controller Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DriveLogix5730 Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DriveLogix5730 Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Real-Time Clock Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Embedded EtherNet/IP Option LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix B A-1 A-1 A-2 A-2 A-3 A-6 A-8 Access Procedures Removing Power from Drive and Compact I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Opening Door Over Power Structure and Main Control Board . . . . . . . . . . . . . . . . . . . . Removing the Control Cassette from Frame 1-6 Size Drives . . . . . . . . . . . . . . . . . . . . . . Removing the Outside Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing the Inside Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replacing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the Embedded EtherNet/IP Option Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the DriveLogix5730 Expansion Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the Compact I/O Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing the Communications Daughtercard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix C 9-1 9-1 9-2 9-4 9-6 9-9 B-1 B-2 B-2 B-3 B-3 B-4 B-5 B-7 B-7 B-8 B-9 Application Restrictions Additional Memory Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1 Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1 Hold Last State and User-Defined Safe State Not Supported . . . . . . . . . . . . . . . . . . . . . . C-3 Index iv Preface Overview Who Should Use This Manual This manual is intended for qualified personnel. You must be able to program and operate Adjustable Frequency AC Drive devices and programmable controllers. Purpose of this Manual This manual guides the development of projects for DriveLogix controllers. It provides procedures on how to establish communications: • with the following networks – ControlNet – DeviceNet – EtherNet/IP – serial • with the following devices – PowerFlex® 700S drive – controllers – I/O – workstations – PanelView terminals p-2 Overview Related Documentation Allen-Bradley publications are available on the internet at www.rockwellautomation.com/literature. These core documents address the Logix5000 family of controllers: If you are: a new user of a Logix5000 controller Use this publication: Logix5000 Controllers Quick Start publication 1756-QS001 This quick start provides a visual, step-by-step overview of the basic steps you need to complete to get your controller configured and running. an experienced user of Logix5000 controllers Logix5000 Controllers System Reference publication 1756-QR107 This system reference provides a high-level listing of configuration information, controller features, and instructions (ladder relay, function block diagram, and structured text). any user of a Logix5000 controller Logix5000 Controllers Common Procedures publication 1756-PM001 This common procedures manual explains the common features and functions of all Logix5000 controllers. DriveLogix-specific information is also available: For Information on the DriveLogix Instruction Set Information on function block programming Logix controllers. Execution times and memory use for instructions Information on selecting CompactLogix and Compact I/O components and modules Information on installing, configuring, and using Compact Analog I/O modules Information on installing, configuring and using PowerFlex® 700S drives Information on the DriveLogix Motion Control Instruction Set Information on installing an ControlNet communications daughtercard (Coax) Information on installing an ControlNet communications daughtercard (Fiber) Information on installing an EtherNet/IP communications daughtercard Information on installing an DeviceNet communications daughtercard Information on installing 1769-SDN DeviceNet Scanner Module Information on using 1769-SDN DeviceNet Scanner Module Information on converting from Phase I PowerFlex 700S and DriveLogix5720 to Phase II PowerFlex 700S and DriveLogix5730 Information on the basic installation of PowerFlex 700S drives and DriveLogix5730 controllers Contacting Tech Support Read this document Logix5000 Controllers General Instruction Set Reference Manual Logix5000 Controllers Process Control/Drives Instruction Set Reference Manual Logix5000 Controllers Execution Time and Memory Use Reference Manual Compact I/O Selection Guide Document number 1756-RM003… 1756-RM006… 1756-RM087… 1769-SG001… Compact I/O Analog Modules User Manual 1769-UM002… PowerFlex 700S Phase II User Manual 20D-UM006… Logix Controller Motion Instruction Set ControlNet Communications Daughtercard Installation Instructions ControlNet Communications Daughtercard Installation Instructions EtherNet/IP Communications Daughtercard Installation Instructions DeviceNet Communications Daughtercard Installation Instructions Compact I/O 1769-SDN DeviceNet Scanner Module 1756-RM007… 1788-IN002… Compact I/O 1769-SDN DeviceNet Scanner Module PowerFlex 700S Conversion Guide Phase I to Phase II Control 1769-UM009… 20D-AT001… 1788-IN005… 1788-IN054… 1788-IN053… 1769-IN060… Quick Start - PowerFlex 700S High Performance AC Drive 20D-QS001… For Automation and Control Technical Support: Title Rockwell Automation Technical Support Online at… http://support.rockwellautomation.com/knowledgebase Overview Controller Firmware Revision p-3 This revision on the DriveLogix 5730 User Manual corresponds to the following: • Version 15.04 and later controller firmware • Version 15.xx and later RSLogix 5000 programming software • Version 3.02 and later DriveExecutive programming software General Precautions Class 1 LED Product ! ! ! ! ATTENTION: Hazard of permanent eye damage exists when using optical transmission equipment. This product emits intense light and invisible radiation. Do not look into module ports or fiber optic cable connectors. ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection handbook. ATTENTION: Only qualified personnel familiar with the PowerFlex 700S Drive and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage. ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the +DC & –DC terminals of the Power Terminal Block. The voltage must be zero. p-4 Notes: Overview Chapter 1 What is DriveLogix5730? The DriveLogix controller is part of the Logix environment. The DriveLogix controller provides a distributed control system built on these components: • The DriveLogix5730 controller has one RS-232 port. The controller supports the Logix instructions. • RSLogix 5000 programming software that supports every Logix controller. • Direct connection to host PowerFlex 700S drive. • Compact I/O modules that provide a compact, DIN-rail or panel mounted I/O system. • Embedded EtherNet/IP option provides communication over an EtherNet/IP network. • 1788 communication daughtercard that provides communication over a standards-based ControlNet, EtherNet/IP, DeviceNet or third party network. The newer DriveLogix5730 controller offers significant performance and capacity improvements over the DriveLogix5720 controller. It offers: • • • • • increased user memory up to 1.5 Mbytes CompactFlash for non-volatile memory storage extended I/O capacity up to 16 I/O modules integrated EtherNet/IP support, including control of distributed I/O Run/Rem/Prog switch Remote Work Station ahw0783.eps EtherNet/IP DriveLogix with Local I/O ControlLogix Controller ControlNet Flex I/O PanelView 1-2 What is DriveLogix5730? Loading Controller Firmware De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of loading controller firmware you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with loading firmware. Loading Firmware The controller ships with working firmware. You may decide to upgrade the firmware. To load firmware, you can use: • ControlFlash utility that ships with RSLogix 5000 programming software. • AutoFlash that launches through RSLogix 5000 software when you download a project to a controller that does not have the current firmware. • a 1784-CF64 CompactFlash card with valid memory already loaded. The firmware is available with RSLogix 5000 software or you can download it from the support website: 1. Go to: http://support.rockwellautomation.com/ 2. In the left column (frame), select “Firmware Updates” under “Technical Support.” 3. Select the desired firmware revision. The download process will require you to enter the serial number of your RSLogix 5000 programming software. If you load (flash) controller firmware via the ControlFlash or AutoFlash utilities, you need a serial or EtherNet/IP connection to the controller. Flashing via an EtherNet/IP connection is faster than the serial connection. What is DriveLogix5730? 1-3 The controller’s EtherNet/IP configuration settings are maintained during a flash process. If you load firmware via an EtherNet/IP connection, browse through the network port, across the virtual backplane, and select the appropriate controller. Using ControlFlash to load firmware You can use ControlFlash to load firmware through either an Ethernet connection (an IP address must already be assigned to the Ethernet port) or a serial connection. 1. Make sure the appropriate network connection is made before starting. 2. Start the ControlFlash utility. Click Next when the Welcome screen appears. 3. Select the catalog number of the controller and click Next. 4. Expand the network until you see the controller. If the required network is not shown, first configure a driver for the network in RSLinx software. If you use an Ethernet connection to load the firmware (which is much faster than the serial connection), the utility will require a valid IP address before connecting to the controller. 5. Select the controller and click OK. 6. Select the revision level to which you want to update the controller and click Next. 7. To start the update of the controller, click Finish and then click Yes. 8. After the controller is updated, the status box displays Update complete. Click OK. 9. To close ControlFlash software, click Cancel and then click Yes. 1-4 What is DriveLogix5730? Using AutoFlash to load firmware You can use AutoFlash to load firmware through either an Ethernet connection (an IP address must already be assigned to the Ethernet port) or a serial connection. 1. Make sure the appropriate network connection is made before starting. 2. Use RSLogix 5000 programming software to download a controller project. If the processor firmware does not match that project revision, AutoFlash automatically launches. 3. Select the catalog number of the controller and click Next. 4. Expand the network until you see the controller. If the required network is not shown, first configure a driver for the network in RSLinx software. If you use an Ethernet connection to load the firmware (which is much faster than the serial connection), the utility will ask for a valid IP address before connecting to the controller. 5. Select the controller and click OK. 6. Select the revision level to which you want to update the controller and click Next. 7. To start the update of the controller, click Finish and then click Yes. 8. After the controller is updated, the status box displays Update complete. Click OK. 9. To close AutoFlash software, click Cancel and then click Yes. Using a CompactFlash card to load firmware If you have an existing DriveLogix5730 controller that is already configured and has firmware loaded, you can store the current controller user program and firmware on CompactFlash and use that card to update other controllers. 1. Store the controller user program and firmware of a currently configured DriveLogix5730 controller to the CompactFlash card. Make sure to select Load Image On Power-up when you save to the card. 2. Remove the card and insert it into a DriveLogix5730 controller that you want to have the same firmware and controller user program. 3. When you power up the second DriveLogix5730 controller, the image stored on the CompactFlash card is loaded into the controller. What is DriveLogix5730? Using CompactFlash 1-5 The 1784-CF64 CompactFlash card provides nonvolatile memory storage for the DriveLogix5730 controller. The card stores the contents of the controller memory (program logic and tag values) and the controller firmware at the time that you store the project. Storing information to the CompactFlash card is like storing a snapshot of controller memory at a given time. ! ATTENTION: If you configured the CompactFlash card to “restore on power up” and you make changes to a project, such as online edits or changes to tag values, you must store the project to the CompactFlash card again after you make changes. Otherwise, your changes are not saved and you will lose those changes on the next power cycle to the controller. Tag values stored in flash are a snapshot at the time of the store. During a program restore the processor tag values will be equal to tag data stored on flash. The locking tab on the front of the controller helps hold the CompactFlash card in its socket. ! ATTENTION: Do not remove the CompactFlash card while the controller is reading from or writing to the card, as indicated by a flashing green CF LED. This could corrupt the data on the card or in the controller, as well as corrupt the latest firmware in the controller. The CompactFlash card supports removal and insertion under power. ! ATTENTION: When you insert or remove the card while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation. See the Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001, for steps on storing an image on the CompactFlash card. 1-6 What is DriveLogix5730? Developing Programs The controller operating system is a preemptive multitasking system that is IEC 1131-3 compliant. This environment provides: • tasks to configure controller execution • programs to group data and logic • routines to encapsulate executable code written in a single programming language control application controller fault handler task 8 task 1 configuration status watchdog program 32 program 1 program (local) tags main routine fault routine other routines controller (global) tags I/O data system-shared data 40012.eps Defining tasks A task provides scheduling and priority information for a set of one or more programs. You can configure tasks as continuous, periodic, or event. Only one task can be continuous. The DriveLogix5730 controller supports as many as eight tasks. A task can have as many as 32 separate programs, each with its own executable routines and program-scoped tags. Once a task is triggered (activated), all the programs assigned to the task execute in the order in which they are grouped. Programs can only appear once in the Controller Organizer and cannot be shared by multiple tasks. What is DriveLogix5730? 1-7 Specifying task priorities Each task in the controller has a priority level. The operating system uses the priority level to determine which task to execute when multiple tasks are triggered. You can configure periodic tasks to execute from the lowest priority of 15 up to the highest priority of 1. A higher priority task will interrupt any lower priority task. The continuous task has the lowest priority and is always interrupted by a periodic task. The DriveLogix5730 controller uses a dedicated periodic task at priority 7 to process I/O data. This periodic task executes at the Requested Packet Interval (RPI) you configure for the CompactBus, which can be as fast as once every 1 ms. Its total execution time is as long as it takes to scan the configured I/O modules. How you configure your tasks affects how the controller receives I/O data. Tasks at priorities 1 to 6 take precedence over the dedicated I/O task. Tasks in this priority range can impact I/O processing time. If you configure the I/ O RPI at 1ms and you configure a task of priority 1 to 6 that requires 500 µs to execute and is scheduled to run every millisecond, this leaves the dedicated I/O task 500 µs to complete its job of scanning the configured I/ O. However, if you schedule two high priority tasks (1 to 6) to run every millisecond, and they both require 500 µs or more to execute, no CPU time would be left for the dedicated I/O task. Furthermore, if you have so much configured I/O that the execution time of the dedicated I/O task approaches 1 ms (or the combination of the high priority tasks and the dedicated I/O task approaches 2 ms) no CPU time is left for low priority tasks (8 to 15). TIP: For example, if your program needs to react to inputs and control outputs at a deterministic rate, configure a periodic task with a priority higher than 7 (i.e., 1 through 6). This keeps the dedicated I/O task from affecting the periodic rate of your program. However, if your program contains a large amount of math and data manipulation, place this logic in a task with priority lower than 7 (i.e., 8 through 15), such as the continuous task, so that the dedicated I/O task is not adversely affected by your program. Important: When using a DriveLogix5730 controller with Compact I/O, all application program tasks must have an assigned priority of 8 through 15 in order that they do not interfere with the proper operation of the Compact I/O. 1-8 What is DriveLogix5730? The following example shows the task execution order for an application with two periodic tasks and one continuous task. Task: 1 2 3 4 Priority Level: 5 7 10 none (lowest) Task Type: periodic task, executes every 20 ms dedicated I/O task (5 ms RPI) periodic task, executes every 10 ms continuous task Example Execution Time: 2 ms 1 ms 4 ms 25 ms Worst Case Completion Time: 2 ms 3 ms 8 ms 60 ms Task 1 Task 2 Task 3 Task 4 0 5 10 15 20 25 30 35 40 45 50 55 60 65 Time (ms) task_example.eps Notes: A. The highest priority task interrupts all lower priority tasks. B. The dedicated I/O task can be interrupted by tasks with priority levels 1 to 6. The dedicated I/O task interrupts tasks with priority levels 8 to 15. This task runs at the selected RPI rate scheduled for the DriveLogix5730 system (2ms in this example). C. The continuous task runs at the lowest priority and is interrupted by all other tasks. D. A lower priority task can be interrupted multiple times by a higher priority task. E. When the continuous task completes a full scan it restarts immediately, unless a higher priority task is running. Defining programs Each program contains program tags, a main executable routine, other routines, and an optional fault routine. Each task can schedule as many as 32 programs. The scheduled programs within a task execute to completion from first to last. Programs that are not attached to any task show up as unscheduled programs. You must specify (schedule) a program within a task before the controller can scan the program. What is DriveLogix5730? 1-9 Defining routines A routine is a set of logic instructions in a single programming language, such as ladder logic. Routines provide the executable code for the project in a controller. A routine is similar to a program file or subroutine in a PLC or SLC controller. Each program has a main routine. This is the first routine to execute when the controller triggers the associated task and calls the associated program. Use logic, such as the Jump to Subroutine (JSR) instruction, to call other routines. You can also specify an optional program fault routine. The controller executes this routine if it encounters an instruction-execution fault within any of the routines in the associated program. Selecting a System Overhead Percentage The Controller Properties dialog lets you specify a percentage for system overhead. This percentage specifies the percentage of controller time (excluding the time for periodic tasks) that is devoted to communication and background functions. 1. View properties for the controller and select the Advanced ahw0757.eps ahw0758.eps System overhead functions include: • communicating with programming and HMI devices (such as RSLogix 5000 software) • responding to messages • sending messages 1-10 What is DriveLogix5730? The controller performs system overhead functions for up to 1 ms at a time. If the controller completes the overhead functions in less than 1 ms, it resumes the continuous task. As the system overhead percentage increases, time allocated to executing the continuous task decreases. If there are no communications for the controller to manage, the controller uses the communications time to execute the continuous task. While increasing the system overhead percentage decreases execution time for the continuous task, it does increase communications performance. However, increasing the system overhead percentage also increases the amount of time it takes to execute a continuous task - increasing overall scan time. The following table shows the ratio between the continuous task and the system overhead functions: At this time slice: 10% 20% 33% 50% The continuous tasks runs for: 9 ms 4 ms 2 ms 1 ms And then overhead occurs for up to: 1 ms 1 ms 1 ms 1 ms TIP: For typical DriveLogix applications, a setting of 20-33% is recommended. At the default time slice of 10%, system overhead interrupts the continuous task every 9 ms (of continuous task time), as illustrated below. Legend: Task executes. Task is interrupted (suspended). periodic 1 ms 1 ms system overhead 9 ms 9 ms continuous task 0 elapsed time (ms) 5 10 15 20 25 What is DriveLogix5730? 1-11 The interruption of a periodic task increases the elapsed time (clock time) between the execution of system overhead, as shown below. 1 ms 1 ms 1 ms 1 ms 1ms periodic task 1 ms 1 ms system overhead 9 ms of continuous task time 9 ms of continuous task time continuous task 0 5 10 15 20 25 elapsed time (ms) If you increase the time slice to 20%, the system overhead interrupts the continuous task every 4 ms (of continuous task time). 1 ms 1 ms 1 ms 1 ms 1 ms system overhead 4 ms 4 ms 4 ms 4 ms 4 ms continuous task 5 10 15 20 25 elapsed time (ms) If you increase the time slice to 50%, the system overhead interrupts the continuous task every 1 ms (of continuous task time). 1 ms system overhead 1 ms continuous task 5 10 15 20 25 elapsed time (ms) If the controller only contains a periodic task(s), the system overhead timeslice value has no effect. System overhead runs whenever a periodic task is not running. periodic task system overhead 5 continuous task elapsed time (ms) 10 15 20 25 1-12 What is DriveLogix5730? Understanding the Virtual Backplane The DriveLogix5730 system has a five-slot virtual backplane. The controller, drive and other components occupy different assigned slots on the backplane. Slot 0 DrvieLogix5730 Controller Slot 1 Embedded EtherNet Option Virtual Backplane Slot 2 PowerFlex 700S Drive Slot 3 Compact I/O Slot 4 NetLinx Daughtercard Chapter 2 Placing and Configuring the Drive De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of placing and configuring the drive you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with placing and configuring the drive. Understanding the Interface The DriveLogix controller supports a direct connection to the drive consisting of 21 inputs and 21 outputs. The tag names and data types to the Drive associated with the inputs and outputs are determined by the communication format selection. Currently, the following five communications formats are available: • • • • • Speed Control – for typical speed regulated applications Position Control – for typical positioning applications Motion Control - for use with Logix motion commands User-Defined 1 – for general use as required. User-Defined 2 - for general use as required. Each communication format contains a number of pre-defined tags and user-defined tags. The pre-defined tag names and data types correspond with the associated parameters, within the drive’s firmware, that are necessary to support the selected communications format. Links must be established in the firmware, using DriveExecutive software, to support the pre-defined tags. Linking is a software mechanism that configures data flow within the drive’s firmware. The links within the firmware to support the pre-defined tags are protected 2-2 Placing and Configuring the Drive and must be present. If the associated links are not present, or are deleted, the communication connection between the controller and drive will be lost. The user-defined tags are made up of a fixed number of REAL (floating point) and DINT (double integer) data types. Links are not required within the drive’s firmware to support these tags. Therefore, links may be created and deleted as desired without having an affect on the communication connection between the controller and the drive. The user-defined tags may be used to address application specific data needs not covered by the pre-defined tags. Mapping for Inputs and Outputs For each of the 21 inputs and 21 outputs, there is a dedicated parameter within the drive, for a total of 42 parameters. Selecting a communication format defines the data types for each input and output. It also determines the data type for the dedicated parameter in the drive. The selection also configures parameters 601 [From DL DataType] and 625 [To DL DataType], which indicate the data types for each dedicated parameter within the drive. The DriveLogix controller follows a producer/consumer model for the drive Determining When the Controller Updates the Drive connection, similar to the interface to an I/O module. The drive acts as both an input module, producing data for the controller; and an output module, consuming data from the controller. Although the producer/consumer model multi-casts data, all data in the drive connection is exclusive to the DriveLogix controller. The controller updates the input and output data in the drive connection asynchronously to the logic scan, consistent with the way it handles other I/ O data. All input data from the drive is read in a single block and all output data is written to the drive in a single block. You must configure the Requested Packet Interval (RPI) rate for the drive. This setting affects how fast the controller reads and writes the data in the drive interface. TIP: If you want data to remain constant throughout one scan, make a copy of the data at the beginning of the scan and use the copy throughout the scan. The Drive consumes data from the DriveLogix controller every 2 milliseconds, and produces data to the controller every 2 milliseconds. The drive updates the inputs and outputs to the controller asynchronous to both the program scan and I/O scan of the controller. Placing and Configuring the Drive 2-3 Placing and Configuring the When you create a project for the DriveLogix controller in RSLogix 5000, the Controller Organizer automatically displays the local DIN rail for Drive Compact I/O. You must add the PowerFlex 700S drive to the configuration, in a manner similar to adding an I/O module. The Controller Organizer automatically places the drive in slot two. In the Controller Organizer, select the I/O Configuration folder. Right-click the selected folder and select New Module. Select the drive (PowerFlex 700S 2-400V in this example). ahw0772.tif 2. ahw0771.tif 1. Important: You must select the correct voltage rating for the drive, when adding the drive. You can find this on the drive data nameplate. 2-4 Placing and Configuring the Drive Select the Major Revision. 4. Configure the drive. Use the module properties wizard to specify characteristics for the module. Click Next to continue through the wizard. 5. Name the drive and specify the Comm Format. Click finish when you are done. The completed module appears in the Controller Organizer. ahw0774.tif ahw0773.tif 3. The selection you make for the Comm Format determines the communication format for the connection to the drive. This determines the tag names and data types. See page 2-5. Once you complete adding a module, you cannot change this selection. Electronic Keying ahw0775.tif Electronic keying has no effect on drive module. However, the default setting (Compatible Module) is recommended. Selecting “Compatible Module” allows you to enter the drive firmware minor revision. Placing and Configuring the Drive 2-5 Revision ahw0776.tif You must enter the correct drive VPL firmware revision, in order to launch DriveExecutive and create the appropriate links for the selected communication format. Determine the firmware revision by viewing parameter 314 [VPL Firmware Rev] in the drive. Communication Formats The communication format determines the data structure, tag names, and required links for communication to the drive. Each communication format has been structured to meet the requirements of a specific type of application (Speed Control, Position Control, or general purpose), and supports a different data structure. The links within the PowerFlex 700S required to support the selected format are also different. Any of the available communication formats create one direct connection to the drive. ahw0777.tif You select the communication format when you configure the drive module. The default communication format for the drive is Speed Control. The tags are created as controller-scoped tags. The following tag structure shows the Placing and Configuring the Drive Speed Control format. The tag structure for this example’s drive connection has the tag name of “drive_module”. ahw0778.tif 2-6 The following tables show the tag names and their relationship to parameters in the drive. These examples use a module name of “drive_module”. Table 2.A Mapping for Speed Control Communication Format Controller Output Tag Element LogicCommand SpeedRef1 TorqueRef1 SpdTorqModeSelect TorqueStep SpdRegDroop UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] Drive Parameter 602 [FromDriveLogix00] 603 [FromDriveLogix01] 604 [FromDriveLogix02] 605 [FromDriveLogix03] 606 [FromDriveLogix04] 607 [FromDriveLogix05] 608 [FromDriveLogix06] 609 [FromDriveLogix07] 610 [FromDriveLogix08] 611 [FromDriveLogix09] 612 [FromDriveLogix10] 613 [FromDriveLogix11] 614 [FromDriveLogix12] 615 [FromDriveLogix13] 616 [FromDriveLogix14] 617 [FromDriveLogix15] 618 [FromDriveLogix16] 619 [FromDriveLogix17] 620 [FromDriveLogix18] 621 [FromDriveLogix19] 622 [FromDriveLogix20] Linked Parameter 151 [Logic Command] 10 [Speed Ref 1] 111 [Torque Ref 1] 110 [Speed/TorqueMode] 116 [Torque Step] 86 [Spd Reg Droop] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Controller Input Tag Element LogicStatus FilteredSpdFdbk MotorTorqueRef OutputCurrent MCStatus LocalIOStatus UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] Drive Parameter 626 [To DriveLogix00] 627 [To DriveLogix01] 628 [To DriveLogix02] 629 [To DriveLogix03] 630 [To DriveLogix04] 631 [To DriveLogix05] 632 [To DriveLogix06] 633 [To DriveLogix07] 634 [To DriveLogix08] 635 [To DriveLogix09] 636 [To DriveLogix10] 637 [To DriveLogix11] 638 [To DriveLogix12] 639 [To DriveLogix13] 640 [To DriveLogix14] 641 [To DriveLogix15] 642 [To DriveLogix16] 643 [To DriveLogix17] 644 [To DriveLogix18] 645 [To DriveLogix19] 646 [To DriveLogix20] Linked Parameter 155 [Logic Status] 71 [Filtered SpdFdbk] 303 [Motor Torque Ref] 308 [Output Current] 555 [MC Status] 824 [Local I/O Status] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Placing and Configuring the Drive Table 2.B Mapping for Position Control Communication Format Controller Output Tag Element LogicCommand SpeedRef1 PositionControl CoarsePositTrgt PtPtPositRef PositOffset1 UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] Drive Parameter 602 [FromDriveLogix00] 603 [FromDriveLogix01] 604 [FromDriveLogix02] 605 [FromDriveLogix03] 606 [FromDriveLogix04] 607 [FromDriveLogix05] 608 [FromDriveLogix06] 609 [FromDriveLogix07] 610 [FromDriveLogix08] 611 [FromDriveLogix09] 612 [FromDriveLogix10] 613 [FromDriveLogix11] 614 [FromDriveLogix12] 615 [FromDriveLogix13] 616 [FromDriveLogix14] 617 [FromDriveLogix15] 618 [FromDriveLogix16] 619 [FromDriveLogix17] 620 [FromDriveLogix18] 621 [FromDriveLogix19] 622 [FromDriveLogix20] Linked Parameter 151 [Logic Command] 10 [Speed Ref 1] 740 [Position Control] 748 [CoarsePosit Trgt] 758 [Pt-Pt Posit Ref] 753 [Posit Offset 1] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Controller Input Tag Element LogicStatus FilteredSpdFdbk OutputCurrent LocalIOStatus PositionStatus PositionFdbk PositionActual PositionError UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] UserDefinedIntegerData[6] Drive Parameter 626 [To DriveLogix00] 627 [To DriveLogix01] 628 [To DriveLogix02] 629 [To DriveLogix03] 630 [To DriveLogix04] 631 [To DriveLogix05] 632 [To DriveLogix06] 633 [To DriveLogix07] 634 [To DriveLogix08] 635 [To DriveLogix09] 636 [To DriveLogix10] 637 [To DriveLogix11] 638 [To DriveLogix12] 639 [To DriveLogix13] 640 [To DriveLogix14] 641 [To DriveLogix15] 642 [To DriveLogix16] 643 [To DriveLogix17] 644 [To DriveLogix18] 645 [To DriveLogix19] 646 [To DriveLogix20] Linked Parameter 155 [Logic Status] 71 [Filtered SpdFdbk] 308 [Output Current] 824 [Local I/O Status] 741 [Position Status] 762 [Position Fdbk] 763 [Position Actual] 769 [Position Error] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined 2-7 2-8 Placing and Configuring the Drive Table 2.C Mapping for Motion Control Communication Format Controller Output Tag Element UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedRealData[10] UserDefinedRealData[11] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] UserDefinedIntegerData[6] UserDefinedIntegerData[7] UserDefinedIntegerData[8] Drive Parameter 602 [FromDriveLogix00] 603 [FromDriveLogix01] 604 [FromDriveLogix02] 605 [FromDriveLogix03] 606 [FromDriveLogix04] 607 [FromDriveLogix05] 608 [FromDriveLogix06] 609 [FromDriveLogix07] 610 [FromDriveLogix08] 611 [FromDriveLogix09] 612 [FromDriveLogix10] 613 [FromDriveLogix11] 614 [FromDriveLogix12] 615 [FromDriveLogix13] 616 [FromDriveLogix14] 617 [FromDriveLogix15] 618 [FromDriveLogix16] 619 [FromDriveLogix17] 620 [FromDriveLogix18] 621 [FromDriveLogix19] 622 [FromDriveLogix20] Linked Parameter User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Controller Input Tag Element LogicStatus UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedRealData[10] UserDefinedRealData[11] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] UserDefinedIntegerData[6] UserDefinedIntegerData[7] Drive Parameter 626 [To DriveLogix00] 627 [To DriveLogix01] 628 [To DriveLogix02] 629 [To DriveLogix03] 630 [To DriveLogix04] 631 [To DriveLogix05] 632 [To DriveLogix06] 633 [To DriveLogix07] 634 [To DriveLogix08] 635 [To DriveLogix09] 636 [To DriveLogix10] 637 [To DriveLogix11] 638 [To DriveLogix12] 639 [To DriveLogix13] 640 [To DriveLogix14] 641 [To DriveLogix15] 642 [To DriveLogix16] 643 [To DriveLogix17] 644 [To DriveLogix18] 645 [To DriveLogix19] 646 [To DriveLogix20] Linked Parameter 155 [Logic Status] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Placing and Configuring the Drive Table 2.D Mapping for User-Defined 1 Communication Format Controller Output Tag Element LogicCommand UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedRealData[10] UserDefinedRealData[11] UserDefinedRealData[12] UserDefinedRealData[13] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] Drive Parameter 602 [FromDriveLogix00] 603 [FromDriveLogix01] 604 [FromDriveLogix02] 605 [FromDriveLogix03] 606 [FromDriveLogix04] 607 [FromDriveLogix05] 608 [FromDriveLogix06] 609 [FromDriveLogix07] 610 [FromDriveLogix08] 611 [FromDriveLogix09] 612 [FromDriveLogix10] 613 [FromDriveLogix11] 614 [FromDriveLogix12] 615 [FromDriveLogix13] 616 [FromDriveLogix14] 617 [FromDriveLogix15] 618 [FromDriveLogix16] 619 [FromDriveLogix17] 620 [FromDriveLogix18] 621 [FromDriveLogix19] 622 [FromDriveLogix20] Linked Parameter 151 [Logic Command] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Controller Input Tag Element LogicStatus UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedRealData[10] UserDefinedRealData[11] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] UserDefinedIntegerData[6] UserDefinedIntegerData[7] Drive Parameter 626 [To DriveLogix00] 627 [To DriveLogix01] 628 [To DriveLogix02] 629 [To DriveLogix03] 630 [To DriveLogix04] 631 [To DriveLogix05] 632 [To DriveLogix06] 633 [To DriveLogix07] 634 [To DriveLogix08] 635 [To DriveLogix09] 636 [To DriveLogix10] 637 [To DriveLogix11] 638 [To DriveLogix12] 639 [To DriveLogix13] 640 [To DriveLogix14] 641 [To DriveLogix15] 642 [To DriveLogix16] 643 [To DriveLogix17] 644 [To DriveLogix18] 645 [To DriveLogix19] 646 [To DriveLogix20] Linked Parameter 155 [Logic Status] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined 2-9 2-10 Placing and Configuring the Drive Table 2.E Mapping for User-Defined 2 Communication Format Controller Output Tag Element LogicCommand UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedRealData[10] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] UserDefinedIntegerData[6] UserDefinedIntegerData[7] UserDefinedIntegerData[8] Drive Parameter 602 [FromDriveLogix00] 603 [FromDriveLogix01] 604 [FromDriveLogix02] 605 [FromDriveLogix03] 606 [FromDriveLogix04] 607 [FromDriveLogix05] 608 [FromDriveLogix06] 609 [FromDriveLogix07] 610 [FromDriveLogix08] 611 [FromDriveLogix09] 612 [FromDriveLogix10] 613 [FromDriveLogix11] 614 [FromDriveLogix12] 615 [FromDriveLogix13] 616 [FromDriveLogix14] 617 [FromDriveLogix15] 618 [FromDriveLogix16] 619 [FromDriveLogix17] 620 [FromDriveLogix18] 621 [FromDriveLogix19] 622 [FromDriveLogix20] Linked Parameter 151 [Logic Command] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined Controller Input Tag Element LogicStatus UserDefinedRealData[0] UserDefinedRealData[1] UserDefinedRealData[2] UserDefinedRealData[3] UserDefinedRealData[4] UserDefinedRealData[5] UserDefinedRealData[6] UserDefinedRealData[7] UserDefinedRealData[8] UserDefinedRealData[9] UserDefinedIntegerData[0] UserDefinedIntegerData[1] UserDefinedIntegerData[2] UserDefinedIntegerData[3] UserDefinedIntegerData[4] UserDefinedIntegerData[5] UserDefinedIntegerData[6] UserDefinedIntegerData[7] UserDefinedIntegerData[8] UserDefinedIntegerData[9] Drive Parameter 626 [To DriveLogix00] 627 [To DriveLogix01] 628 [To DriveLogix02] 629 [To DriveLogix03] 630 [To DriveLogix04] 631 [To DriveLogix05] 632 [To DriveLogix06] 633 [To DriveLogix07] 634 [To DriveLogix08] 635 [To DriveLogix09] 636 [To DriveLogix10] 637 [To DriveLogix11] 638 [To DriveLogix12] 639 [To DriveLogix13] 640 [To DriveLogix14] 641 [To DriveLogix15] 642 [To DriveLogix16] 643 [To DriveLogix17] 644 [To DriveLogix18] 645 [To DriveLogix19] 646 [To DriveLogix20] Linked Parameter 155 [Logic Status] User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined User Defined For each of the communication formats, drive_module:O.LogicCommand and drive_module:I.LogicStatus are provided as DINT data types. In addition to these tags, the control bits for each are also available as Boolean values with tag names that correspond to the control bits in the drive. This gives you the option of programming the Logic Command and Status words at the Boolean level or as an integer value. Not all 32-bits within parameter 151 [Logic Command], are directly visible in the PowerFlex 700S. To view all 32-bits, refer to parameter 152 [Applied LogicCmd]. Placing and Configuring the Drive Inhibiting the Drive Connection 2-11 RSLogix 5000 programming software allows you to inhibit the controller’s connection to the drive, in the same way you inhibit its connection to an I/O module. Inhibiting the drive module shuts down the connection from the controller to the drive. When you create the module you can choose to inhibit it. After you have created the module you can inhibit or un-inhibit it by manipulating its properties window. ! ATTENTION: Inhibiting a drive module breaks the controller’s connection to the drive. In this situation, the controller can neither start or stop the drive, nor read the status of the drive. The drive can continue to operate based on its parameter settings and inputs. To avoid potential personal injury and damage to machinery, make sure this does not create unsafe operation. On the Connection tab during creation or in the Properties window ahw0779.tif Check the inhibit box to inhibit the connection to the drive When you inhibit the drive module, the Controller Organizer displays a yellow attention symbol ! over the module. If you are: offline Inhibit the drive module to: put a place holder for the drive module to indicate that configuration is not yet complete. online The inhibit status is stored in the project. When you download the project, the module is still inhibited. stop communication to the drive. If you inhibit the drive while you are connected to the module, the connection to the module is closed. By default, the PowerFlex 700S drive will fault. The data inputs to the drive will either hold last state, or reset to zero data based on the setting of parameter 385 [Lgx CommLossData]. If you inhibit the drive but a connection to the module was not established (perhaps due to an error condition or fault), the module is inhibited. The module status information changes to indicate that the module is inhibited and not faulted. If you uninhibit the drive (clear the check box), and no fault condition occurs, a connection is made to the drive. To inhibit a module from logic, you must first read the Mode attribute for the module using a GSV instruction. Set bit 2 to the inhibit status (1 to 2-12 Placing and Configuring the Drive ahw0514.tif inhibit or 0 to uninhibit). Use a SSV instruction to write the Mode attribute back to the module. For example: Using DriveExecutive Lite If not already done, enter the drive firmware revision. Click the Finish button to apply the revision data. ahw0779.tif 1. In order to launch DriveExecutive Lite from within RSLogix 5000, the drives power rating must be selected. The drive firmware revision must be applied prior to selecting the power rating. Placing and Configuring the Drive In the Controller Organizer, select the PowerFlex 700S drive. Right-click the drive module and select Properties. 3. Select the Power tab. 4. Select the correct Drive Rating. This data can be found on the PowerFlex 700S data nameplate. ahw0781.tif ahw0780.tif 2. 2-13 TIP: If your drive’s power rating does not appear as a selection, you do not have the DriveExecutive Lite database file for your drive. To create a database file, connect to the drive with DriveExecutive Lite. This will automatically create the database. You can also download the database file from http://www.ab.com/drives/data.html 2-14 Placing and Configuring the Drive Once the power rating is selected, apply your changes by selecting the Apply button. 6. Select the Setup tab. 7. Enter the file name for your DriveExecutive Lite parameter file, then click the Apply button. 8. Click the DriveExecutive button to launch DriveExecutive Lite. ahw0785.tif ahw0782.tif ahw0784.tif 5. Placing and Configuring the Drive When asked to create a new DriveExecutive Lite file, select yes. ahw0786.tif DriveExecutive will then launch and open the newly created file ahw0787.tif 9. 2-15 2-16 Placing and Configuring the Drive Viewing the Communication Interface to the Controller DriveExecutive Lite has a setup screen that details the communication interface between the controller and drive. From this screen, the relationship between drive parameters and controller tags is presented for the selected communication format. You can create additional links within the drive for use with the user-defined tags in the controller. To view the setup screen select Display DriveLogix from the Drive drop-down menu. Then select the From DriveLogix tab. ahw0789.tif ahw0788.tif 1. Placing and Configuring the Drive ahw0790.tif To send additional data from the drive to the controller, go to the To DriveLogix tab. Click the button in front of the UserDefinedRealData[0] tag ahw0791.tif 2. 2-17 3. Select the desired source (parameter 307 [Output Voltage] in this example) in the resulting window. Configuring the Drive’s Response to a Connection Failure or Controller Mode Change The drive contains several parameters that allow you to configure the drive’s response to communication loss to the controller. From the drive’s perspective, a communication loss can come in the following two forms. • The controller closes the connection (for example, the connection is inhibited). • A general failure occurs causing the connection to time out. Parameter 386 [Lgx OutofRunCnfg] configures the drive’s response to the controller is removed from the Run Mode. Parameter 387 [Lgx Timeout 2-18 Placing and Configuring the Drive Cnfg] configures the drive’s response to a general connection failure as detected by the drive. Parameter 388 [Lgx Closed Cnfg] configures the drive’s response to the controller closing the connection. All of these parameters configure the drive’s response to these exception events in the following ways: ignore, alarm, fault and coast to stop, fault and ramp to stop, fault and stop in current limit. Parameter 385 [Lgx CommLossData] determines what the drive does with data from the controller when communication is lost. It determines if the drive resets the data to zero or holds the data in its last state. ahw0792.tif Configure these parameters, using DriveExecutive Lite. Locate them in the Fault/Alm Config group of the Utility file. Placing and Configuring the Drive 2-19 Using Existing DriveExecutive Lite Files Before using an existing DriveExecutive Lite file, verify the firmware revision, communication format, and power rating in the drive file match the data entered in drive module properties in your DriveLogix application. Select Properties from the Drive menu. ahw0793.tif 2. View the revision and ratings on the General tab of the Properties window. ahw0794.tif 1. 3. Refer to Viewing the Communication Interface to the Controller on page 2-16, to view the communication format. 2-20 Placing and Configuring the Drive In RSLogix 5000, go to the Setup tab of the Properties window. Click the Browse button. Select the existing DriveExecutive file (Existing Drive.dno in this example). Click the open button. ahw0795.tif ahw0785.tif 4. ahw0796.tif Click the Apply button and then launch DriveExecutive. ahw0797.tif 5. Placing and Configuring the Drive Accessing Drive Data 2-21 Drive data is displayed as structures of multiple tags. The names and data structures are based on the selected communication format. The programming software automatically creates the necessary structures and tags when you configure the drive module. Each tag name follows this format: ModuleName:Type.MemberName.SubMemberName.Bit where: This address variable: Is: ModuleName Identifies the module name entered during the drive module configuration Type Type of data I = input O = output MemberName Specific data from the drive; depends on the selected communication format. For tags associated with pre-defined data links, this name will be the same as the corresponding parameter name in the drive. SubMemberName Specific data related to a MemberName Bit (optional) Specific bit of a DINT data value Refer to Communication Formats on page 2-5 for sample tag names. Monitoring Drive Data The DriveLogix controller offers different levels at which you can monitor the drive module. You can: • configure the drive module so that the controller faults if the drive loses its connection to the controller. • use the programming software to display fault data • program logic to monitor fault data so you can take appropriate action 2-22 Placing and Configuring the Drive ahw0798.tif Configuring the Controller’s You can configure the drive module to generate a major fault in the Response to a Connection controller if the drive loses its connection to the controller. Failure Check this box to configure the drive module to generate a major fault if it loses its connection to the controller If you do not configure the major fault to occur, you should monitor the drive module status. If the drive loses its connection to the controller: • Outputs remain in their last • Inputs remain in their last state • By default the drive will fault ! ATTENTION: If a drive loses its connection to the controller, the controller and other I/O modules continue to operate based on old data from the drive, and the drive can continue to operate based on old data from the controller. To avoid potential personal injury and damage to machinery, make sure this does not create unsafe operation. Configure the drive to generate a controller major fault when the drive loses its connection to the controller. Or, monitor the status of the drive module. Placing and Configuring the Drive 2-23 Monitoring the drive module Each communication format provides a drive status word that will indicate when a drive fault or alarm occurs. To view this data through the programming software: In the Controller Organizer, select Controller Tags. Right-click on the selected icon and select Monitor Tags. ahw0799.tif 1. Expand the data as necessary. ahw0800.tif 2. Placing and Configuring the Drive You can write logic to monitor these bits and take appropriate action if a fault or alarm occurs. For example, you may want a drive alarm to turn on a warning lamp and a drive fault to sound an alarm and set the motor brake. Example: Energizing Alarm Lamp, Siren and Brake in Response to Fault and Alarm Status Bits ahw0801.tif Given this configuration, the following logic checks the fault and alarm drive status bits. ahw0802.tif 2-24 Placing and Configuring the Drive Recommended Programming Techniques Naming Tags Use a convention when naming tags and consistently follow it. The following convention is used internally at Allen-Bradley: <prefix>_<function>_<suffix> Prefix - identifies the machine section in multi section programs Prefix examples: Sct1 = Section 1 Fan2 = Fan 2 RewA = Rewind A Function - describes the function or signal Function examples: SpdRef = Speed Reference FaultState = Status of a fault Suffix - identifies the units of the signal or control status Suffix examples: Rpm = Rotations per Minute Ok = status OK Off = contact Off Full tag examples: Sct2_SpdRef_Fpm = Speed Reference, in feet per minute, on Section 2 Fan5_FaultState_OK = Status of fault, where 1 = OK, on Fan 5 TIP: Add descriptions for each tag when creating the tag 2-25 2-26 Placing and Configuring the Drive Use Aliasing for all Communication Format Connections Between DriveLogix and the PowerFlex 700S Using aliases for the tags in the Communication Format (i.e. Speed Control, Motion Control, Position Control, User-Defined 1 and User-Defined 2) has the following benefits: • Improves program portability over processors and through upgrades to DriveLogix, PowerFlex 700S, and RSLogix 5000 firmware. • Allows real names to be applied to the User Defined tags of the static assembly. • Allows new functions of DriveLogix and the PowerFlex 700S to be clearly named in the program even if RSLogix 5000 has not been updated. • Allows long tag names in RSLogix 5000 to be shortened for easier program viewing. • Allows tags to be named using the above naming convention to identify machine section association. Apply aliases to all external connections including the PowerFlex 700S Communication Format and I/O. All defined bits should be included. Use "Periodic Tasks" to optimize processor utilization. Name periodic tasks to identify the update time (e.g. Periodic_020ms_P9 = 20ms task with priority 9). Set the periodic task time appropriate programming requirements. Important: Remember that tasks with faster the task times consume more processor bandwidth than those with slower task times. Set the priority of each task to coincide with the task speed. Set faster tasks to higher priority. Important: Remember lower priority numbers define higher priorities (e.g. a task with a priority number of 9 has a higher priority than one with a priority of 10). Important: Do not set the priority number lower than 8 (the recommended priority range is 8-15). This will provide I/O scanning with optimal updating. Flex I/O and Compact I/O are coded as priority 7 for DriveLogix. Chapter 3 Placing and Configuring Local I/O De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of placing and configuring I/O you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with placing and configuring the I/O. The DriveLogix5730 controller supports up to 2 banks of modules with a maximum of 8 modules per bank. You must distribute the modules within each bank so that no more than 4 modules are on either side of the power supply. ahw0803.eps Understanding How the DriveLogix5730 Supports I/O Power Module I/O Modules I/O Modules Placing and Configuring Local I/O Refer to the Compact I/O Selection Guide, publication 1769-SG001, for information about selecting Compact I/O modules. Use the 20D-DL2-CR3 or 20D-DL2-CL3 cables to connect a DriveLogix5730 controller to a bank of Compact I/O. Use 1769-CRR1/-CRR3 or 1769-CRL1/-CRL3 expansion cable to connect banks of I/O modules. You can split a bank right after the power supply or after any I/O module. Each bank must contain one power supply. An end cap/terminator must be used on the last I/O bank opposite of the expansion cable. Only the local DriveLogix5730 controller can scan the local Compact I/O. ! ATTENTION: The Compact I/O system does not support Removal and Insertion Under Power (RIUP). While the DriveLogix / Compact I/O is under power: • any break in the connection between the power supply and the controller (i.e. removing the power supply, controller, or an I/O module) may subject the logic circuitry to transient conditions above the normal design thresholds and may result in damage to system components or unexpected behavior. • removing an end cap or a module fault may fault the controller. A 20D-DL2-CL3 cable connects the controller to the left side of an I/O bank. A 20D-DL2-CR3 cable connects the controller to the right side of an I/O bank. 20D-DL2-CL3 ahw0805.eps Placing Local I/O Modules ahw0804.eps 3-2 20D-DL2-CR3 Placing and Configuring Local I/O 3-3 20D-DL2-CL3 ahw0808.eps ahw0806.eps A 1769-CRL1/-CRL3 connects the left side of one bank of Compact I/O to the right side of another. This facilitates a horizontal I/O orientation. 1769-CRLX 1769-CRLX 20D-DL2-CR3 ahw0809.eps ahw0807.eps A 1769-CLL1/-CLL3 connects the left side of one bank of Compact I/O to the left side of another. A 1769-CRR1/-CRR3 connects the right side of one bank of Compact I/O to the right side of another. This facilitates a vertical I/O orientation. 20D-DL2-CL3 20D-DL2-CR3 1769-CRRX Validating I/O Layout 1769-CLLX To validate your planned I/O layout, consider these requirements: • Each module in a Compact I/O system uses a set amount of backplane memory, in addition to the data that the module stores or transfers. As you add modules, the minimum backplane RPI increases. • The I/O modules must be distributed such that the current consumed from the left or right side of the power supply never exceeds 2.0A at 5V dc and 1.0A at 24V dc. 3-4 Placing and Configuring Local I/O Estimating RPI As you install modules, the minimum backplane RPI increases. The RPI (request packet interval) defines the frequency at which the controller sends and receives all I/O data on the backplane. There is one RPI for the entire 1769 backplane. Consider these guidelines when installing modules: Type of Module: Considerations: digital and analog (any mix) • 1-4 modules can be scanned in 1.0 ms • 5-16 modules can be scanned in 1.5 ms • some input modules have a fixed 8.0 ms filter, so selecting a faster RPI has no affect specialty • “full-sized” 1769-SDN modules add 1.5 ms per module • 1769-HSC modules add 0.5 ms per module You can always select an RPI that is slower than listed above. These considerations show how fast modules can be scanned - not how fast an application can use the data. The RPI is asynchronous to the program scan. Other factors, such as program execution duration, affect I/O throughput. Determining When the Controller Updates I/O The controller continually scans the control logic. One scan is the time it takes the controller to execute the logic once. Input data transfers to the controller and output data transfers to output modules are asynchronous to the logic scan. TIP: If you need to ensure that the I/O values being used during logic execution are from one moment in time (such as at the beginning of a ladder program), use the Synchronous Copy instruction (CPS) to buffer I/O data. Refer to the Logix5000 Controllers Common Procedures Programming Manual, publication number 1756-PM001 for examples of I/O buffering or to the Logix5000 Controllers General Instruction Set Reference Manual, publication number 1756-RM003 for information on the CPS instruction. Placing and Configuring Local I/O Configuring the CompactBus In the Controller Organizer, select CompactBus Local icon. Right click and select Properties. ahw0810.tif ahw0811.tif 1. When you create a DriveLogix5730 project, the programming software automatically creates the local CompactBus. You must configure the CompactBus. 3-5 Placing and Configuring Local I/O On the General tab, specify the size of the chassis. Enter the number of modules you plan to install. Include the DriveLogix5730 controller and drive in this total, along with a maximum of 16 I/O modules, not including the power supply. The Comm Format for the CompactBus is automatically set to Rack Optimized and cannot be changed. Using the Connection tab, you can specify the RPI for the systems and choose to inhibit or uninhibit the CompactBus. ahw0812.tif 3-6 The RPI you specify here is the RPI for every 1769 module on this controller’s local CompactBus. Specify an RPI from 1-750ms for the system. You do not specify individual RPI values for each module. By inhibiting and uninhibiting the CompactBus, you can write new configuration data to the entire system at once. The controller’s response to a CompactBus connection failure is dependant upon the Compact I/O modules configuration. The checkbox which indicates that the controller will fault should be ignored - for the CompactBus adapter. Furthermore, if any Compact I/O module is configured to fault the module on connection loss, any Compact I/O module fault will cause the controller to fault. Placing and Configuring Local I/O Configuring Local I/O Modules Use your programming software to configure the I/O modules for the controller. In the Controller Organizer, select CompactBus Local icon. Right click and select New Module. 2. Select the new module (1769-IA16 in this example). ahw0815.tif ahw0813.tif ahw0814.tif 1. 3. Configure the module, using the module wizard to specify characteristics. Click Next to advance the wizard. Click Finish when you are done. The completed module will appear in the Controller Organizer. 3-7 Placing and Configuring Local I/O Communication Formats The communication format determines the data structure the I/O module uses. Each format supports a different data structure. Presently, the DriveLogix5730 controller supports two data formats: • Input Data – INT (for 1769 input modules) • Data – INT (for 1769 output modules) TIP: The DriveLogix5730 controller must own its local I/O modules. No other Logix-based controller can own the local Compact I/O. The communication format determines the tag structure that is created for the module. Assume that a 1769-IA16 Input module is in slot 1. The software creates the appropriate tags using the slot number to differentiate the tags for this example module from any other module. ahw0816.tif 3-8 Hold Last State and User-Defined Safe State Not Supported ! ATTENTION: Risk of injury or equipment damage exists. When 1769 Compact I/O modules are used as local I/O modules in a DriveLogix5730 system, the local I/O modules do not support the Hold Last State or User-Defined Safe State features, even though you can configure these options in the programming software. Precautions should be taken to ensure that these settings do not create a hazard of injury or equipment damage. When a compact I/O module is configured to do so, it will cause the controller to go into a faulted mode when the compact I/O module fails and communication to the controller is lost, or the compact I/O module is Placing and Configuring Local I/O 3-9 disconnected from the system bus while under power. All outputs turn off when the system bus or any module faults. RSLogix 5000 software creates tags for modules when you add them to the I/O configuration. The 1769 module tags define configuration (C) data type members which may include attributes for alternate outputs. DriveLogix5730 does not enable local modules to use the alternate outputs. Do not configure the attributes listed below: For digital output modules: For analog output modules: • • • • • • • • • ProgToFaultEn ProgMode ProgValue FaultMode FaultValue CHxProgToFaultEn CHxProgMode CHxFaultMode where CHx = the channel number Any 1769 Compact I/O modules used as remote I/O modules in a DriveLogix5730 system do support the Hold Last State and User-Defined Safe State features. Inhibiting I/O Module Operation In some situations, such as when initially commissioning a system, it is useful to disable portions of a control system and enable them as you wire up the control system. The controller lets you inhibit individual modules or groups of modules, which prevents the controller from trying to communicate with these modules. Inhibiting a module shuts down the connection from the controller to that module. When you create an I/O module, it defaults to being not inhibited. You can change an individual module’s properties to inhibit a module. ! ATTENTION: Inhibiting a module causes the connection to the module to be broken and prevents communication of I/O data. The controller and other I/O modules continue to operate based on old data from that module. To avoid potential injury and damage to machinery, make sure this does not create unsafe operation. Placing and Configuring Local I/O On the Connection tab of the Module Properties dialog, you can select to inhibit that specific module. ahw0817.tif 3-10 TIP: To easily inhibit all local I/O modules, you can inhibit the CompactBus, which in turn inhibits all the modules on that bus. See Configuring the CompactBus on page 3-5. When you select to inhibit a module, the controller organizer displays a yellow circle symbol over the module. If you are: Inhibit a module to: offline put a place holder for a module you are configuring. The inhibit status is stored in the project. When you download the project, the module is still inhibited. online stop communication to a module. If you inhibit a module while you are connected to the module, the connection to the module is closed. The module’s outputs turn off. If you inhibit a module but a connection to the module was not established (perhaps due to an error condition or fault), the module is inhibited. The module status information changes to indicate that the module is inhibited and not faulted. If you uninhibit a module (clear the check box), and no fault condition occurs, a connection is made to the module and the module is dynamically reconfigured with the configuration you created for that module. If you uninhibit the module and a fault condition occurs, a connection is not made to the module. The module status information changes to indicate the fault condition. To inhibit a module from logic, you must first read the Mode attribute for the module using a GSV instruction. Set bit 2 to the inhibit status (1 to Placing and Configuring Local I/O 3-11 inhibit or 0 to uninhibit). Use a SSV instruction to write the Mode attribute back to the module. For example: The GSV instruction gets the current status of the module named “input_module.” The SSV instruction sets the state of “input_module” as either inhibited or uninhibited. GSV ladder.tif When on, inhibits the module. When off, uninhibits the module. Sending Module Configuration Information The controller sends module configuration information once module connections are established. ! ATTENTION: If you make a configuration change to any module in the system do one of the following to resend module configuration data: • cycle power to the controller • inhibit and then uninhibit the bus • inhibit and then uninhibit the individual module • send a MSG instruction of type Module Reconfigure (for information on configuring a MSG to send configuration data, see the Logix5000 Controllers General Instructions Reference Manual, publication 1756-RM003) 3-12 Placing and Configuring Local I/O Configuring the Controller’s Response to a Connection Failure In a DriveLogix5730 system, the controller’s response to a CompactBus connection failure is dependant on the setting of the individual compact I/O modules. ahw0817.tif Important: The controller’s response to a connection failure of any I/O module is dependant on the configuration of the I/O modules. If any I/O module has the "Major Fault On Controller If Connection Fails While in Run Mode" checkbox selected, the controller will fault on any I/O fault. The I/O modules respond to a connection failure by turning off output. Accessing I/O Data The programming software displays I/O data as structures of multiple tags that depend on the specific features of the I/O module. The names of the data structures are based on the location of the I/O module. The programming software automatically creates the necessary structures and tags when you configure the module. Each tag name follows this format: Location:SlotNumber:Type.MemberName.SubMemberName.Bit where: This address variable: Is: Location Identifies network location LOCAL = local chassis SlotNumber Slot number of I/O module in its chassis Type Type of data I = input O = output C = configuration Placing and Configuring Local I/O 3-13 This address variable: Is: MemberName Specific data from the I/O module; depends on the type of data the module can store For example, Data and Fault are possible fields of data for an I/O module. Data is the common name for values that are sent to or received from I/O points. SubMemberName Specific data related to a MemberName. Bit (optional) Specific point on the I/O module; depends on the size of the I/O module (0-31 for a 32-point module) The following examples show addresses for data in a DriveLogix5730 system. Example: ahw0818.eps I/O module on the local CompactBus utilizing two banks 1 2 Bank 1 3 4 5 Bank 2 3-14 Placing and Configuring Local I/O Sample tag names for this example: Location: Example Tag Name: input module in slot 1, LOCAL Bank 1 Local:1:C Local:1:I output module in slot 2, LOCAL Bank 1 Local:2:C Local:2:I Local:2:O analog input module in slot 3, LOCAL Bank 2 Local:3:C Local:3:I analog output module in slot 4, LOCAL Bank 2 Local:4:C Local:4:I Local:4:O analog input module in slot 5, LOCAL Bank 2 Local:5:C Local:5:I Using aliases to simplify tag names An alias lets you create a tag that represents another tag. This is useful for defining descriptive tag names for I/O values. For example: Example: Direct Connections for I/O Modules Description: I/O structure Local:1:I:Data[0].0 Local:1:I:Fault.0 alias light_on = Local:1:I:Data[0].0 module_failed = Local:1:I:Fault.0 The aliases describe the specific I/O points. Each local I/O module uses a direct connection to the DriveLogix5730 controller. A direct connection is a real-time, data transfer link between the controller and an I/O module. The controller maintains and monitors the connection between the controller and the I/O module. Any break in the connection, such as a module fault, causes the controller to set fault status bits in the input data area associated with the module. ! ATTENTION: The DriveLogix5730 controller does not support Removal and Insertion Under Power (RIUP). While the DriveLogix5730 system is under power: • any break in the connection between the power supply and the controller (i.e. removing the power supply, controller, or an I/ O module) may subject the logic circuitry to transient conditions above the normal design thresholds and may result in damage to system components or unexpected behavior. • removing an end cap or an I/O module may fault the controller and may also result in damage to system components. Placing and Configuring Local I/O Monitoring I/O Modules 3-15 The DriveLogix5730 controller offers different levels at which you can monitor I/O modules. You can: • use the programming software to display fault data (See Displaying Fault Data on page 3-15) • program logic to monitor fault data so you can take appropriate action (Refer to Logix5000 Controllers Common Procedures Programming Manual, publication number 1756-PM001, for examples.) Displaying Fault Data Fault data for certain types of module faults can be viewed through the programming software. ahw0819.tif To view this data, select Controller Tags in the Controller Organizer. Right-click to select Monitor Tags. 3-16 Placing and Configuring Local I/O The display for the fault data defaults to decimal. Change it to Hex to read the fault code. fault_word.eps If the module faults, but the connection to the controller remains open, the controller tags database displays the fault value 16#0E01_0001. The fault word uses this format: 31 27 23 19 15 11 Fault_Code_Value reserved FaultCode 7 3 0 reserved FaultInfo 0 = connection open 1 = connection closed } Connection_Closed Fault_Bit Where: Bit Description Fault_Bit This bit indicates that at least one bit in the fault word is set (1). If all the bits in the fault word are cleared (0), this bit is cleared (0). Connection_Closed This bit indicates whether the connection to the module is open (0) or closed (1). If the connection is closed (1), the Fault_Bit it set (1). ahw0817.tif You can also view module fault data on the Connection tab of the Module Properties screen. See your 1769 module’s user documentation for a description of module faults. To recover from module faults, correct the module fault condition and send new data to the module by downloading the user program with configuration data, inhibiting and then uninhibiting the module, or cycling power. Placing and Configuring Local I/O 3-17 End-cap Detection and Module Faults If a module that is not adjacent to an end cap experiences a fault and the connection to the controller is not broken, only the module enters the fault state. If a module that is adjacent to an end cap experiences a fault, the module will fault and the controller may fault. 2. In the Controller Organizer, select CompactBus Local icon. Right click and select New Module. Select the 1769-MODULE (Generic 1769 Module). ahw0820.tif 1. Use the Generic 1769 Module only when a 1769 I/O module does not appear in the list of modules to add to the Controller Organizer. To configure a 1769 I/O module for a DriveLogix5730 controller using the generic 1769-MODULE: ahw0813.tif Configuring I/O Modules Using the Generic 1769-MODULE 3-18 Placing and Configuring Local I/O ahw0821.tif 3.Configure the module, using the module wizard to specify characteristics. Click Next to advance the wizard. Click Finish when you are done. The completed module will appear in the Controller Organizer. The generic module requires you to specify more parameters of the module. Important: The values you enter for these parameters are device specific. See the documentation for the device to determine which values to enter. On the generic module screen, you define the parameters of the module. In this field: Specify: Name name of the module Description (optional) provide more details about the module Comm Format communication format 1769 analog output modules, digital output modules, analog combination modules, and digital combination modules, use Data – INT. 1769 analog input modules and digital input modules use Input Data – INT. Slot slot placement of the module on the CompactBus Connection Parameters Input Output Configuration connection information unique to the module The documentation for module should list the assembly instance and size numbers for the input, output, and configuration parameters. Placing and Configuring Local I/O 3-19 Entering the Configuration Information for the Module Once you configure a module using the generic 1769-MODULE, you must enter the configuration information for the module into the tag database. The configuration information is downloaded to the module at program download, power up, and whenever a module is inhibited and then uninhibited. In the Controller Organizer, double-click on Controller Tags. 2. Edit the tags for the module so that the tags contain the appropriate configuration ahw0822.tif ahw0823.tif 1. The generic module was added to slot 3, so you want to enter configuration data into the Local:3:C tags. RSLogix 5000 programming software automatically create tags for configured I/O modules. All local I/O addresses are preceded by the word Local. These addresses have the following format: • Input Data: Local:s:I • Output Data: Local:s:O • Configuration Data: Local:s:C Where s is the slot number assigned the I/O module. Open the configuration tag for that module by clicking on the plus sign to the left of its configuration tag in the tag database. The configuration information depends on the module. See the documentation on the I/O module for the appropriate configuration information. 3-20 Notes: Placing and Configuring Local I/O Chapter 4 Configuring DriveLogix Motion De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of configuring DriveLogix motion you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with configuring DriveLogix motion. About this Chapter This chapter introduces DriveLogix5730 motion. The steps in this chapter provide the minimum settings required to begin testing DriveLogix motion. System Requirements • • • • PowerFlex 700S Phase II Drive with firmware revision 2.XX or higher DriveLogix5730 Controller with firmware revision 15.XX or higher DriveExecutive programming software version 3.02 or higher RSLogix 5000 programming software version 15 or higher 4-2 Configuring DriveLogix Motion Programming the Controller In RSLogix 5000, create a new project. 1. From the File menu, select New. 2. In the New Controller dialog define the project: a. Use Revision 15 or higher. b. Enter a Name for the project (e.g., Motion_Drive). c. Click the OK button. Configuring DriveLogix Motion 3. In the Controller Organizer: a. Right-click on the I/O Configuration folder. b. Select New Module from the menu. 4. In the Select Module dialog, click the plus sign (+) next to Drives to expand the selection. 4-3 4-4 Configuring DriveLogix Motion 5. Select the desired drive (PowerFlex 700S 2-400V in this example) and click the OK button. 6. In the Major Revision dialog: a. Select the Major Revision number and click the OK button. 7. Configure the Drive by specifying the characteristics of the module using the New Module dialog: a. Enter a name for the drive in the Name field (Drive_Axis in this example). a. Select Motion Control in the Comm Format box. b. Verify that the Open Module Properties box is checked. c. Click the OK button. Configuring DriveLogix Motion 4-5 8. On the Connections tab of the Modules Properties dialog: a. Change the value on the Requested Packet Interval (RPI) box to 3.0 ms. b. Click on the Associated Axis tab and click the New Axis button to assign a channel to Axis00. c. In the New Tag dialog, create a new tag structure for Axis00 by typing Axis00 in the Name field and clicking the OK button. d. On the Associated Axis tab, click the New Axis button to assign a channel to Axis01. 4-6 Configuring DriveLogix Motion e. In the New Tag dialog, create a new tag structure for Axis01 by typing Axis01 in the Name field and clicking the OK button. f. On the Associated Axis tab, click the drop-down arrow next to Channel 0 (Primary) and select Axis00. g. On the Associated Axis tab, click the drop-down arrow next to Channel 1 (Auxiliary) and select Axis01. Configuring DriveLogix Motion 9. Click on the Power tab and select the proper Drive Rating. 10. Click the Apply button. 11. Click the OK button. 12. Create a new Motion Group. a. In the Controller Organizer, right-click on Motion Groups. b. Select New Motion Group from the menu. 4-7 4-8 Configuring DriveLogix Motion c. Enter a Name for the Motion Group (Grouped_Axis in this example). d. Verify that the Open MOTION_GROUP Configuration box is checked. e. Click on the OK button. 13. In the Motion Group Wizard dialog, move each axis from the Unassigned box to the Assigned box by clicking on the axis name and then clicking the Add button. 14. Click the Next button. Configuring DriveLogix Motion 4-9 15. Finish creating the new Motion Group: a. Set the Coarse Update Period to 4ms for version 13.xx or lower, or to 2ms for version 15.xx or higher. This is the minimum time usable with DriveLogix motion. b. Set the Auto Tag Update to Enabled. c. Set the General Fault Type to Non Major Fault. d. Click the Finish button. 16. Configure Axis00. a. Right click on the axis you want to configure (Axis00 in this example). b. Select Properties in the menu. 4-10 Configuring DriveLogix Motion 17. On the General tab: a. Associate the module with the drive. Match the Module name with the drive’s name in the I/O Configuration. b. Set the Channel to the channel being used for the encoder. Channel 0 must be selected for the Servo axis and Channel 1 can be used only for feedback. 18. On the Motion Planner tab, determine how many Output Cam execution nodes (instances) are created for a specific axis The value specified for Output Cam Execution Target in the MAOC instruction references a specific instance in which a value of zero selects the first instance. Configuring DriveLogix Motion 4-11 19. On the Units tab, define the Position Units. In this example the Position Units are revs (revolutions). Position Units can be almost anything (e.g. degrees, radians, pallets, widgets etc.). 20. Define Average Velocity Timebase as the sample rate that is used for the Average Velocity tag in the controller tags. 21. On the Conversion tab, setup the Positioning Mode for Linear to Rotary. 22. The Conversion Constant is the number of feedback counts per Position Unit. 4-12 Configuring DriveLogix Motion 23. On the Dynamics tab, define the limits for speed, acceleration, and deceleration. Important: Do not exceed the system dynamics. 24. On the Homing tab, setup the Homing Mode, Position, Offset and Sequence values. Refer to the following tables. Mode Active - the desired homing sequence is selected by specifying whether a home limit switch and/or the encoder marker are used for this axis. Active homing sequences always use the trapezoidal velocity profile. Passive - homing redefines the absolute position of the axis on the occurrence of a home switch or encoder marker event. Passive homing is most commonly used to calibrate uncontrolled axes, although it can also be used with controlled axes to create a custom homing sequence. Passive homing, for a given home sequence, works similar to the corresponding active homing sequence, except that no motion is commanded; the controller just waits for the switch and marker events to occur. Position Type the desired absolute position, in position units, for the axis after the specified homing sequence has been completed. In most cases, this position will be set to zero, although any value within the software travel limits can be used. After the homing sequence is complete, the axis is left in this position. If the Positioning Mode (set in the Conversion tab) of the axis is Linear, then the home position should be within the travel limits, if enabled. If the Positioning Mode is Rotary, then the home position should be less than the unwind distance in position units. Configuring DriveLogix Motion Offset Type the desired offset (if any) in position units the axis is to move, upon completion of the homing sequence, to reach the home position. In most cases, this value will be zero. Sequence Select the event that will cause the Home Position to be set: Sequence Type Description Immediate Sets the Home Position to the present actual position, without motion. Switch Sets the Home Position when axis motion encounters a home limit switch. Marker Sets the Home Position when axis encounters an encoder marker. Switch-Marker Sets the Home Position when axis first encounters a home limit switch, then encounters an encoder marker. 4-13 Important: Selecting a Homing Sequence event will configure parameters 825 [Dig In1 Sel] and 826 [Dig In2 Sel] in the host PowerFlex 700S drive. Limit Switch If a limit switch is used, indicate the normal state of that switch (i.e., before being engaged by the axis during the homing sequence): Normally Open Normally Closed Direction For active homing sequences, except for the Immediate Sequence type, select the desired homing direction: Forward Uni-directional The axis jogs in the positive axial direction until a homing event (switch or marker) is encountered, then continues in the same direction until axis motion stops (after decelerating or moving the Offset distance). Forward Bi-directional The axis jogs in the positive axial direction until a homing event (switch or marker) is encountered, then reverses direction until motion stops (after decelerating or moving the Offset distance). Reverse Uni-directional The axis jogs in the negative axial direction until a homing event (switch or marker) is encountered, then continues in the same direction until axis motion stops (after decelerating or moving the Offset distance). Reverse Bi-directional The axis jogs in the negative axial direction until a homing event (switch or marker) is encountered, then reverses direction until motion stops (after decelerating or moving the Offset distance). 25. When you have completed defining the axis, click the Apply, then the OK button. 26. Configure Axis01 by repeating the tasks in Steps 16 - 25. Important:Only Channel 0 will function for a Servo axis. Channel 1 may be used for a Feedback Only axis. 27. Save the RSLogix 5000 project and download it to the controller. ! ATTENTION: Running the system without proper tuning can cause unstable and unpredictable operation. To avoid potential personal injury and damage to machinery, determine the proper values for system dynamics and tune the system before beginning operation. 4-14 Configuring DriveLogix Motion Launching DriveExecutive from RSLogix Next open the drive properties window and launch DriveExecutive drive programming software. ahw0869.tif 1.In the Controller Organizer, select the PowerFlex 700S drive. Right-click the drive module and select Properties ahw0870.tif That will launch the Module Properties Window for the drive. Click on the Setup tab. Configuring DriveLogix Motion 2.Type the desired DriveExecutive filename or browse for an existing one. ahw0872.tif ahw0871.tif Then click Apply. 3.Click the Launch DriveExecutive button to launch DriveExecutive Lite. 4-15 4-16 Configuring DriveLogix Motion Configuring the Drive with DriveExecutive Software In DriveExecutive software, connect to the drive and access the Display DriveLogix dialog as shown below: ahw0824.tif 1.From the Drive Menu, select Display DriveLogix. ahw0825.tif 2.Click on the From DriveLogix tab. 3.Verify that the Communication Format is set to Motion Control. Click OK to apply and close the DriveLogix Setup Dialog. Next link the appropriate parameters to the words being produced and consumed by the controller. 5.Click on the Link Source tab. 6.Type or select the desired Source parameter. ahw0826.tif 4.On the Links view, double-click on the desired Sink parameter. 4-17 ahw0827.tif Configuring DriveLogix Motion 4-18 Configuring DriveLogix Motion Create the links in the table below: Table 4.A Parameter Links for DriveLogix Motion Configuration Destination (Sink) Parameter 12 [Speed Ref 2] Source Parameter 751 [Interp Speed] 22 [Speed Trim 2] 318 [Posit Spd Output] 23 [Speed Trim 3] 55 [Speed Comp] 626 [To DriveLogix00] 155 [Logic Status] 693 [Intrep SyncInput] 700 [Motn Posit Sync] 748 [CoarsePosit Trgt] 698 [Motn Posit Cmmd] 750 [Coarse Spd Trgt] 699 [Motn Mx Pos Trvl] Description Speed reference from the Coarse to Fine Interpolator, to Speed Ref 2 This is a default link. It connects the position regulator in the drive to the velocity loop. This setup is for speed compensation to reduce position error. The status of the drive is sent to the DriveLogix. The drive receives the synchronization pulse from the DriveLogix. This keeps the interpolators synchronized. The position interpolator of the drive receives the coarse position target from the DriveLogix Motion Interpolator The Speed loop of the drive receives the coarse velocity target from the DriveLogix Motion Interpolator ahw0828.tif Next, make the appropriate parameter settings. 7.On the Parameters view, double-click on the desired parameter. 4-19 ahw0829.tif Configuring DriveLogix Motion 8.Type the desired value. Make the parameter settings shown in the table below: Table 4.B Parameter Settings for DriveLogix Motion Configuration Parameter 13 [Spd Ref2 Multi] 24 [Spd Trim 3 Scale] 27 [Speed Ref A Sel] 146 [FW TaskTime Sel](1) 147 [FW Functions En] 151 [Logic Command] 222 [Motor Fdbk Sel Pri] 600 [Lgx Comm Format] 686 [Motn Config] 701 [FdbkAxis FdbkSel] 740 [Position Control] 742 [Position Ref Sel] 824 [Local I/O Status] 904 [SL Node Cnfg] (1) (1) Value 1 0.003 2 0 16 = 1 Bit 0 = 1 Bit10 = 1 Bit13 = 1 0-6 Description Speed Ref 2 scale value Speed Trim 3 scale value Select Speed Ref 2 as the speed reference Firmware Task Time Selection. Position Control enabled Bit 0 bypasses the speed ramp in the drive Bit 10 enables Inertia Comp Bit 13 enables the position loop within the drive. Select the Motor Speed Feedback being used. This is also the feedback for the Servo Axis in DriveLogix Motion Group 19 This selects the format of the commands coming from DriveLogix Bits 0 - 2 Bit 0 = Change the polarity of the feedback only feedback axis Bit 1 = Enable Software Overtravel Limits Bit 2 = Enable Hardware Overtravel Limits 1 – 10 This selects the feedback channel used for the “Feedback Only axis” in the Motion Group in DriveLogix. Encoders, Optional Feedback, and SynchLink selections. See User Manual for details. Bit 1 = 1 This sets the position regulator to work with the DriveLogix Bit 6 = 0 configuration and enables the Integral part of the regulator Bit 2 = 1 Bit 8 = 0 0 This configures the drive position loop to receive position commands from DriveLogix via the Interpolator Bit 0 = 0 Eliminate erroneous physical axis faults Bit 1 = 1 Bit 0 =1 This sets up the SynchLink as the time keeper. This is used to synchronize the Drive and DriveLogix. Changes to these parameters require a drive reset before the changes will take effect. The HIM will indicate “Reset Req’d” on the status line. 4-20 Configuring DriveLogix Motion Downloading the Settings and Links to the Drive ahw0873.tif 1.From the Drive Menu, select Display Download. 2.Using the resulting windows and RSLinx navigate to the drive and download the settings and links. Additional Testing and Programming is Necessary The steps in this chapter provide the minimum settings required to begin testing DriveLogix motion. ! ATTENTION: Running the system without proper tuning can cause unstable and unpredictable operation. To avoid potential personal injury and damage to machinery, determine the proper values for system dynamics and tune the system before beginning operation. You must perform testing to determine the actual system dynamics and tune the drive. In addition, you must create ladder logic that uses the Logix Motion Instructions. Refer to Supported Motion Commands on page 4-21 and publication 1756-RM007, Reference Manual - Logix Controller Motion Instruction Set. ! ATTENTION: There is no default Position Error Fault logic in this system. To avoid potential personal injury and damage to machinery, detect Position Error faults, by using parameter links and ladder logic. Configuring DriveLogix Motion Supported Motion Commands 4-21 The following Logix Motion Instructions are supported by the DriveLogix controller: Motion State • • • • • MSO (Motion Servo On) MSF (Motion Servo Off) MASD (Motion Axis Shutdown) MASR (Motion Axis Shutdown Reset) MAFR (Motion Axis Fault Reset) Motion Move • • • • • • • • • • MAJ (Motion Axis Jog) MAM (Motion Axis Move) MAS (Motion Axis Stop) MAH (Motion Axis Home) MAG (Motion Axis Gearing) MCD (Motion Change Dynamics) MRP (Motion Redefine Position) MCCP (Motion Calculate Position Profile) MAPC (Motion Axis Position Cam) MATC (Motion Axis Time Cam) Motion Event • • • • • • MAW (Motion Arm Watch) MDW (Motion Disarm Watch) MAR (Motion Arm Registration) MDR (Motion Disarm Registration) MAOC (Motion Arm Output Cam) MDOC (Motion Disarm Output Cam) Motion Group • • • • MGS (Motion Group Stop) MGSD (Motion Group Shutdown) MGSR (Motion Group Shutdown Reset) MGSP (Motion Group Strobe Position) 4-22 Notes: Configuring DriveLogix Motion Chapter 5 Communicating with Devices on a Serial Link De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of configuring serial communication you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with configuring serial communication. Configuring Your System for For the DriveLogix controller to operate on a serial network, you need: a Serial Link • a workstation with a serial port • RSLinx software to configure the serial communication driver • RSLogix 5000 programming software to configure the serial port of the controller Important: Limit the length of serial (RS-232) cables to 15.2m (50 ft.). Communicating with Devices on a Serial Link Configuring the Hardware The RS-232 port is an isolated serial port built-in to the front of the Main Control Board. Refer to Opening Door Over Power Structure and Main Control Board on page B-2. ahw0914.eps Serial Port To connect to the serial port: 1. Select the appropriate cable. The 1756-CP3 cable attaches the controller directly to the controller. 1 CD 1 CD 2 RDX 2 RDX 3 TXD 3 TXD 4 DTR 4 DTR COMMON COMMON 6 DSR 6 DSR 7 RTS 7 RTS 8 CTS 8 CTS 9 9 40046.eps 5-2 If you make your own cable, it must be shielded and the shields must be tied to the metal shell (that surrounds the pins) on both ends of the cable. You can also use a 1747-CP3 cable (from the SLC product family). This cable has a taller right-angle connector housing than the 1756-CP3 cable. 2. Connect the cable to the serial port on the controller. Communicating with Devices on a Serial Link Configuring the Serial Port of the Controller 1. In the Controller Organizer, select the Controller folder. Right-click the selected folder and select Properties. On the Serial tab, specify serial port characteristics. ahw0915.tif ahw0916.tif 2. Characteristic: Description (default is shown in bold): Mode Select System (for DF1 communication) or User mode (for ASCII communication). Baud rate Specifies the communication rate for the serial port. Select a baud rate that all devices in your system support. Select 110, 300 600, 1200, 2400, 4800, 9600, 19200, or 38400 Kbps. Parity Specifies the parity setting for the serial port. Parity provides additional message-packet error detection. Select None or Even. Data bits Specifies the number of bits per message packet. Select 8. Stop bits Specifies the number of stop bits to the device with which the controller is communicating. Select 1 or 2. Control line Specifies the mode in which the serial driver operates. Select No Handshake, Full-Duplex, Half-Duplex with Continuous Carrier, or Half-Duplex without Continuous Carrier. If you are not using a modem, select No Handshake If both modems in a point-to-point link are full-duplex, select Full-Duplex for both controllers. 5-3 5-4 3. Communicating with Devices on a Serial Link On the System Protocol tab, select the appropriate DF1 communication mode for point-to-point or master/slave communications. ahw0918.tif ahw0917.tif Or use the User Protocol tab to specify ASCII protocol to communicate to an ASCII device. Use this mode: For: See page: DF1 point-to-point communication between the controller and one other DF1-protocol-compatible device. This is the default system mode. This mode is typically used to program the controller through its serial port. 5-6 DF1 master mode control of polling and message transmission between the master and slave nodes. The master/slave network includes one controller configured as the master node and as many as 254 slave nodes. Link slave nodes using modems or line drivers. A master/slave network can have node numbers from 0-254. Each node must have a unique node address. Also, at least 2 nodes must exist to define your link as a network (1 master and 1 slave station are the two nodes). 5-9 DF1 slave mode using a controller as a slave station in a master/slave serial communication network. When there are multiple slave stations on the network, link slave stations using modems or line drivers. When you have a single slave station on the network, you do not need a modem to connect the slave station to the master; you can configure the control parameters for no handshaking. You can connect 2-255 nodes to a single link. In DF1 slave mode, a controller uses DF1 half-duplex protocol. One node is designated as the master and it controls who has access to the link. All the other nodes are slave stations and must wait for permission from the master before transmitting. 5-8 User mode communicating with ASCII devices This requires your program logic to use the ASCII instructions to read and write data from and to an ASCII device. 5-12 Important: Half-Duplex settings do not work as with other Logix controllers. RTS and CTS are not functional. Communicating with Devices on a Serial Link 5-5 Configuring the Communication Driver Use RSLinx software to configure the serial communication driver. Select the “DF1” driver. 1. In the Communications menu, select the Configure Driver. Specify a name for the driver and click OK. 3. Specify the appropriate communication settings. ahw0483.tif ahw0484.tif 2. ahw0482.tif ahw0481.tif From the Available Driver Type list select the DF1 Driver, then click Configure. 5-6 Communicating with Devices on a Serial Link In the following example, a workstation directly connects to a DriveLogi5730 controller over a serial link. This is useful for downloading a controller project directly to the controller. ahw0919.eps Example 1: Workstation Directly Connected to a DriveLogix Controller Use RSLogix 5000 programming software to configure the controller’s serial port for the DF1 point-to-point (full-duplex) protocol. This type of protocol supports simultaneous transmission between two devices in both directions. The DF1 point-to-point protocol controls message flow, detects and signals errors, and retries if errors are detected. Configuring a DF1 Point-to-Point Station This field: Description: Station address The station address for the serial port on the DF1 point-to-point network. Enter a valid DF1 address (0-254). Address 255 is reserved for broadcast messages. The default is 0. NAK receive limit Specifies the number of NAKs the controller can receive in response to a message transmission. Enter a value 0-127. The default is 3. ENQ transmit limit Specifies the number of inquiries (ENQs) you want the controller to send after an ACK timeout. Enter a value 0-127. The default is 3. ACK timeout Specifies the amount of time you want the controller to wait for an acknowledgment to its message transmission. Enter a value 0-32767. Limits are defined in 20ms intervals. The default is 50 (1000ms). Embedded response Specifies how to enable embedded responses. Select Autodetect (enabled only after receiving one embedded response) or Enabled. The default is Autodetect. Error detection Select BCC or CRC error detection. Configure both stations to use the same type of error checking. BCC: the controller sends and accepts messages that end with a BCC byte for error checking. BCC is quicker and easier to implement in a computer driver. This is the default. CRC: the controller sends and accepts messages with a 2-byte CRC for error checking. CRC is a more complete method. Enable duplicate detection Select whether or not the controller should detect duplicate messages. The default is duplicate detection enabled. Communicating with Devices on a Serial Link In the following example, a workstation remotely connects to a DriveLogix controller over s serial link. A modem is connected to the controller to provide remote access. ahw0920.eps Example 2: Workstation Remotely Connected to a DriveLogix Controller 5-7 modem modem If you use a modem to remotely connect the controller to one workstation, use RSLogix 5000 programming software to configure the serial port of the controller for the DF1 point-to-point (full-duplex) protocol, as in the previous example. If the controller is part of a master/slave serial network, configure the serial port of the controller for either the DF1 master or DF1 slave protocol (both half-duplex). 5-8 Communicating with Devices on a Serial Link Master/Slave Communication Methods A master station can communicate with a slave station in two ways: Name: This method: Benefits: standard communication mode Initiates polling packets to slave stations according to their position in the polling array(s). Polling packets are formed based on the contents of the normal poll array and the priority poll array. This communication method is most often used for point-to-multipoint configurations. This method provides these capabilities: • slave stations can send messages to the master station (polled report-by-exception) • slave stations can send messages to each other via the master • master maintains an active station array The poll array resides in a user-designated data file. You can configure the master: • to send messages during its turn in the poll array or • for between-station polls (master transmits any message that it needs to send before polling the next slave station) In either case, configure the master to receive multiple messages or a single message per scan from each slave station. message-based communication mode initiates communication to slave stations using only user-programmed message (MSG) instructions. Each request for data from a slave station must be programmed via a MSG instruction. The master polls the slave station for a reply to the message after waiting a user-configured period of time. The waiting period gives the slave station time to formulate a reply and prepare the reply for transmission. After all of the messages in the master’s message-out queue are transmitted, the slave-to-slave queue is checked for messages to send. If your application uses satellite transmission or public switched-telephone-network transmission, consider choosing message-based communication. Communication to a slave station can be initiated on an as-needed basis. Also choose this method if you need to communicate with non-intelligent remote terminal units (RTUs). Configuring a DF1 Slave Station This field: Description: Station address The station address for the serial port on the DF1 slave. Enter a valid DF1 address (0-254). Address 255 is reserved for broadcast messages. The default is 0. Transmit retries The number of times the remote station retries a message after the first attempt before the station declares the message undeliverable. Enter a value 0-127. The default is 3. Slave poll timeout Specifies the amount of time the slave station waits to be polled by a master before indicating a fault. Enter a value 0-32767. Limits are defined in 20ms intervals. The default is 3000 (60,000ms). EOT suppression Select whether or not to suppress sending EOT packets in response to a poll. The default is not to suppress sending EOT packets. Error detection Select BCC or CRC error detection. Configure both stations to use the same type of error checking. BCC: the controller sends and accepts messages that end with a BCC byte for error checking. BCC is quicker and easier to implement in a computer driver. This is the default. CRC: the controller sends and accepts messages with a 2-byte CRC for error checking. CRC is a more complete method. Enable duplicate detection Select whether or not the controller should detect duplicate messages. The default is duplicate detection enabled. Communicating with Devices on a Serial Link 5-9 Configuring a DF1 Master Station This field: Description: Station address The station address for the serial port on the DF1 master. Enter a valid DF1 address (0-254). Address 255 is reserved for broadcast messages. The default is 0. Transmit retries Specifies the number of times a message is retried after the first attempt before being declared undeliverable. Enter a value 0-127. The default is 3. ACK timeout Specifies the amount of time you want the controller to wait for an acknowledgment to its message transmission. Enter a value 0-32767. Limits are defined in 20ms intervals. The default is 50 (1000ms). Reply message wait Message-based polling mode only Specifies the amount of time the master station waits after receiving an ACK to a master-initiated message before polling the slave station for a reply. Enter a value 0-65535. Limits are defined in 20ms intervals. The default is 5 (100ms). Polling mode Select one of these: • Message Based (slave cannot initiate messages) • Message Based (slave can initiate messages) - default • Standard (multiple message transfer per node scan) • Standard (single message transfer per node scan) Master transmit Standard polling modes only Select when the master station sends messages: • between station polls (default) • in polling sequence Normal poll node tag Standard polling modes only An integer tag array that contains the station addresses of the slave stations. Create a single-dimension array of data type INT that is large enough to hold all the normal station addresses. The minimum size is three elements. This tag must be controller-scoped. The format is: list[0] contains total number of stations to poll list[1] contains address of station currently being polled list[2] contains address of first slave station to poll list[3] contains address of second slave station to poll list[n] contains address of last slave station to poll Normal poll group size Standard polling modes only The number of stations the master station polls after polling all the stations in the priority poll array. Enter 0 (default) to poll the entire array. Priority poll node tag Standard polling modes only An integer tag array that contains the station addresses of the slave stations you need to poll more frequently. Create a single-dimension array of data type INT that is large enough to hold all the priority station addresses. The minimum size is three elements. This tag must be controller-scoped. The format is: list[0] contains total number of stations to be polled list[1] contains address of station currently being polled list[2] contains address of first slave station to poll list[3] contains address of second slave station to poll list[n] contains address of last slave station to poll Active station tag Standard polling modes only An array that stores a flag for each of the active stations on the DF1 link. Both the normal poll array and the priority poll array can have active and inactive stations. A station becomes inactive when it does not respond to the master’s poll. Create a single-dimension array of data type SINT that has 32 elements (256 bits). This tag must be controller-scoped. Error detection Select BCC or CRC error detection. Configure both stations to use the same type of error checking. BCC: the controller sends and accepts messages that end with a BCC byte for error checking. BCC is quicker and easier to implement in a computer driver. This is the default. CRC: the controller sends and accepts messages with a 2-byte CRC for error checking. CRC is a more complete method. Enable duplicate detection Select whether or not the controller should detect duplicate messages. The default is duplicate detection enabled. 5-10 Communicating with Devices on a Serial Link If you choose one of the standard polling modes The master station polls the slave stations in this order: 1. all stations that are active in the priority poll array 2. one station that is inactive in the priority poll array 3. the specified number (normal poll group size) of active stations in the normal poll array 4. one inactive station, after all the active stations in the normal poll array have been polled Use the programming software to change the display style of the active station array to binary so you can view which stations are active. In the following example, a workstation connects to a bar code reader. A bar code reader is an ASCII device, so you configure the serial port differently than in the previous examples. Configure the serial port for user mode, rather than a DF1 mode. ahw0921.eps Example 3: DriveLogix Controller to a Bar Code Reader scanner Communicating with Devices on a Serial Link 5-11 Connecting the ASCII Device to the Controller To connect the ASCII device to the serial port of the controller: 1. For the serial port of the ASCII device, determine which pins send signals and which pins receive signals. 2. Connect the sending pins to the corresponding receiving pins and attach jumpers: If the communications: handshake do not handshake Then wire the connectors as follows: ASCII Device Controller 1 CD 1 2 RDX 2 RDX 3 TXD 3 TXD 4 DTR 4 DTR COMMON COMMON 6 DSR 6 DSR 7 RTS 7 8 CTS 8 9 9 ASCII Device Controller 1 CD 1 2 RDX 2 RDX 3 TXD 3 TXD 4 DTR 4 DTR COMMON COMMON 6 DSR 6 DSR 7 RTS 7 8 CTS 8 9 9 3. Attach the cable shield to both connectors and tie the cable to both connectors. 4. Connect the cable to the controller and the ASCII device. The following table lists the default serial port configuration settings for the ASCII protocol. You specify these settings on the User Protocol tab under Controller Properties. 5-12 Communicating with Devices on a Serial Link Configuring User Mode This field: Description: Buffer size Specify the maximum size (in bytes) of the data array you plan to send and receive. The default is 82 bytes. Termination characters Specify the characters you will use to designate the end of a line. The default characters are ‘$r’ and ‘$FF’. Append characters Specify the characters you will append to the end of a line. The default characters are ‘$r’ and ‘$l’. XON/XOFF Select whether or not to regulate the flow of incoming data. The default is disabled. Echo mode Select whether or not to echo data back to the device from which it was sent. The default is disabled. Delete mode Select Ignore, CTR, or Printer for the delete mode. The default is Ignore. Programming ASCII instructions The controller supports ASCII instructions to communicate with ASCII devices. Your RSLogix 5000 programming software CDROM includes programming examples using ASCII instructions. For information about using these examples, see the Logix5000 Controllers Reference Manual, publication 1756-RM001. Chapter 6 Communicating with Devices on an EtherNet/IP Link De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of configuring EtherNet/IP communication you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with configuring EtherNet/IP communication. 6-2 Communicating with Devices on an EtherNet/IP Link Communicating Through the Embedded EtherNet/IP Option For the DriveLogix controller to operate on an Ethernet network, you need: • a workstation with an appropriate EtherNet/IP communication daughtercard • RSLinx software to configure the EtherNet/IP communication driver • RSLogix 5000 programming software (Version 13 or later) to configure the embedded EtherNet/IP option or NetLinx EtherNet/IP communication daughtercard as part of the DriveLogix system • an embedded EtherNet/IP option card installed on the DriveLogix controller (refer to Installing the Embedded EtherNet/IP Option Board on page B-7) or • a 1788-ENBT EtherNet/IP communication daughtercard installed on the DriveLogix controller (refer to Installing the Communications Daughtercard on page B-9) DriveLogix controller with 1788-ENBT Communications Daughtercard ahw0938.eps EtherNet/IP ! DriveLogix controller with Embedded EtherNet/IP Option Card or EtherNet/IP EtherNet/IP Determining Network Settings Before configuring the system you must determine several network settings. In the Run dialog box of Windows, type “cmd”. ahw0884.tif 2. At the Command Prompt, type “ipconfig”, and note the values for the network settings. ahw0875.tif 1. Communicating with Devices on an EtherNet/IP Link 6-3 Assigning Network Parameters with BOOTP/DHCP The EtherNet/IP Option board ships with BOOTP enabled. You must assign an IP address to the Ethernet port in order for the controller to communicate over an EtherNet/IP network. The BOOTP/DHCP utility is a stand alone program that is located in the: • BOOTP-DHCP Server folder in the Rockwell Software program folder on the Start menu (the utility is automatically installed when you install RSLinx software) • Tools directory on the RSLogix 5000 installation CD. The computer running the BOOTP/DHCP utility and the DriveLogix5730 controller must be on the same EtherNet/IP network. To use the BOOTP/DHCP utility: Start the BOOTP/DHCP software. From the Tools menu, select Network Settings. Note: If you have not run the BOOTP/DHCP program before, it will automatically launch the Network Settings window. ahw0858.tif ahw0861.tif 1. 2. 3. Enter the required data. Click OK. In the Request History panel you see the hardware addresses of devices issuing BOOTP requests. Double-click on the hardware address of the device you want to configure. ahw0859.tif 5. The New Entry window appears with the device’s Ethernet Address (MAC). Enter the Ethernet address, IP address, subnet mask, and gateway. Click OK. Note: The selected controller will verify that the IP address that has been assigned in this dialog does not belong to another device on the network. If the IP address exists, a warning message will display. The new entry then appears in the Relation List. ahw0876.tif 4. Communicating with Devices on an EtherNet/IP Link ahw0860.tif 6-4 Communicating with Devices on an EtherNet/IP Link 6. 6-5 To permanently assign this configuration to the device, highlight the device and click on the Disable BOOTP/DHCP button. When power is recycled, the device uses the configuration you assigned and not issue a BOOTP request. ahw0885.tif Important: If you do not select the Disable BOOTP/DHCP button, on a power cycles and drive resets, the controller clears the current IP configuration and will again begin sending BOOTP requests. Click Disable BOOTP/ DHCP. Highlight the device Other methods to assign network parameters include: If you are working in these conditions: • a BOOTP server is not available Use this method for assigning network parameters: See page: RSLinx software 6-6 RSLogix 5000 software 6-7 • the EtherNet/IP module is connected to another NetLinx network • the RSLogix 5000 project is online with the controller that communicates to or through the EtherNet/IP module If you use the Rockwell Software BOOTP or DHCP server in an up-linked subnet where an enterprise DHCP server exists, a module may get an address from the enterprise server before the Rockwell Automation utility even sees the module. You might have to disconnect from the uplink to set the address and have the module remember its static address before reconnecting to the uplink. 6-6 Communicating with Devices on an EtherNet/IP Link Using RSLinx Software to Set the IP Address Via the Controller Serial Port You need RSLinx software version 2.41 or higher. 1. Make sure the controller that uses the IP address is installed and running. 2. Make a serial connection to the controller via the CH0 serial connector. You might also need to use RSLinx software to create a DF1 driver for the workstation. See Chapter 5 for more information. 3. Start RSLinx. Open the RSWho window. Navigate in RSWho to the Ethernet network. ahw0874.tif 4. Right-click on the Ethernet port (not the controller) and select Module Configuration 5. Select the Port Configuration tab, choose Static Network Configuration type, and enter the IP address, network (subnet) mask, and gateway address (if needed). You must leave the Static radio button selected to permanently assign this configuration to the port. If you select Dynamic, the controller clears its IP configuration and sends BOOTP requests on every power cycle and drive reset. Note: The selected controller will verify that the IP address that has been assigned in this dialog does not belong to another device on the network. If the IP address exists, a warning message will display. ahw0878.tif Click OK. Communicating with Devices on an EtherNet/IP Link Using RSLogix 5000 Software to Set the IP Address 1. 2. Create a new offline project, with the drive and any other necessary components. In the Controller Organizer, select the I/O Configuration folder. Right-click the selected folder and select New Module. Important: You must create an offline project and download it to the controller before going online. If the controller is already programmed, skip these first three steps. Select a DriveLogix5730 Ethernet Port from the list of possible communication devices. Click OK. ahw0905.tif ahw0904.tif ahw0903.tif 3. 4. Enter a Name for the port and the desired address. Click Finish. Note: The selected controller will verify that the IP address that has been assigned in this dialog does not belong to another device on the network. If the IP address exists, a warning message will display. 6-7 6-8 Communicating with Devices on an EtherNet/IP Link 4. To go online with the controller in RSLogix 5000 programming software, select Who Active from the Communications menu. Then highlight the controller and click the Download button. ahw0880.tif ahw0879.tif If the controller is already programmed click Go Online instead. Communicating with Devices on an EtherNet/IP Link ahw0881tif In the Controller Organizer, right click on the icon for the port and select Properties. 6. Select the Port Configuration tab and enter the proper data. Uncheck the Enable Bootp checkbox. Click Set, Apply and OK to make changes. ahw0883.tif 5. 6-9 6-10 Communicating with Devices on an EtherNet/IP Link Configuring the EtherNet/IP Communications Driver Important: EtherNet/IP only works within the local subnet and with EtherNet/IP devices (not Ethernet control products). To configure the AB_ETH Ethernet communication driver perform the following steps in RSLinx: From the Communications menu, select Configure Drivers. ahw0853.tif 2. Select EtherNet/IP Driver from the list of Available Driver Types. Then Click Add New. ahw0854.tif 3. ahw0855.tif 1. Select the default driver name (i.e. AB-ETHIP-1) or type in your own name. Then Click OK. After you create the driver, configure it to correspond to the Ethernet port on the Embedded EtherNet/IP option board. Communicating with Devices on an EtherNet/IP Link Select where the EtherNet/IP devices reside. The software locates valid IP addresses. ahw0856.tif 4. 6-11 ahw0857.tif Click OK. 5. The driver is now available and you can select the EtherNet/IP port in RSLogix 5000. Controller Connections Over EtherNet/IP A Logix system uses a connection to establish a communication link between two devices. Connections can be: • • • controller to distributed I/O or remote communication modules produced and consumed tags messages You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. 6-12 Communicating with Devices on an EtherNet/IP Link Connections are allocations of resources that provide more reliable communications between devices than unconnected messages. All EtherNet/IP connections are unscheduled. An unscheduled connection is a message transfer between controllers that is triggered by the requested packet interval (RPI) or the program (such as a MSG instruction). Unscheduled messaging lets you send and receive data when needed. The DriveLogix5730 controller supports 32 CIP connections over an EtherNet/IP network. Configuring Distributed I/O The DriveLogix5730 controller supports distributed I/O over a EtherNet/IP link. Configuring I/O in a remote chassis is similar to configuring local I/O. You create the remote communication module and distributed I/O modules on the local Ethernet port. To communicate with distributed I/O modules, you add a remote adapter and I/O modules to the I/O Configuration folder of the controller. ahw0886.tif To Add Distributed I/O Build the I/O Configuration in this Order 1. Add the remote adapter to the embedded EtherNet/IP port of the controller. 2. Add the I/O modules to the remote adapter. Communicating with Devices on an EtherNet/IP Link 6-13 Accessing Distributed I/O I/O information is presented as a structure of multiple fields, which depend on the specific features of the I/O module. The name of the structure is based on the location of the I/O module in the system. Each I/O tag is automatically created when you configure the I/O module through the programming software. Each tag name follows this format: Location:SlotNumber:Type.MemberName.SubMemberName.Bit where: This address variable: Is: Location Identifies network location LOCAL = local DIN rail or chassis ADAPTER_NAME = identifies remote adapter or bridge SlotNumber Slot number of I/O module in its chassis Type Type of data I = input O = output C = configuration S = status MemberName Specific data from the I/O module; depends on the type of data the module can store For example, Data and Fault are possible fields of data for an I/O module. Data is the common name for values the are sent to or received from I/O points. SubMemberName Specific data related to a MemberName. Bit (optional) Specific point on the I/O module; depends on the size of the I/O module (0-31 for a 32-point module) Example 6-14 Communicating with Devices on an EtherNet/IP Link Device: Example Tag Names (automatically created by the software): remote adapter “FLEX_io_adapter” FLEX_io_adapter:I FLEX_io_adapter:I.SlotStatusBits FLEX_io_adapter:I.Data FLEX_io_adapter:O FLEX_io_adapter:O.Data remote “input_module” in slot 0 rack-optimized connection FLEX_io_adapter:0:C FLEX_io_adapter:0:C.Config FLEX_io_adapter:0:C.DelayTime_0 FLEX_io_adapter:0:C.DelayTime_1 FLEX_io_adapter:0:C.DelayTime_2 FLEX_io_adapter:0:C.DelayTime_3 FLEX_io_adapter:0:C.DelayTime_4 FLEX_io_adapter:0:C.DelayTime_5 FLEX_io_adapter:0:I remote “output_module” in slot 1 rack-optimized connection FLEX_io_adapter:1:C FLEX_io_adapter:1:C.SSData FLEX_io_adapter:1:O FLEX_io_adapter:1:O.Data remote “combo_analog” in slot 2 direct connection FLEX_io_adapter:2:C FLEX_io_adapter:2:C.InputFIlter FLEX_io_adapter:2:C.InputConfiguration FLEX_io_adapter:2:C.OutputConfiguration FLEX_io_adapter:2:C.RTSInterval FLEX_io_adapter:2:C.SSCh0OuputData FLEX_io_adapter:2:C.SSCH1OutputData FLEX_io_adapter:2:I Communicating with Devices on an EtherNet/IP Link 6-15 Adding a Remote Controller If you want to add the controller as a remote consumed controller to the I/O configuration, you first add the EtherNet/IP port and then the controller. ahw0888.tif To Add a Remote Controller Build the I/O Configuration in this Order 1. Add the remote EtherNet/IP port or bridge to the local EtherNet/IP port. 2. Add the remote controller to the remote EtherNet/IP port. Producing and Consuming Data The DriveLogix5730 controller supports the ability to produce (broadcast) and consume (receive) system-shared tags over an EtherNet/IP link. Produced and consumed data is accessible by multiple controllers over an Ethernet network. The controller sends or receives data at a predetermined RPI rate. This is the recommended method of communication between Logix controllers. Produced and consumed tags must be controller-scoped tags of DINT or REAL data type, or in an array or structure. Tag type: Description: Specify: produced These are tags that the controller produced for other controllers to consume. Enabled for producing How many consumers allowed consumed These are tags whose values are produced by another controller. Controller name that owns the tag that the local controller wants to consume Tag name or instance that the controller wants to consume Data type of the tag to consume Update interval of how often the local controller consumes the tag 6-16 Communicating with Devices on an EtherNet/IP Link The producer and consumer must be configured correctly for the specified data to be shared. A produced tag in the producer must be specified exactly the same as a consumed tag in the consumer. If any produced/consumed tag between a producer and consumer is not specified correctly, none of the produced/consumed tags for that producer and consumer will be transferred. For example, if a DriveLogix5730 controller is consuming three tags that another controller consumes but the first tag is specified incorrectly, none of the tags are transferred to the consuming DriveLogix5730 controller. However, one consumer failing to access shared data does not affect other consumers accessing the same data. For example, if the producing DriveLogix5730 controller from the previous example also produced tags for other consuming controllers but did so correctly, those tags are still transferred to the additional consuming controllers. Maximum Number of Produced and Consumed Tags The maximum number of produced/consumed tags that you can configure depends on the connection limits of the Ethernet port on the controller. You can have a maximum of 32 connections through the Ethernet port. Each produced tag uses one connection for the tag and the first configured consumer of the tag. Each consumer thereafter uses an additional connection. If you have a lot of data to produce or consume, organize that data into an array. An array is treated as one tag, so it uses only one connection. An array can be as large as 488 bytes, which is also the limit of a produced or consumed tag. Size Limit of a Produced or Consumed Tag A produced or consumed tag can be as large as 488 bytes, but it must also fit within the bandwidth of the EtherNet/IP network. Communicating with Devices on an EtherNet/IP Link 6-17 Producing a tag Produced data must be of DINT or REAL data type or a structure. You can use a user-defined structure to group BOOL, SINT, and INT data to be produced. To create a produced tag: 1. You must be programming offline. 2. In the controller organizer, double-click the Controller Tags folder and then click the Edit Tags tab. 3. Select the tag that you want to produce, or enter a new tag, and display the Tag Properties dialog box. 4. Make sure the tag is controller scope. 5. Select the “Produce this tag” check box. Specify how many controllers can consume the tag. You can produce a base, alias, or consumed tag. The consumed tag in a receiving controller must have the same data type as the produced tag in the originating controller. The controller performs type checking to ensure proper data is being received. Produced tags require connections. The number of connections depends on how many controllers are consuming the tags. The controller requires one connection for the produced tag and the first consumer. Then, the controller requires an additional connection for each subsequent consumer. 6-18 Communicating with Devices on an EtherNet/IP Link Consuming a Tag A consumed tag represents data that is produced (broadcast) by one controller and received and stored by the consuming controller. To create a consumed tag: 1. You must be programming offline. 2. In the controller organizer, double-click the Controller Tags folder and then click the Edit Tags tab. 3. Select the tag that you want to consume, or enter a new tag, and display the Tag Properties dialog box. 4. Specify: In this field: Type or select: Tag Type Select Consumed. Controller Select the name of the other controller. You must have already created the controller in the controller organizer for the controller name to be available. Remote Tag Name Remote Instance Type a name for the tag in the other controller you want to consume. Important: The name must match the name in the remote controller exactly, or the connection faults. RPI (requested packet interval) Type the amount of time in msec between updates of the data from the remote controller. The local controller will receive data at least this fast. Virtual-backplane controllers, such as DriveLogix5730, CompactLogix and FlexLogix controllers, only produce data at RPIs in powers of two milliseconds (such as 2, 4, 8, 16, 32, 64, etc.), or when triggered by an IOT instruction. Display Style If you are creating a consumed tag that refers to a tag whose data type is BOOL, SINT, INT, DINT, or REAL, you can select a display style. This display style defines how the tag value will be displayed in the data monitor and ladder editor. The display style does not have to match the display style of the tag in the remote controller. All consumed tags are automatically controller-scope. The produced tag in the originating DriveLogix5730 controller must have the same data type as the consumed tag in the consuming controller. The DriveLogix5730 controller performs type checking to make sure proper data is being received. Important: If a consumed-tag connection fails, none of the tags are transferred from the producing controller to the consuming controller. Communicating with Devices on an EtherNet/IP Link 6-19 Sending Messages The DriveLogix5730 controller can send MSG instructions to other controllers and devices over an EtherNet/IP link. Each MSG instruction requires you to specify a target and an address within the target. Important: Revision 15.xx of DriveLogix firmware adds more stringent range checks when reading to or writing from tags. Message packets are limited to 240 bytes. This could cause some MSG instructions that worked in previous firmware revisions to not work in revision 15.xx firmware. For example, use a CIP Generic MSG instruction to perform a Get Attribute Single service. The attribute is 4 bytes in length. Assume the destination tag is an INT data type (2 bytes in length). In revision 13.xx firmware, the MSG instruction places the first 2 bytes of the attribute in the destination tag. In revision 15.xx firmware, the MSG instruction errors because the destination tag is not large enough. To correct this error, change the destination tag to a DINT data type. MSG instructions are unscheduled. The type of MSG determines whether or not it requires a connection. If the MSG instruction requires a connection, it opens the needed connection when it is executed. You can configure the MSG instruction to keep the connection open (cache) or to close it after sending the message. This type of MSG: Using this communication method: Uses a connection: Which you can cache: CIP data table read or write CIP X X PLC-2, PLC-3, PLC-5, or SLC (all types) CIP X X CIP with Source ID X X DH+ X CIP generic CIP X(1) X block-transfer read or write na X X (1) You can connect CIP generic messages, but for most applications, we recommend you leave CIP generic messages unconnected. The update time of local I/O modules may increase when the controller is bridging messages. Important: Bridging over the DriveLogix5730 controller should be targeted toward applications that are not real time dependent, such as RSLogix 5000 program downloads and ControlFlash updates. 6-20 Communicating with Devices on an EtherNet/IP Link Communicating with Another Logix-based Controller All Logix-based controllers can use MSG instructions to communicate with each other. The following examples show how to use tags in MSG instructions between Logix-based controllers. Type of MSG Instruction: Example Source and Destination: Logix-based controller writes to Logix-based controller (CIP Data Table Write) source tag array_1 destination tag array_2 Logix-based controller reads from Logix-based controller (CIP Data Table Read) source tag array_1 destination tag array_2 The source and destination tags: • must be controller-scoped tags. • can be of any data type, except for AXIS, MESSAGE, or MOTION_GROUP. Communicating with other controllers over EtherNet/IP The DriveLogix5730 controller also uses MSG instructions to communicate with PLC and SLC controllers. The MSG instructions differ depending on which controller initiates the instruction. For MSG instructions originating from a DriveLogix5730 controller to a PLC or SLC controller: Type of MSG Instruction: DriveLogix5730 writes to PLC-5 or SLC Supported Source File Types: Supported Destination File Types: In the DriveLogix5730 controller, specify the source data type based on the destination device: Specify the destination file type based on the destination device: PLC-5: SINT, INT, DINT, or REAL SLC: INT, REAL PLC-5 typed write: S, B, N, or F PLC-5 word-range write: S, B, N, F, I, O, A, or D SLC: B, N or F Example source element: array_1 Example destination tag: N7:10 Communicating with Devices on an EtherNet/IP Link Type of MSG Instruction: Supported Source File Types: Supported Destination File Types: DriveLogix5730 writes to PLC-2 In the DriveLogix5730 controller, select one of these data types: Use the PLC-2 compatibility file. 6-21 SINT, INT, DINT, or REAL Example destination tag: 010 Example source element: array_1 DriveLogix5730 reads from PLC-5 or SLC DriveLogix5730 reads from PLC-2 Specify the destination file type based on the destination device: In the DriveLogix5730 controller, specify the destination data type based on the destination device: PLC-5 typed read: S, B, N, or F PLC-5 word-range read: S, B, N, F, I, O, A, or D SLC: B, N or F PLC-5: SINT, INT, DINT, or REAL SLC: INT, REAL Example source element: N7:10 Example destination tag: array_1 Use the PLC-2 compatibility file. In the DriveLogix5730 controller, select one of these data types: SINT, INT, DINT, or REAL Example source element: 010 Example destination tag: array_1 The DriveLogix5730 controller can send typed or word-range commands to PLC-5 controllers. These commands read and write data differently. The following diagrams show how the typed and word-range commands differ. Word-range read command Typed read command 16-bit words in PLC-5 controller 32-bit words in DriveLogix5730 controller 16-bit words in PLC-5 controller 32-bit words in DriveLogix5730 controller 1 1 1 2 1 2 2 2 4 3 3 3 3 4 4 4 The typed commands maintain data structure and value. The word-range commands fill the destination tag contiguously. Data structure and value change depending on the destination data type. The DriveLogix5730 controller can process messages initiated from PLC or SLC controllers. These messages use data table addresses. In order for these controllers to access tags within the DriveLogix5730 controller, you map tags to data table addresses. 6-22 Communicating with Devices on an EtherNet/IP Link Mapping Addresses The programming software includes a PLC/SLC mapping tool which allows you to make an existing controller array tag in the local controller available to PLC-2, PLC-3, PLC-5, or SLC controllers. To map addresses: ahw0889.tif 1. From the Logic menu, select Map PLC/SLC Messages. 2. Specify this information: For: In this field: Specify: For example: PLC-3, PLC-5, and SLC controllers File Number Type the file number of the data table in the PLC/SLC controller. 10 Tag Name Type the array tag name the local controller uses to refer to the PLC/SLC data table address. The tag must be an integer array (SINT, INT, or DINT) that is large enough for the message data. array_1 PLC-2 controllers Tag Name Type the tag name to be the PLC-2 compatibility file. 200 TIP: You can map as many tags as you want to a PLC-3, PLC-5, or SLC controller. You can map only one tag to a PLC-2 controller. The following table shows example source and destination tags and elements for different controller combinations. Type of MSG Instruction: Example Source and Destination: PLC-5 writes to DriveLogix5730 source element N7:10 SLC writes to DriveLogix5730 SLC 5/05 SLC 5/04 OS402 and above SLC 5/03 OS303 and above destination tag “array_1” The PLC-5, PLC-3, and SLC controllers support logical ASCII addressing so you do not have to map a compatibility file for MSG instructions initiated by a PLC-5, PLC-3, or SLC controller. Place the DriveLogix5730 tag name in double quotes (“). You could optionally map a compatibility file. For example, if you enter 10 for the compatibility file, you enter N10:0 for the destination tag. PLC-2 writes to DriveLogix5730 source element 010 destination tag 200 The destination tag is the three-digit PLC-2 address you specified for PLC-2 mapping. Communicating with Devices on an EtherNet/IP Link Type of MSG Instruction: Example Source and Destination: PLC-5 reads from DriveLogix5730 source tag “array_1” SLC reads from DriveLogix5730 SLC 5/05 SLC 5/04 OS402 and above SLC 5/03 OS303 and above destination element N7:10 6-23 The PLC-5, PLC-3, and SLC controllers support logical ASCII addressing so you do not have to map a compatibility file for MSG instructions initiated by a PLC-5, PLC-3, or SLC controller. Place the DriveLogix5730 tag name in double quotes (“). You could optionally map a compatibility file. For example, if you enter 10 for the compatibility file, you enter N10:0 for the source tag. PLC-2 reads from DriveLogix5730 source tag 200 destination element 010 The source tag is the three-digit PLC-2 address you specified for PLC-2 mapping. When the DriveLogix5730 controller initiates messages to PLC or SLC controllers, you do not have to map compatibility files. You enter the data table address of the target device just as you would a tag name. SLC 5/05 controllers, SLC 5/04 controllers (OS402 and above), and SLC 5/ 03 controllers (OS303 and above) support logical ASCII addressing and support PLC/SLC mapping (see the examples above). For all other SLC or MicroLogix1000 controllers, you must map a PLC-2 compatibility file (see the PLC-2 examples above). 6-24 Communicating with Devices on an EtherNet/IP Link Using a MSG Instruction to Send an Email The controller is an email client that uses a mail relay server to send email. The DriveLogix5730 controller can execute a generic CIP message that sends an email message to an SMTP mail relay server using the standard SMTP protocol. Some mail relay servers require a domain name be provided during the initial handshake of the SMTP session. For these mail relay servers, make sure you specify a domain name when you configure the network settings. See 6-3 for information on configuring the network settings of the controller and specifying a domain name. Important: Be careful to write the ladder logic to ensure the MSG instructions are not continuously triggered to send email messages. Creating String Type for Email String Data Type The tags for the email text and transmission status can contain as many as 474 characters. For these tags, you must create a user-defined STRING data type that is larger than the default. For example, create a STRING data type named EMAILSTRING. While offline, in the Controller Organizer, right click on the folder for Strings and select New String Type. ahw0890.tif 2. Enter the Name (e.g. EMAILSTRING) and the maximum number of characters (e.g. 520). Click Apply, then OK. ahw0891.tif 1. Communicating with Devices on an EtherNet/IP Link 6-25 Creating String Tags On the Edit tab of the Controller Tags window, create three tags: ahw0892.tif • one to identify the mail server (use STRING data type for this tag) • one for the email text (use EMAILSTRING data type for this tag) • one for the email transmission status (use EMAILSTRING data type for this tag) Entering String Data On the Monitor Tags tab of the Controller Tags window, click the button in the Value column to launch the String Browser for each tag. On the Monitor Tags tab of the Controller Tags window, click the button in the Value column to launch the String Browser. ahw0893.tif 1. Click on this button Communicating with Devices on an EtherNet/IP Link To include “To:”, “From:”, and “Subject:” fields in the email, use <CR><LF> symbols to separate each of these fields. The “To:” and “From”” fields are required; the “Subject:” field is optional. Use a second set of <CR><LF> symbols after the last one of these fields you enter. For example: To: email address of recipient $r$l From: email address of sender$r$l Subject: subject of message $r$l$r$l body of email message Use the “From” address to specify where the mail relay server can send an undeliverable email message. The maximum length of an email message is 474 characters. An additional 4-byte string-length value is added to the tag. As a result, the maximum source length is 478 characters. Entering Ladder Logic You need two MSG instructions. One MSG instruction configures the mail server. This only needs to be executed once. The second MSG instruction triggers the email transmission. This can be executed as often as needed. Important: Be careful to write the ladder logic to ensure the MSG instructions are not continuously triggered to send email messages. This is an example of the basic MSG logic. You can build more complex logic that automatically manages the Source Lengths within the MSG blocks. Refer to Using Ladder Logic to Dynamically Configure Messages on page 6-30. ahw0897.tif 6-26 Communicating with Devices on an EtherNet/IP Link 6-27 Configuring the MSG Instruction that Identifies the Mail Relay Server On the Configuration tab of the Message Configuration, fill out the following fields: ahw0898.tif 1. In this field: Enter: Service Type Set Attribute Single Instance 1 Class 32f Attribute 5 Source Element the STRING tag that contains the IP address or host name of the mail relay server In this example, enter EmailConfig Source Length the number of characters in the IP address or host name of the mail server plus 4 In this example, enter 17 (13 characters in the IP address 10.88.128.111 + 4) On the Communication tab of the Message Configuration, set the Path (e.g. browse for the Embedded EtherNet Port). Click Apply. Click OK. ahw0899.tif 2. Communicating with Devices on an EtherNet/IP Link Configuring the MSG Instruction that Transmits the Email 1. On the Configuration tab of the Message Configuration, fill out the following fields: ahw0900.tif 6-28 In this field: Enter: Service Type Custom Service Code 4b Instance 1 Class 32f Attribute 0 Source Element the tag that contains the email text This tag is of the STRING data type you created to contain the email text. In this example, EmailText. Source Length the number of characters in the email text plus 4 In this example, enter 114 (110 characters in the email + 4) Destination a tag to contain the status of the email transmission This tag is also of the STRING data type you created to contain the email text. In this example, EmailStatus. Communicating with Devices on an EtherNet/IP Link On the Communication tab of the Message Configuration, set the Path in the same manner as in the MSG that identifies the mail relay server. Click Apply. Click OK. ahw0901.tif 2. 6-29 Understanding Email Status Codes Examine the destination element of the email MSG to see whether the email was successfully delivered to the mail relay server. This indicates that the mail relay server placed the email message in a queue for delivery. It does not mean the intended recipient successfully received the email message. Possible codes that could be in this destination element are: Error Code (hex): Extended-Error Code (hex): Description: 0x00 none Delivery successful to the mail relay server. 0x02 none Resource unavailable. The email object was unable to obtain memory resources to initiate the SMTP session. 0x08 none Unsupported Service Request. Make sure the service code is 0x4B and the Class is 0x32F. 0x11 none Reply data too large. The Destination string must reserve space for the SMTP server reply message. The maximum reply can be 470 bytes. 0x13 none Configuration data size too short. The Source Length is less than the Source Element string size plus the 4-byte length. The Source Length must equal the Source Element string size + 4. 0x15 none Configuration data size too large. The Source Length is greater than the Source Element string size plus the 4-byte length. The Source Length must equal the Source Element string size + 4. 0x19 none Data write failure. An error occurred when attempting to write the SMTP server address (attribute 4) to non-volatile memory. 6-30 Communicating with Devices on an EtherNet/IP Link Error Code (hex): Extended-Error Code (hex): 0xFF 0x0100 Error returned by email server; check the Destination string for reason. The email message was not queued for delivery. 0x0101 SMTP mail server not configured. Attribute 5 was not set with a SMTP server address. 0x0102 “To:” address not specified. Attribute 1 was not set with a “To:” address AND there is not a “To:” field header in the email body. 0x0103 “From:” address not specified. Attribute 2 was not set with a “From:” address AND there is not a “From:” field header in the email body. 0x0104 Unable to connect to SMTP mail server set in Attribute 5. If the mail server address is a hostname, make sure that the device supports DNS, and that a Name Server is configured. If the hostname is not fully qualified, i.e., “mailhost” and not “mailhost.xx.yy.com” then the domain must be configured as “xx.yy.com”. Try “ping <mail server address>” to insure the mail server is reachable from your network. Also try “telnet <mail server address> 25” which attempts to initiate a SMTP session with the mail server via telnet over port 25. (If you connect then enter “QUIT”). 0x0105 Communication error with SMTP mail server. An error occurred after the initial connection with the SMTP mail server. See the ASCII text following the error code for more details as to the type of error. 0x0106 SMTP mail server host name DNS query did not complete. A previous send service request with a host name as the SMTP mail server address did not yet complete. Note that a timeout for a DNS lookup with an invalid host name can take up to 3 minutes. Long timeouts can also occur if a domain name or name server is not configured correctly. Description: Using Ladder Logic to Dynamically Configure Messages ahw0902.tif Use ADD instructions to calculate the MSG Source Length. Communicating with Devices on an EtherNet/IP Link In the following example, one DriveLogix5730 controller controls distributed I/O through a 1794-AENT module. ahw0906.eps Example 1: DriveLogix5730 Controller and Distributed I/O 6-31 DriveLogix5730 controller (DriveLogix1) EtherNet/IP 1794-AENT with distributed I/O (Remote1) Controlling Distributed I/O This example has DriveLogix1 controlling the I/O connected to the remote 1794-AENT module. The data the DriveLogix5730 controller receives from the distributed I/O modules depends on how you configure the I/O modules. You can configure each module as a direct connection or as rack optimized. One chassis can have a combination of some modules configured as a direct connection and others as rack optimized. All analog modules require direct connections. Diagnostic modules support rack-optimized connections, but require direct connections to take full advantage of their diagnostic features. Total Connections Required by DriveLogix1 The following table calculates the connections used in this example. Connection: Amount: DriveLogix1 to 4 distributed I/O modules (through 1794-AENT) all I/O modules configured as direct connection no connection to the 1794-AENT 4 total connections used: 4 If you configured the distributed I/O modules as rack-optimized, you would only need a rack-optimized connection to the 1794-AENT, reducing the above example by 3 connections. 6-32 Communicating with Devices on an EtherNet/IP Link Example 2: Controller to Controller In the following example, one EtherNet/IP DriveLogix5730 controller communicates with another EtherNet/IP DriveLogix5730 controller over EtherNet/IP. Each controller has its own local I/O. ahw0907.eps EtherNet/IP DriveLogix1 DriveLogix2 workstation Producing and Consuming Tags Produced data must be of DINT or REAL data type or an array or structure. You can use a user-defined structure to group BOOL, SINT, and INT data to be produced. You can produce a base, alias, or consumed tag. The consumed tag must have the same data type as the produced tag in the originating controller. The controller performs type checking to ensure proper data is being received. ahw0907.eps EtherNet/IP DriveLogix1 tagA DINT tagB Real DriveLogix2 (controllerb) tagA DINT tagB Real workstation Communicating with Devices on an EtherNet/IP Link 6-33 ahw0912.eps ahw0909.eps ahw0910.eps ahw0908.eps ahw0911.eps This example shows DriveLogix1 producing tagA and consuming tagB: Communicating with Devices on an EtherNet/IP Link Each produced tags requires one connection for the producing controller and an additional connection for each consuming controller. Each consumed tag requires one connection. Sending a MSG instruction To send a MSG from DriveLogix1 to DriveLogix2: 1. For DriveLogix1, create a controller-scoped tag and select the MESSAGE data type. 2. Enter a MSG instruction. In this example logic, a message is sent when a specific condition is met. When count_send is set, the ladder logic sends the count_msg MSG. ahw0913.eps 6-34 3. Configure the MSG instruction. On the Configuration tab: For this item: Specify: Message Type CIP Data Table Read or CIP Data Table Write Source Tag Tag containing the data to be transferred Number of Elements Number of array elements to transfer Destination Tag Tag to which the data will be transferred 4. On the Communication tab, specify the communication path. Use the Browse button to select the device that will receive the MSG instruction. The communication path in this example is: For this item: Specify: Communication Path 1,1,2,xxx.xxx.xxx.xxx,1,0 where: 1 is the virtual backplane of DriveLogix1 1 is the slot of the Ethernet port in the controller (note, the 1,1 displays as LocalENB) 2 is the EtherNet/IP network 100.100.115.11 is the IP address of DriveLogix2 1 is the virtual backplane of DriveLogix2 0 is the controller slot of DriveLogix2 Communicating with Devices on an EtherNet/IP Link 6-35 Total Connections Required by DriveLogix1 The following table calculates the connections used in this example. Connection: Amount: connected, cached MSG from DriveLogix1 to DriveLogix2 1 produced tagA produced from DriveLogix1 to DriveLogix2 other consumer (2 are configured) 1 1 consumed tagB 1 total connections used: 4 Receiving a MSG Instruction When other devices send messages to the DriveLogix5730 controller, the path for the message must identify the controller. Configure a CIP-type message in the originating device. Specify the path the DriveLogix5730 controller as: xxx.xxx.xxx.xxx,1,1 IP Address virtual backplane slot 1 6-36 Notes: Communicating with Devices on an EtherNet/IP Link Chapter 7 Communicating with Devices on a ControlNet Link De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of configuring ControlNet communication you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with configuring ControlNet communication. Configuring Your System for For the DriveLogix5730 controller to operate on a ControlNet network, you need: a ControlNet Link • a workstation with an appropriate ControlNet communication daughtercard • a 1788-CNx communication daughtercard installed in the DriveLogix communication slot • RSLinx software to configure the ControlNet communication driver • RSLogix 5000 programming software to configure the 1788-CNx communication daughtercard as part of the DriveLogix system • RSNetWorx software to schedule the DriveLogix system on the network Configuring the Hardware Before you can connect the DriveLogix system to the ControlNet network, you must configure the 1788-CNx communication daughtercard and make 7-2 Communicating with Devices on a ControlNet Link sure it’s properly installed in the DriveLogix controller. Refer to Installing the Communications Daughtercard on page B-9. You’ll need to configure the communication daughtercard slot number to 1 in the RSLogix 5000 programming software. The DriveLogix controller uses slot 0 for the Communication Format with the local drive. For more information about configuring a 1788-CNx communication daughtercard, see: For this card: See this document: 1788-CNC, -CNCR 1788-IN002 1788-CNF, -CNFR 1788-IN005 Configuring the Communication Driver Use RSLinx software to configure the ControlNet communication driver. Select the appropriate communication driver for the communication daughtercard in your workstation. In RSLinx software, select Configure Driver. Select the appropriate driver. ahw0434.tif ahw0433.tif 1. The installation instructions for the communications daughtercard should identify which communication driver to install. 2. Specify the appropriate settings. For example. If you are using this device: Specify this information: 1784-KTCx card memory address, which must match the switch setting on the card I/O base address, which must match the switch setting on the card ControlNet node address 1784-PCC card ControlNet node address (MAC ID) 1784-PCIC card ControlNet node address (MAC ID) Communicating with Devices on a ControlNet Link 7-3 Configuring Your Daughtercard as Part of the System Use RSLogix 5000 programming software to map the 1788-CNx communication daughtercard as part of the DriveLogix5730 system. In the Controller Organizer, add the communication daughtercard to the I/O Configuration folder. 1. In the Controller Organizer, select the I/O Configuration folder. Right-click the selected folder and select New Module. Select the proper ControlNet daughtercard from the list of possible communication devices. Click OK. ahw0922.tif ahw0903.tif 2. ahw0923.tif Do not change the slot number. This must be slot 4. 3. Enter a Name for the daughtercard and the desired. Click Finish. 7-4 Communicating with Devices on a ControlNet Link Configuring Distributed I/O The DriveLogix5730 controller supports distributed I/O over a ControlNet link. Configuring I/O in a remote chassis is similar to configuring local I/O. You create the remote communication module and distributed I/O modules on the local ControlNet daughtercard. To communicate with distributed I/O modules, you add a remote adapter and I/O modules to the I/O Configuration folder of the controller. ahw0924.tif To Add Distributed I/O Build the I/O Configuration in this Order 1. Add the remote adapter to the ControlNet daughtercard of the controller. 2. Add the I/O modules to the remote adapter. Communicating with Devices on a ControlNet Link 7-5 Accessing Distributed I/O I/O information is presented as a structure of multiple fields, which depend on the specific features of the I/O module. The name of the structure is based on the location of the I/O module in the system. Each I/O tag is automatically created when you configure the I/O module through the programming software. Each tag name follows this format: Location:SlotNumber:Type.MemberName.SubMemberName.Bit where: This address variable: Is: Location Identifies network location LOCAL = local DIN rail or chassis ADAPTER_NAME = identifies remote adapter or bridge SlotNumber Slot number of I/O module in its chassis Type Type of data I = input O = output C = configuration S = status MemberName Specific data from the I/O module; depends on the type of data the module can store For example, Data and Fault are possible fields of data for an I/O module. Data is the common name for values the are sent to or received from I/O points. SubMemberName Specific data related to a MemberName. Bit (optional) Specific point on the I/O module; depends on the size of the I/O module (0-31 for a 32-point module) ahw0925.tif Example 7-6 Communicating with Devices on a ControlNet Link Device: Example Tag Names (automatically created by the software): remote adapter “FLEX_io_adapter” FLEX_io_adapter:I FLEX_io_adapter:I.SlotStatusBits FLEX_io_adapter:I.Data FLEX_io_adapter:O FLEX_io_adapter:O.Data remote “input_module” in slot 0 rack-optimized connection FLEX_io_adapter:0:C FLEX_io_adapter:0:C.Config FLEX_io_adapter:0:C.DelayTime_0 FLEX_io_adapter:0:C.DelayTime_1 FLEX_io_adapter:0:C.DelayTime_2 FLEX_io_adapter:0:C.DelayTime_3 FLEX_io_adapter:0:C.DelayTime_4 FLEX_io_adapter:0:C.DelayTime_5 FLEX_io_adapter:0:I remote “output_module” in slot 1 rack-optimized connection FLEX_io_adapter:1:C FLEX_io_adapter:1:C.SSData FLEX_io_adapter:1:O FLEX_io_adapter:1:O.Data remote “combo_analog” in slot 2 direct connection FLEX_io_adapter:2:C FLEX_io_adapter:2:C.InputFIlter FLEX_io_adapter:2:C.InputConfiguration FLEX_io_adapter:2:C.OutputConfiguration FLEX_io_adapter:2:C.RTSInterval FLEX_io_adapter:2:C.SSCh0OuputData FLEX_io_adapter:2:C.SSCH1OutputData FLEX_io_adapter:2:I Communicating with Devices on a ControlNet Link Scheduling the ControlNet Network In the Network menu, select Online. ahw0929.tif 1. Use RSNetWorx software to schedule the ControlNet network. The controller project must already be downloaded from RSLogix 5000 programming software to the controller and the controller must be in Program or Remote Program mode. Survey the network. Enable Edits ahw0926.tif 2. In the Network menu, select Properties. ahw0930.tif 3. 7-7 In the Network menu, select Properties. ahw0930.tif 4. 5. Edit the parameters as desired. Click Apply. Click OK. In the File menu, select Save. ahw0931.tif 3. Communicating with Devices on a ControlNet Link ahw0927.tif 7-8 Communicating with Devices on a ControlNet Link Enter a name and path for the network configuration. ahw0928.tif ahw0932.tif 6. 7-9 7. Click OK to optimize and reschedule the connections. Sending Messages The DriveLogix5730 controller can send MSG instructions to other controllers over a ControlNet link. Each MSG instruction requires you to specify a target and an address within the target. The number of messages that a device can support depends on the type of message and the type of device: Support this many unconnected messages: Support this many connected messages: 1756-CNB or 1756-CNBR module (for a Logix5550 controller) 20 64 1788-CNx daughtercard (for a DriveLogix controller) 5 32 with a maximum of 9 scheduled ControlNet PLC-5 controller 32 128 This device: Important: Revision 15.xx of DriveLogix firmware adds more stringent range checks when reading to or writing from tags. Message packets are limited to 240 bytes. This could cause some MSG instructions that worked in previous firmware revisions to not work in revision 15.xx firmware. For example, use a CIP Generic MSG instruction to perform a Get Attribute Single service. The attribute is 4 bytes in length. Assume the destination tag is an INT data type (2 bytes in length). In revision 13.xx firmware, the MSG instruction places the first 2 bytes of the attribute in the destination tag. In revision 15.xx 7-10 Communicating with Devices on a ControlNet Link firmware, the MSG instruction errors because the destination tag is not large enough. To correct this error, change the destination tag to a DINT data type. MSG instructions are unscheduled. The type of MSG determines whether or not it requires a connection. If the MSG instruction requires a connection, it opens the needed connection when it is executed. You can configure the MSG instruction to keep the connection open (cache) or to close it after sending the message. This type of message: And this communication method: CIP data table read or write PLC2, PLC3, PLC5, or SLC (all types) Uses a connection: X CIP CIP with Source ID CIP generic DH+ X CIP Optional(1) block-transfer read or write (1) X You can connect CIP generic messages, but for most applications, we recommend you leave CIP generic messages unconnected. Connected messages are unscheduled connections on ControlNet. If a MSG instruction uses a connection, you have the option to leave the connection open (cache) or close the connection when the message is done transmitting. If you: Then: Cache the connection The connection stays open after the MSG instruction is done. This optimizes execution time. Opening a connection each time the message executes increases execution time. Do not cache the connection The connection closes after the MSG instruction is done. This frees up that connection for other uses. The controller has the following limits on the number of connections that you can cache: If you have this software and firmware revision: Then you can cache: 12.x or later up to 32 connections Communicating with Devices on a ControlNet Link 7-11 Communicating with Another Logix-Based Controller All Logix-based controllers can use MSG instructions to communicate with each other. The following examples show how to use tags in MSG instructions between Logix-based controllers. Type of MSG Instruction: Example Source and Destination: Logix-based controller writes to Logix-based controller (CIP Data Table Write) source tag array_1 destination tag array_2 Logix-based controller reads from Logix-based controller (CIP Data Table Read) source tag array_1 destination tag array_2 The source and destination tags: • must be controller-scoped tags. • can be of any data type, except for AXIS, MESSAGE, or MOTION_GROUP. Communicating with Other Controllers Over ControlNet The DriveLogix5730 controller also uses MSG instructions to communicate with PLC and SLC controllers. The MSG instructions differ depending on which controller initiates the instruction. For MSG instructions originating from a DriveLogix5730 controller to a PLC or SLC controller: Type of MSG Instruction: Supported Source File Types: Supported Destination File Types: DriveLogix writes to PLC-5 or SLC In the DriveLogix controller, specify the source data type based on the destination device: Specify the destination file type based on the destination device: PLC-5: SINT, INT, DINT, or REAL SLC: INT PLC-5 typed write: S, B, N, or F PLC-5 word-range write: S, B, N, F, I, O, A, or D SLC: B or N Example source element: array_1 Example destination tag: N7:10 7-12 Communicating with Devices on a ControlNet Link Type of MSG Instruction: DriveLogix writes to PLC-2 Supported Source File Types: Supported Destination File Types: In the DriveLogix controller, select one of these data types: Use the PLC-2 compatibility file. SINT, INT, DINT, or REAL DriveLogix reads from PLC-5 or SLC DriveLogix reads from PLC-2 Example source element: array_1 Example destination tag: 010 Specify the destination file type based on the destination device: In the DriveLogix controller, specify the destination data type based on the destination device: PLC-5 typed read: S, B, N, or F PLC-5 word-range read: S, B, N, F, I, O, A, or D SLC: B or N PLC-5: SINT, INT, DINT, or REAL SLC: INT Example source element: N7:10 Example destination tag: array_1 Use the PLC-2 compatibility file. In the DriveLogix controller, select one of these data types: SINT, INT, DINT, or REAL Example source element: 010 Example destination tag: array_1 The DriveLogix5730 controller can send typed or word-range commands to PLC-5 controllers. These commands read and write data differently. The following diagrams show how the typed and word-range commands differ. Word-range read command Typed read command 16-bit words in PLC-5 controller 32-bit words in DriveLogix5730 controller 16-bit words in PLC-5 controller 32-bit words in DriveLogix5730 controller 1 1 1 2 1 2 2 2 4 3 3 3 3 4 4 4 The typed commands maintain data structure and value. The word-range commands fill the destination tag contiguously. Data structure and value change depending on the destination data type. The DriveLogix5730 controller can process messages initiated from PLC or SLC controllers. These messages use data table addresses. In order for these controllers to access tags within the DriveLogix5730 controller, you map tags to data table addresses. Mapping Addresses The programming software includes a PLC/SLC mapping tool which allows you to make an existing controller array tag in the local controller available to PLC-2, PLC-3, PLC-5, or SLC controllers. Communicating with Devices on a ControlNet Link 7-13 To map addresses: ahw0889.tif 1. From the Logic menu, select Map PLC/SLC Messages. 2. Specify this information: For: In this field: Specify: For example: PLC-3, PLC-5, and SLC controllers File Number Type the file number of the data table in the PLC/SLC controller. 10 Tag Name Type the array tag name the local controller uses to refer to the PLC/SLC data table address. The tag must be an integer array (SINT, INT, or DINT) that is large enough for the message data. array_1 PLC-2 controllers Tag Name Type the tag name to be the PLC-2 compatibility file. 200 TIP: You can map as many tags as you want to a PLC-3, PLC-5, or SLC controller. You can map only one tag to a PLC-2 controller. The following table shows example source and destination tags and elements for different controller combinations. Type of MSG Instruction: Example Source and Destination: PLC-5 writes to DriveLogix5730 source element N7:10 SLC writes to DriveLogix5730 SLC 5/05 SLC 5/04 OS402 and above SLC 5/03 OS303 and above destination tag “array_1” The PLC-5, PLC-3, and SLC controllers support logical ASCII addressing so you do not have to map a compatibility file for MSG instructions initiated by a PLC-5, PLC-3, or SLC controller. Place the DriveLogix5730 tag name in double quotes (“). You could optionally map a compatibility file. For example, if you enter 10 for the compatibility file, you enter N10:0 for the destination tag. PLC-2 writes to DriveLogix5730 source element 010 destination tag 200 The destination tag is the three-digit PLC-2 address you specified for PLC-2 mapping. 7-14 Communicating with Devices on a ControlNet Link Type of MSG Instruction: Example Source and Destination: PLC-5 reads from DriveLogix5730 source tag “array_1” SLC reads from DriveLogix5730 SLC 5/05 SLC 5/04 OS402 and above SLC 5/03 OS303 and above destination element N7:10 The PLC-5, PLC-3, and SLC controllers support logical ASCII addressing so you do not have to map a compatibility file for MSG instructions initiated by a PLC-5, PLC-3, or SLC controller. Place the DriveLogix5730 tag name in double quotes (“). You could optionally map a compatibility file. For example, if you enter 10 for the compatibility file, you enter N10:0 for the source tag. PLC-2 reads from DriveLogix5730 source tag 200 destination element 010 The source tag is the three-digit PLC-2 address you specified for PLC-2 mapping. When the DriveLogix5730 controller initiates messages to PLC or SLC controllers, you do not have to map compatibility files. You enter the data table address of the target device just as you would a tag name. SLC 5/05 controllers, SLC 5/04 controllers (OS402 and above), and SLC 5/ 03 controllers (OS303 and above) support logical ASCII addressing and support PLC/SLC mapping (see the examples above). For all other SLC or MicroLogix1000 controllers, you must map a PLC-2 compatibility file (see the PLC-2 examples above). Producing and Consuming Data The DriveLogix5730 controller supports the ability to produce (broadcast) and consume (receive) system-shared tags over a ControlNet link. Produced and consumed data is accessible by multiple controllers over a ControlNet network. Produced and consumed data are scheduled connections because the controller sends or receives data at a predetermined RPI rate. Produced and consumed tags must be controller-scoped tags of DINT or REAL data type, or in an array or structure. Tag type: Description: Specify: produced These are tags that the controller produced for other controllers to consume. Enabled for producing How many consumers allowed consumed These are tags whose values are produced by another controller. Controller name that owns the tag that the local controller wants to consume Tag name or instance that the controller wants to consume Data type of the tag to consume Update interval of how often the local controller consumes the tag The producer and consumer must be configured correctly for the specified data to be shared. A produced tag in the producer must be specified exactly the same as a consumed tag in the consumer. If any produced/consumed tag between a producer and consumer is not specified correctly, none of the produced/consumed tags for that producer and consumer will be transferred. However, other consumers can still access their shared tags, as long as their tags are specified correctly. One consumer failing to access shared data does not affect other consumers accessing the same data. Communicating with Devices on a ControlNet Link 7-15 Maximum Number of Produced and Consumed Tags The maximum number of produced/consumed tags that you can configure depends on the connection limits of the communication device that transfers the produced/consumed data. Each produced tag uses one connection for the tag and the first configured consumer of the tag. Each consumer thereafter uses an additional connection. Size Limit of a Produced or Consumed Tag A produced or consumed tag can be as large as 488 bytes, but it must also fit within the bandwidth of the ControlNet network: • As the number of connections over a ControlNet network increases, several connections, including produced or consumed tags, may need to share a network update. • Since a ControlNet network can only pass 500 bytes in one update, the data of each connection must be less than 488 bytes to fit into the update. If a produced or consumed tag is too large for your ControlNet network, make one or more of the following adjustments: • Reduce the Network Update Time (NUT). At a faster NUT, less connections have to share an update slot. • Increase the Requested Packet Interval (RPI) of all connections. At a higher RPI, connections can take turns sending data during an update slot. • For a ControlNet bridge module (CNB) in a remote chassis, select the most efficient communication format for that chassis: Are most of the modules in the chassis non-diagnostic, digital I/O modules? Then select this communication format for the remote communication module: yes rack optimization no none The Rack Optimization format uses an additional 8 bytes for each slot in its chassis. Analog modules or modules that are sending or getting diagnostic, fuse, or timestamp data require direct connections and cannot take advantage of the rack optimized form. Selecting “None” frees up the 8 bytes per slot for other uses, such as produced or consumed tags. • Separate the tag into two or more smaller tags: – Group the data according to similar update rates. For example, you could create one tag for data that is critical and another tag for data that is not as critical. – Assign a different RPI to each tag. • Create logic to transfer the data in smaller sections (packets). 7-16 Communicating with Devices on a ControlNet Link Producing a Tag Produced data must be of DINT or REAL data type or an array or structure. You can use a user-defined structure to group BOOL, SINT, and INT data to be produced. To create a produced tag: 1. You must be programming offline. 2. In the controller organizer, double-click the Controller Tags folder and then click the Edit Tags tab. 3. Select the tag that you want to produce, or enter a new tag, and display the Tag Properties dialog box. 4. Make sure the tag is controller scope. 5. Select the “Produce this tag” check box. Specify how many controllers can consume the tag. You can produce a base, alias, or consumed tag. The consumed tag in a receiving controller must have the same data type as the produced tag in the originating controller. The controller performs type checking to ensure proper data is being received. Produced tags require connections. The number of connections depends on how many controllers are consuming the tags. The controller requires one connection for the produced tag and the first consumer. Then, the controller requires an additional connection for each subsequent consumer. Consuming a Tag A consumed tag represents data that is produced (broadcast) by one controller and received and stored by the consuming controller. To create a consumed tag: Communicating with Devices on a ControlNet Link 7-17 1. You must be programming offline. 2. In the controller organizer, double-click the Controller Tags folder and then click the Edit Tags tab. 3. Select the tag that you want to consume, or enter a new tag, and display the Tag Properties dialog box. 4. Specify: In this field: Type or select: Tag Type Select Consumed. Controller Select the name of the other controller. You must have already created the controller in the controller organizer for the controller name to be available. Remote Tag Name Remote Instance Type a name for the tag in the other controller you want to consume. Important: The name must match the name in the remote controller exactly, or the connection faults. If the remote controller is a ControlNet PLC-5, this field is Remote Instance. Select the instance number (1-128) of the data on the remote controller. RPI (requested packet interval) Type the amount of time in msec between updates of the data from the remote controller. The local controller will receive data at least this fast. Display Style If you are creating a consumed tag that refers to a tag whose data type is BOOL, SINT, INT, DINT, or REAL, you can select a display style. This display style defines how the tag value will be displayed in the data monitor and ladder editor. The display style does not have to match the display style of the tag in the remote controller. All consumed tags are automatically controller-scope. To consume data from a remote controller, use RSNetWorx software to schedule the connection over the ControlNet network. The produced tag in the originating DriveLogix controller must have the same data type as the consumed tag in the other DriveLogix controller. The DriveLogix controller performs type checking to ensure proper data is being received. Important: If a consumed-tag connection fails, all of the other tags being consumed from that remote controller stop receiving data. Guidelines for Configuring Connections The 1788-CNx communication daughtercard supports 9 scheduled connections. How you configure these connections determines how many devices the daughtercard can support. The NUT and RPI also play a part in determining how many connections a 1788-CNx can support in a given application, assuming the RPIs will be the same for all connections. You must also make sure that you do not exceed the maximum number of bytes per NUT. • With the NUT = 5ms, the limit is 3 connections • With the NUT = 10ms, the limit is 7connections • With the NUT > 20ms, the limit is 9 connections 7-18 Communicating with Devices on a ControlNet Link Determining the API The API (actual packets per interval) is related to the RPI for the connection and the NUT of the network. Use this table to select the API to enter in the above worksheet: Enter this value for the API: RPI ≥ NUT and RPI < 2∗NUT NUT RPI ≥ 2∗NUT and RPI < 4∗NUT 2∗NUT RPI ≥ 4∗NUT and RPI < 8∗NUT 4∗NUT RPI ≥ 8∗NUT and RPI < 16∗NUT 8∗NUT RPI ≥ 16∗NUT and RPI < 32∗NUT 16∗NUT RPI ≥ 32∗NUT and RPI < 64∗NUT 32∗NUT RPI ≥ 64∗NUT and RPI < 128∗NUT 64∗NUT RPI ≥ 128∗NUT 128∗NUT In the following example, one DriveLogix5730 controller controls remote I/O through a 1794-ACN15 module. ahw0933.eps Example 1: DriveLogix Controller and Remote I/O If: DriveLogix5730 Controller (DriveLogix1) ControlNet 1794-ACN with remote I/O (Remote1) Example 1: Controlling Remote Devices This example has DriveLogix1 controlling the I/O connected to the remote 1794-ACN15 module. The data the DriveLogix controller receives from the remote I/O modules depends on how you configure the remote I/O modules. You can configure each module as a direct connection or as rack optimized. One chassis can have a combination of some modules configured as a direct connection and others as rack optimized. Communicating with Devices on a ControlNet Link 7-19 Example 1: Total Connections Required by DriveLogix1 The following table calculates the connections used in this example. Connection: Amount: DriveLogix1 controller to 3 local I/O modules rack-optimized connection for the DIN rail direct connection for each I/O module 1 3 DriveLogix1 controller to remote 1794-ACNR15 1 DriveLogix1 to 4 remote I/O modules (through 1794-ACNR15) all I/O modules configured as direct connection no connection to the 1794-ACNR15 4 total connections used: 9 If you configured the remote I/O modules as rack-optimized, you would only need a rack-optimized connection to the 1794-ACNR15, reducing the above example by 3 connections. Example 2: DriveLogix5730 Controller to DriveLogix5730 Controller In the following example, one DriveLogix5730 controller communicates with another DriveLogix5730 controller over ControlNet. Each DriveLogix controller has its own local I/O. ahw0934.eps DriveLogix5730 Controller (DriveLogix1) DriveLogix5730 Controller (DriveLogix2) workstation ControlNet Example 2: Sending a MSG Instruction To send a MSG from DriveLogix1 to DriveLogix2: 1. For DriveLogix1, create a controller-scoped tag and select the MESSAGE data type. 2. Enter a MSG instruction. ahw0913.eps In this example logic, a message is sent when a specific condition is met. When count_send is set, the ladder logic sends the count_msg MSG. Communicating with Devices on a ControlNet Link 3. Configure the MSG instruction. On the Configuration tab: For this item: Specify: Message Type CIP Data Table Read or CIP Data Table Write Source Tag Tag containing the data to be transferred Number of Elements Number of array elements to transfer Destination Tag Tag to which the data will be transferred 4. On the Communication tab, specify the communication path. A communication path requires pairs of numbers. The first number in the pair identifies the port from which the message exits. The second number in the pair designates the node address of the next device. For this item: Specify: Communication Path 1,4,2,27,1,0 where: 1 is the virtual backplane of DriveLogix1 4 is 1788-CNC daughtercard in slot 1 2 is the ControlNet port 27 is the ControlNet node of DriveLogix2 1 is the virtual backplane of DriveLogix2 0 is the controller slot of DriveLogix2 Example 2: Producing and Consuming Tags Produced data must be of DINT or REAL data type or an array or structure. You can use a user-defined structure to group BOOL, SINT, and INT data to be produced. You can produce a base, alias, or consumed tag. The consumed tag must have the same data type as the produced tag in the originating controller. The controller performs type checking to ensure proper data is being received. ahw0934.eps 7-20 ControlNet DriveLogix1 tagA DINT tagB Real DriveLogix2 (controllerb) tagA DINT tagB Real workstation Communicating with Devices on a ControlNet Link 7-21 ahw0912.eps ahw0909.eps ahw0910.eps ahw0908.eps ahw0935.eps This example shows DriveLogix1 producing tagA and consuming tagB: 7-22 Communicating with Devices on a ControlNet Link Each produced tags requires one connection for the producing controller and an additional connection for each consuming controller. Each consumed tag requires one connection. Example 2: Total connections required by DriveLogix1 The following table calculates the connections used in this example. Connection: Amount: DriveLogix1 controller to 3 local I/O modules rack-optimized connection for the DIN rail direct connection for each I/O module 1 3 DriveLogix1 controller to local 1788-CNC 0 DriveLogix1 controller to remote 1788-CNC 0 connected, cached MSG from DriveLogix1 to DriveLogix2 1 produced tagA produced from DriveLogix1 to DriveLogix2 other consumer (2 are configured) 1 1 produced tagA produced from DriveLogix1 to DriveLogix2 other consumer (2 are configured) 1 1 consumed TagB 1 total connections used: 10 If you configured the local I/O modules as rack-optimized, you would only need the DIN-rail connection to the I/O modules, reducing the above example by 3 connections. In the following example, one DriveLogix controller communicates with a Logix5550 controller and a ControlNet PLC-5 controller over ControlNet. ahw0936.eps Example 3: DriveLogix Controller to Other Devices ControlNet DriveLogix5730 Controller (DriveLogix1) ControlLogix Controller (Control1) ControlNet PLC5 Controller (PLC5C1) DriveLogix5730 Controller (DriveLogix2) Communicating with Devices on a ControlNet Link 7-23 Example 3: Sending MSG Instructions You configure a MSG instruction to a Logix5550 controller the same as you do for a DriveLogix controller. All Logix-based controllers follow the same MSG configuration requirements. See Example 2 above. Configuring a MSG instruction for a PLC-5 controller depends on the originating controller. For MSG instructions originating from the DriveLogix controller to the ControlNet PLC-5 controller: Type of Logix MSG instruction: Source: Destination: Typed Read any integer element (such as B3:0, T4:0.ACC, C5:0.ACC, N7:0, etc.) SINT, INT, or DINT tag any floating point element (such as F8:0, PD10:0.SP, etc.) REAL tag SINT or INT tag any integer element (such as B3:0, T4:0.ACC, C5:0.ACC, N7:0, etc.) REAL tag any floating point element (such as F8:0, PD10:0.SP, etc.) Word Range Read any data type (such as B3:0, T4:0, C5:0, R6:0, N7:0, F8:0, etc.) SINT, INT, DINT, or REAL Word Range Write SINT, INT, DINT, or REAL any data type (such as B3:0, T4:0, C5:0, R6:0, N7:0, F8:0, etc.) Typed Write The PLC-5 controller supports logical ASCII addressing so you do not have to map a compatibility file for MSG instructions initiated by a PLC-5 controller. Place the DriveLogix tag name in double quotes (“). Type of MSG Instruction: Example Source and Destination: PLC-5 writes to DriveLogix source element N7:10 destination tag “array_1” source tag “array_1” destination element N7:10 PLC-5 reads from DriveLogix Example 3: Producing and Consuming Tags You can produce and consume tags with any Logix controller the same as you do with a DriveLogix controller. All Logix controllers follow the same requirements for producing and consuming tags. See Example 2 above. 7-24 Communicating with Devices on a ControlNet Link ahw0936.eps Producing and consuming tags with a ControlNet PLC-5 controller depends on the type of data. ControlNet DriveLogix5730 Controller (DriveLogix1) tagA ControlLogix Controller (Control1) DINT ControlNet PLC5 Controller (PLC5C1) DriveLogix5730 Controller (DriveLogix2) Producing a Tag to a ControlNet PLC-5 controller To produce a tag that a ControlNet PLC-5 controller can consume: 1. Determine the type of data to produce? If: And you are producing: Then: INT na Create a user-defined data type that contains an array of INTs with an even number of elements, such as INT[2]. When you produce INTs, you must produce two or more. Create a produced tag and select the user-defined data type you created. DINT or REAL Only one DINT or REAL value Create a produced tag and select the DINT or REAL data type, as appropriate. More than one DINT or REAL Create a user-defined data type that contains an array of DINTs or REALs, as appropriate. Create a produced tag and select the user-defined data type you created. 2. In RSNetWorx software, open the ControlNet configuration for the target ControlNet PLC-5 controller, insert a Receive Scheduled Message and enter the following Message size: If the produced tag contains: Then, for the Message size, enter: INTs The number of integers in the produced tag DINTs Two times the number of DINTs or REALs in the produced tag. For example, if the produced tag contains 10 DINTs, enter 20 for the Message size. REALs 3. In the RSNetWorx software, reschedule (save) the network. The ControlNet PLC-5 controller does not perform type checking. Make sure the PLC-5 data type can correctly receive the DriveLogix produced tag to ensure proper data is being received. When a ControlNet PLC-5 controller consumes a tag that is produced by a Logix5000 controller, it stores the data in consecutive 16-bit integers. Communicating with Devices on a ControlNet Link 7-25 The ControlNet PLC-5 controller stores floating-point data, which requires 32-bits regardless of the type of controller, as follows: – The first integer contains the upper (left-most) bits of the value. – The second integer contains the lower (right-most) bits of the value. To re-construct the floating point data within the ControlNet PLC-5 controller, first reverse the order of the integers and then copy them to a floating-point file. Consuming a Tag from a ControlNet PLC-5 Controller To consume a tag from a ControlNet PLC-5 controller,: 1. In RSNetWorx software, open the ControlNet configuration of the ControlNet PLC-5 controller, insert a Send Scheduled Message. 2. In RSLogix 5000 software, add the ControlNet PLC-5 controller to the Controller Organizer. 3. Create a user-defined data type that contains these members: Data type: Description: DINT Status INT[x], where “x” is the output size of the data from the ControlNet PLC-5 controller. (If you are consuming only one INT, no dimension is required.) Data produced by a ControlNet PLC-5 controller 4. Create a consumed tag with the following properties: For this tag property: Type or select: Tag Type Consumed Controller The ControlNet PLC-5 that is producing the data Remote Instance The message number from the ControlNet configuration of the ControlNet PLC-5 controller RPI A power of two times the NUT of the ControlNet network. For example, if the NUT is 5ms, select an RPI of 5, 10, 20, 40, etc. Data Type The user-defined data type that you created. 5. In the RSNetWorx for ControlNet software, reschedule (save) the network. 7-26 Communicating with Devices on a ControlNet Link Example 3: Total Connections Required by DriveLogix1 The following table calculates the connections used in this example. Connection: Amount: DriveLogix1 controller to 3 local I/O modules rack-optimized connection for the DIN rail direct connection for each I/O module 1 3 DriveLogix1 controller to local 1788-CNC 0 DriveLogix1 controller to remote 1756-CNB 1 DriveLogix1 controller to remote ControlNet PLC-5 1 connected, cached MSG from DriveLogix1 to Control1 1 connected, cached MSG from DriveLogix1 to PLC5C1 1 Produced TagA produced from DriveLogix1 to DriveLogix2 consumed by PLC5C1 1 1 Consumed TagB from DriveLogix2 1 Consumed INT from PLC5C1 1 total connections used: 12 If you configured the local I/O modules as rack-optimized, you would only need the DIN-rail connection to the I/O modules, reducing the above example by 3 connections. You can configure the 1756-CNB module to use no connection. This is useful if you configure all direct connections to their associated I/O modules and do not need a rack-optimized connection. Chapter 8 Communicating with Devices on a DeviceNet Link De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of configuring DeviceNet communication you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with configuring DeviceNet communication. 8-2 Communicating with Devices on a DeviceNet Link For the DriveLogix controller to operate on a DeviceNet link, you need: • a workstation with an appropriate DeviceNet interface card • RSLinx software to configure the DeviceNet communication driver • RSLogix 5000 programming software (Version 13 or later) to configure the DeviceNet communication daughtercard or local 1769-SDN DeviceNet scanner module as part of the DriveLogix system • a NetLinx DeviceNet communication daughtercard installed on the DriveLogix controller (refer to Installing the Communications Daughtercard on page B-9) or ahw0939.eps • 1769-SDN DeviceNet scanner module installed on the a bank of local Compact I/O controlled by the DriveLogix controller DriveLogix controller with 1769-SDN Scanner Module installed in a bank of Compact I/O or DriveLogix controller with 1788-DNBO Communications Daughtercard DeviceNet DeviceNet This example uses a NetLinx DeviceNet communication daughtercard installed on the DriveLogix controller to control a bank of I/O attached to a 1769-ADN adapter module. ahw0953.eps Example: Controlling I/O Over DeviceNet DriveLogix controller with 1788-DNBO Communications Daughtercard DeviceNet MS NS IO DIAG 1769-ADN Scanner Module installed in a bank of Compact I/O Communicating with Devices on a DeviceNet Link 8-3 Configuring the 1769-ADN Adapter In RSNetWorx for DeviceNet, select Online from the Network menu. Choose the appropriate driver depending on whether the computer is directly connected to DeviceNet or you are accessing the network through a controller’s backplane and using a different port. ahw0945.tif 1. continued Communicating with Devices on a DeviceNet Link The software then prompts you to either upload or download. Choose upload. RSNetWorx will then browse the network and obtain their settings. ahw0946.tif 2. 3. Right click on the 1769-ADN and choose Properties. ahw0947.tif 8-4 4. Click on the I/O Bank 1 Configuration tab, then choose upload when prompted. The actual 1769-ADN I/O layout appears. From this screen you can configure the I/O modules in the 1769-ADN system by simply clicking on the slot number box associated with each I/O module. 5. When the I/O modules are configured, click on the Summary tab. Note the number of bytes of input and output data. This will be used later when adding the adapter to the 1769-SDN’s scanlist. 6. Click Apply, then OK to save the configuration and download it to the adapter. Communicating with Devices on a DeviceNet Link 8-5 TIP: Configuration changes made to the adapter or any of its I/O modules with RSNetWorx will not be saved or downloaded to the adapter once the adapter is configured in a scanner’s scanlist. To make configuration changes, the controller must be placed into the Program mode and the adapter must be temporarily removed from the scanner’s scanlist. Setting Up the 1788-DNBO DeviceNet Scanner Scanlist Right click on the 1788-DNBO and choose Properties. ahw0948.tif 1. Click the Scanlist tab, then click Upload when prompted. The area on the left is called “Available Devices” and the area on the right is called “Scanlist”. The 1769-ADN adapter should be on the left. ahw0949.tif 2. 8-6 Click on the adapter, then click on the single arrow pointing to the right. This moves the adapter from Available Devices to the scanner’s scanlist. ahw0951.tif ahw0950.tif Then click on the Edit I/O Parameters button 4. Verify that the Input Size and Output Size are correct. The Output and Input sizes correspond to the total number of output and input bytes noted from the adapter’s summary page. In this example, the scanner transmits 6 bytes to the adapter (output data) and receives 28 bytes from the adapter (input data). Click OK when finished with this screen. ahw0952.tif 3. Communicating with Devices on a DeviceNet Link 5. Click on the Input tab. Then click Apply and OK. Download when prompted. Communicating with Devices on a DeviceNet Link 8-7 Mapping starts at word 0 for both the input and the output data image. The input status and output configuration words are no longer included with the I/O data scanlist. Use the status and configuration tags created in RSLogix 5000 software to read status or set configuration bits. TIP: The input and output data being exchanged by the scanner and adapter is packed data. This means that there is no special structure to it that makes it obvious which I/O module it is associated with. To establish which data is from which module, you must list the number of input and output words each module has. Then, based on its position in the I/O bank, you can determine where any module’s data is in the controller’s I/O tags. Transferring Data There are 28 bytes of input data and 6 bytes of output data for this example. The I/O modules in the adapter’s system are: Module Input Output ADN Status Information (added by the 1769-ADN) 1 DINT word 0 words 1769-IA16 1/2 DINT word 0 words 1769-OB16 1/2 DINT word 1/2 DINT word 1769-IF4 3 DINT words 0 words 1769-OF2 2 DINT words 1 DINT word Total Words 7 DINT words 1 1/2 DINT words Total Bytes 28 bytes 6 bytes The total is 7 DINT words or 28 input bytes. The first DINT word is adapter status, leaving 6 DINT words (24 bytes) for data. The input data maps to the controller’s input data tag at the following word locations: Location Description Word 0 1769-ADN status information Word 1 1769-IA16 module’s input word Word 1 1769-OB16 module’s input data (output data echo) Words 2-4 1769-IF4 module’s input data Words 5-6 1769-OF2 module’s input data The output data can be determined in a similar manner. This data begins with word 0 of the output tag in the controller as follows: Location Description Word 0 1769-OB16 module’s output word Words 0-1 1769-OF2 module’s output words Communicating with Devices on a DeviceNet Link Module Command Array The module command array is the primary control interface between your control program and the module. In RSLogix 5000 software, the CommandRegister tag structure is as follows: ahw0953.tif 8-8 Output Word Bit Description Behavior 0 0 Run This bit controls when the module scans its mapped slave devices. When set (1), the scanner will process I/O data as defined by its scanlist. To actually scan the network the Fault and Disable Network command bits must be clear (0). 1 Fault When set, the scanner’s I/O mode will be Halt; messaging will still operate. The fault bit is primarily used to artificially set the slave devices into a fault state due to some event or condition within the control program. 2 Disable Network When set, the scanner is functionally removed from the network. 3 HaltScanner When set, the scanner stops scanning its mapped slave devices. 4 Reset Restarts access to the DeviceNet network. Communicating with Devices on a DeviceNet Link Creating a Project for the DriveLogix5730 Controller 2. Select the 1788-DNBO DeviceNet Scanner from the list of possible communication devices. Click OK. ahw0940.tif ahw0939.tif In the Controller Organizer, select the I/O Configuration folder. Right-click the selected folder and select New Module. ahw0941.tif 1. 3. Enter a Name for the port and make sure it is assigned to slot 4. Click Finish. 8-9 8-10 Communicating with Devices on a DeviceNet Link If you are using a 1769-SDN Scanner Module, add it to the local CompactBus: ahw0942.tif In the Controller Organizer, select the I/O Configuration folder. Right-click the selected Local CompactBus and select New Module. Select the 1769-SDN DeviceNet Scanner from the list of possible communication devices. Click OK. ahw0943.tif 2. ahw0944.tif 1. 3. Enter a Name for the port and make sure it is assigned to appropriate I/O slot. Click Finish. Communicating with Devices on a DeviceNet Link 8-11 All tags for I/O modules are automatically created when the profiles for these modules are configured. Double click on Controller Tags in the controller organizer to view these tags. Each I/O module slot has Input, Output and Configuration tags created, if they apply. These tags are structured as: Tag Definition Local:s:I s is the slot number I represents Input Data Local:s:O O represents Output Data Local:s:C C represents Configuration Data If the 1769-SDN is in slot 1, the input addresses for the scanner are: Tag Definition Local:1:I.Data[0] 1769-ADN Status Information Local:1:I.Data[1] Input Data from 1769-IA16 Local:1:I.Data[1] Input (output echo) Data from 1769-OB16 Local:1:I.Data[2] through Local:3:I.Data[4] Input Data from 1769-IF4 Local:1:I.Data[5] through Local:3:I.Data[6] Input Data from 1769-OF2 This output addresses for the scanner are: Tag Definition Local:1:O.Data[0] Output data for 1769-OB16 Local:1:O.Data[0] through Local:3:O.Data[1] Output data for 1769-OF2 ahw0953.tif The controller uses the CommandRegister (Local:1:O.CommandRegister) to send commands to the scanner Communicating with Devices on a DeviceNet Link Entering Program Logic The program for this example consists of a single rung that is used to place the scanner into the RUN mode. ahw0955.tif 8-12 Chapter 9 Communicating with Devices on a DH485 Link De-energizing the Drive to Connect or Disconnect a Cable ! ATTENTION: Severe injury or death can result from electrical shock or burn. Verify that the voltage on the bus capacitors has discharged before connecting to the communication ports. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. During the process of configuring DH485 communication you will need to connect or disconnect a programming or network cable at the controller. You should do this only if the drive is de-energized. 1. Turn off and lock out input power. Wait five minutes. 2. Verify that there is no voltage at the drive’s input power terminals. 3. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. 4. Connect or disconnect the programming or network cable. 5. Turn power back on and proceed with configuring DH485 communication. Understanding How the DriveLogix5730 Controller Supports DH485 Communications When using a DriveLogix5730 controller it is recommended that you use NetLinx networks (EtherNet/IP, ControlNet, or DeviceNet) because excessive traffic on a DH-485 network may make it impractical to connect to a DriveLogix5730 controller with RSLogix 5000 programming software. DriveLogix5730 processors fully support the DH-485 protocol, but using the recommended NetLinx networks is more practical. The DH-485 protocol uses RS-485 half-duplex as its physical interface. (RS-485 is a definition of electrical characteristics; it is not a protocol.) You can configure the RS-232 port of the DriveLogix5730 controller to act as a DH-485 interface. By using a 1761-NET-AIC and the appropriate RS232 cable (1756-CP3 or 1747-CP3), a DriveLogix5730 controller can send and receive data on a DH-485 network. Important: A DH-485 network consists of multiple cable segments. Limit the total length of all the segments to 1219m (4000 ft.). 9-2 Communicating with Devices on a DH485 Link Configuring Your System for For the DriveLogix5730 controller to operate on a DH-485 network, you need: a DH-485 Link a 1761-NET-AIC interface converter for each DriveLogix5730 controller you want to put on the DH-485 network. You can have two controllers per one 1761-NET-AIC converter, but you need a different cable for each controller. Connect one controller to port 1 (9-pin connector) and one controller to port 2 (mini-DIN connector). RSLogix 5000 programming software to configure the serial port of the controller for DH-485 communications. When attempting to go online or upload/download a program using the Communications/Who Active window in RSLogix 5000 software, disable the Autobrowse feature to minimize traffic from RSLogix 5000 software on the DH-485 network. Step 1: Configure the Hardware The RS-232 port is built-in to the front of the DriveLogix5730 controller. The 1769-L31 controller has two serial ports. Connect the serial port to an RS-232-to-RS-485 interface converter. One possible converter is the 1761-NET-AIC interface converter. RS-485 port port 2: mini-DIN 8 RS-232 baud rate selector switch port 1: DB-9 RS-232, DTE ahw0610.eps dc power source selector switch terminals for external 24V dc power supply Connect the serial port of the DriveLogix5730 controller to either port 1 or port 2 of the 1761-NET-AIC converter. Use the RS-485 port to connect the converter to the DH-485 network. Communicating with Devices on a DH485 Link 9-3 The cable you use to connect the controller depends on the port you use on the 1761-NET-AIC converter. If you connect to this port: Use this cable: port 1 DB-9 RS-232, DTE connection 1747-CP3 or 1761-CBL-AC00 port 2 mini-DIN 8 RS-232 connection 1761-CBL-AP00 or 1761-CBL-PM02 Step 2: Configure the DH-485 port of the controller 1. In RSLogix 5000 programming software, select the Controller folder. Right-click to select Properties. 2. On the System Protocol tab, specify the appropriate serial communication configuration. ahw0600.tif ahw0601.tif 3. On the Serial Port tab, specify the appropriate communication settings. ahw0602.tif The grayed out settings are selections that do not apply to a DH-485 network. 9-4 Communicating with Devices on a DH485 Link Specify these characteristics on the Serial Port tab (default values are shown in bold): Characteristic: Description (default is shown in bold): Baud Rate Specifies the communication rate for the DH-485 port. All devices on the same DH-485 network must be configured for the same baud rate. Select 9600 or 19200 Kbps. Node Address Specifies the node address of the DriveLogix controller on the DH-485 network. Select a number 1-31 decimal, inclusive. To optimize network performance, assign node addresses in sequential order. Initiators, such as personal computers, should be assigned the lowest address numbers to minimize the time required to initialize the network. Token Hold Factor Number of transmissions (plus retries) that a node holding a token can send onto the data link each time that it receives the token. Enter a value between 1-4. The default is 1. Maximum Node Address Specifies the maximum node address of all the devices on the DH-485 network. Select a number 1-31 decimal, inclusive. To optimize network performance, make sure: the maximum node address is the highest node number being used on the network that all the devices on the same DH-485 network have the same selection for the maximum node address. Planning a DH-485 Network The DH-485 network offers: • • • • • interconnection of 32 devices multi-master capability token passing access control the ability to add or remove nodes without disrupting the network maximum network length of 1219 m (4000 ft.) The DH-485 protocol supports two classes of devices: initiators and responders. All initiators on the network get a chance to initiate message transfers. The DH-485 protocol uses a token-pass algorithm to determine which initiator has the right to transmit DH-485 Token Rotation A node holding the token can send any valid packet onto the network. Each node gets only one transmission (plus two retries) each time it receives the token. After a node sends one message packet, it attempts to give the token to its successor by sending a “token pass” packet to its successor. If no network activity occurs, the initiator sends the token pass packet again. After two retries (a total of three tries) the initiator attempts to find a new successor. Important: The maximum address that the initiator searches for before starting again with zero is the value in the configurable parameter “maximum node address.” The default value for this parameter is 31 for all initiators and responders. Communicating with Devices on a DH485 Link 9-5 The allowable range of the node address of an initiator is 0 to 31. The allowable address range for all responders is 1 to 31. There must be at least one initiator on the network. Network Initialization The network requires at least one initiator to initialize it. Network initialization begins when an initiator on the network detects a period of inactivity that exceeds the time of a link dead timeout. When the link dead timeout is exceeded, usually the initiator with the lowest address claims the token. When an initiator has the token it will begin to build the network. Building a network begins when the initiator that claimed the token tries to pass the token to the successor node. If the attempt to pass the token fails, or if the initiator has no established successor (for example, when it powers up), it begins a linear search for a successor starting with the node above it in the addressing. When the initiator finds another active initiator, it passes the token to that node, which repeats the process until the token is passed all the way around the network to the first node. At this point, the network is in a state of normal operation. Number of Nodes and Node Addresses The number of nodes on the network directly affects the data transfer time between nodes. Unnecessary nodes (such as a second programming terminal that is not being used) slow the data transfer rate. The maximum number of nodes on the network is 32. If the node addresses for controllers are assigned in sequence, starting at node 1 (with node 0 left for a programming terminal), it is as efficient to leave the maximum node address at 31 as it is to decrease it to the highest node address on the network. Then, adding devices to the network at a later time will not require modifying the maximum node address in every device on the network. The maximum node address should be the same for all devices on a DH-485 network for optimal operation. The best network performance occurs when node addresses start at 0 and are assigned in sequential order. The controller defaults to node address 1 (controllers cannot be node 0). Initiators, such as personal computers, should be assigned the lowest numbered addresses to minimize the time required to initialize the network. 9-6 Communicating with Devices on a DH485 Link Installing a DH-485 Network A DH-485 network consists of a number of cable segments daisy-chained together. The total length of the cable segments cannot exceed 1219 m (4000 ft). Important: Use shielded, twisted-pair cable - either Belden 3106A or Belden 9842. A daisy-chained network is recommended. Star connections are not recommended ahw0606.eps When cutting cable segments, make them long enough to route them from one link coupler to the next with sufficient slack to prevent strain on the connector. Allow enough extra cable to prevent chafing and kinking in the cable. Figure 9.1 Single Cable Connection Shrink Tubing (Recommended) Belden 3106A or 9842 Cable (3106A Shown) tion ina erm 6 T ta A a 5 D ta B a n 4 D mmo o nd 3 C ield Grou h 2 S assis h 1C Orange Wire with White Stripe (OR/WH) White Wire with Orange Stripe (WH/OR) Blue Wire (BU) Drain Wire (Shield) ahw0603.eps Communicating with Devices on a DH485 Link Connections Using Belden 3106 Cable The table and schematic diagram below shows wire/terminal connections for Belden 3106A cable. 6 5 4 3 2 1 OR/WH WH/OR BU ahw0604.eps Termination Data A Data B Common Shield Chassis Ground For this Wire/Pair Connect this Wire To this Terminal white/orange orange with white stripe 5 - Data A) white with orange stripe 4 - (Data B) blue blue 3 - (Common) shield/drain non-jacketed 2 - Shield Connections Using Belden 9842 Cable The table and schematic diagram below shows wire/terminal connections for Belden 9842 cable. ahw0609.eps OR/WH WH/OR BU/WH WH/BU 6 5 4 3 2 1 Termination Data A Data B Common Shield Chassis Ground For this Wire/Pair Connect this Wire To this Terminal white/orange orange with white stripe 5 - (Data A) white with orange stripe 4 - (Data B) white with blue stripe cut back - no connection(1) blue with white stripe 3 - (Common) non-jacketed 2 - Shield blue/white shield/drain (1) To prevent confusion when installing the communication cable, cut back the white with blue stripe wire immediately after the insulation jacket is removed. This wire is not used by DH-485. 9-7 9-8 Communicating with Devices on a DH485 Link Grounding and Terminating a DH-485 Network You must terminate the network at the first and last PHYSICAL devices, by connecting pin 6 (Termination) to pin 5 (Data A). You must ground the network at the first PHYSICAL device by connecting pin 1 (Chassis Ground) to pin 2 (Shield). Add jumpers to connect pin 6 (Termination) to pin 5 (Data A) on the first and last PHYSICAL devices ahw0607.eps Termination Data A Data B Common Shield Chassis Ground 6 5 4 3 2 1 OR/WH WH/OR BU OR/WH WH/OR BU 6 5 4 3 2 1 Termination Data A Data B Common Shield Chassis Ground Add jumper to connect pin 1 (Chassis Ground) to pin 2 (Shield) on the first PHYSICAL device Important: A device’s physical location may be independent of its node address. Make sure you ground and terminate the proper PHYSICAL locations. Communicating with Devices on a DH485 Link 9-9 Browsing a DH-485 Network To improve performance when browsing a DH-485 network, configure the DH-485 network properties in RSLinx software to display only those nodes Remotely that actually exist on the network. 1. In RSLinx software, right-click on the DH-485 network you plan to browse and select Properties. 2. On the Browse Addresses tab, specify the lowest and highest addresses that exist on the DH-485 network. ahw0954.tif If you do not specify a specific range of addresses on the DH-485 network, the RSWho function in RSLinx software attempts to locate a device at every node address. Trying to locate devices that do not exist adds considerable time to displaying the RSWho window for the network. 9-10 Notes: Communicating with Devices on a DH485 Link Appendix A DriveLogix5730 Controller Specifications DriveLogix5730 Controller Specifications Category serial port (CH0 -RS-232) Specification RS-232, fully isolated DF1, DH-485, ASCII 38.4 Kbits/s maximum optional embedded EtherNet/IP RJ-45 or 100BaseT 10/100 Mbytes/sec connectivity options • NetLinx communication daughtercards (these options require the Logix (ControlNet, EtherNet/IP, DeviceNet, Third Party) Expansion Board and Expanded • Compact I/O connection Cassette) • CompactFlash (memory card) user memory 1.5 Mbyte nonvolatile memory 1784-CF64 CompactFlash maximum number of I/O banks 2 maximum number of I/O modules 16 (8 modules per bank) or (4 max on either side of the power supply) battery 1769-BA serial cable 1756-CP3 directly to controller Compact I/O Cable 1747-CP3 directly to controller 20D-DL2-CR3 20D-DL2-CL3 DriveLogix5730 Environmental Specifications Category operating temperature storage temperature relative humidity vibration shock emissions Electrical/EMC ESD Immunity (IEC61000-4-2) Radiated RF Immunity (IEC61000-4-3) Surge Transient Immunity (IEC61000-4-5) Conducted RF Immunity (IEC61000-4-6) Specification CISPA11: Group 1, Class A The unit has passed testing at the following levels: 4 kV contact discharges, 8 kV air discharges 10V/M with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900MHz +1 kV line-line (DM) and +2 kV line-earth (CM) on signal ports A-2 DriveLogix5730 Controller Specifications DriveLogix5730 Certifications Certification c-UL-us CE(1) C-Tick(1) Pending at time of printing EtherNet/IP c-UL-us (1) Real-Time Clock Accuracy Description UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada European Union 89/336/EEC EMC Directive, compliant with: • EN 50082-2; Industrial Immunity • EN 61326; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions Australian Radio communications Act, compliant with: • AS/NZS CISPR 11; Industrial Emissions ODVA conformance tested to EtherNet/IP specifications UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details. Ambient °C 0°C +25°C +40°C +55°C +60°C Accuracy +54 to -56 seconds/month +9 to -124 seconds/month -84 to -234 seconds/month -228 to -394 seconds/month -287 to -459 seconds/month DriveLogix5730 Controller Specifications A-3 Controller LEDs ! ATTENTION: The controller LEDs are only operational when the drive is energized, and only visible with the drive door open. Servicing energized equipment can be hazardous. Severe injury or death can result from electrical shock, burn or unintended actuation of controlled equipment. Follow Safety related practices of NFPA 70E, ELECTRICAL SAFETY FOR EMPLOYEE WORKPLACES. DO NOT work alone on energized equipment! RUN (Drive)(1) RUN (DriveLogix) FORCE I/O COM BAT (1) Do not confuse the Drive Run LED with the DriveLogix Run LED. The Drive Run LED indicates a drive function NOT a DriveLogix function. led_drivelogix.eps OK A-4 DriveLogix5730 Controller Specifications Indicator: Color: Description: RUN off The controller is in Program or Test mode. FORCE BAT I/O COM OK solid green The controller is in Run mode. off No tags contain I/O force values. I/O forces are inactive (disabled). solid amber I/O forces are active (enabled). I/O force values may or may not exist. flashing amber One or more input or output addresses have been forced to an On or Off state, but the forces have not been enabled. off The battery supports memory. solid red Either the battery is: not installed. 95% discharged and should be replaced. off Either: There are no devices in the I/O configuration of the controller. The controller does not contain a project (controller memory is empty). solid green The controller is communicating with all the devices in its I/O configuration. flashing green One or more devices in the I/O configuration of the controller are not responding. flashing red The controller is not communicating to any devices. The controller is faulted. off No RS-232 activity. flashing green RS-232 activity. off No power is applied. flashing red If the controller is: Then: a new controller the controller requires a firmware update not a new controller A major fault occurred. To clear the fault, either: - Turn the key switch from PROG to RUN to PROG - Go online with RSLogix 5000 software solid red The controller detected a non-recoverable fault, so it cleared the project from memory. To recover: Cycle power to the chassis. Download the project. Change to Run mode. If the OK LED remains solid red, contact your Rockwell Automation representative or local distributor. solid green Controller is OK. flashing green The controller is storing or loading a project to or from nonvolatile memory. DriveLogix5730 Controller Specifications A-5 CompactFlash card LED ! ! ATTENTION: The CompactFlash LED is only operational when the drive is energized, and only visible with the drive door open. Servicing energized equipment can be hazardous. Severe injury or death can result from electrical shock, burn or unintended actuation of controlled equipment. Follow Safety related practices of NFPA 70E, ELECTRICAL SAFETY FOR EMPLOYEE WORKPLACES. DO NOT work alone on energized equipment! ATTENTION: Do not remove the CompactFlash card while the controller is reading from or writing to the card, as indicated by a flashing green CF LED. This could corrupt the data on the card or in the controller, as well as corrupt the latest firmware in the controller. Indicator: Color: Description: CF off No activity. flashing green The controller is reading from or writing to the CompactFlash card. flashing red CompactFlash card does not have a valid file system. A-6 DriveLogix5730 Controller Specifications Embedded EtherNet/IP Option LEDs ! ATTENTION: The Embedded EtherNet/IP Option LEDs are only operational when the drive is energized, and only visible with the drive door open. Servicing energized equipment can be hazardous. Severe injury or death can result from electrical shock, burn or unintended actuation of controlled equipment. Follow Safety related practices of NFPA 70E, ELECTRICAL SAFETY FOR EMPLOYEE WORKPLACES. DO NOT work alone on energized equipment! Module Status (MS) Network Status (NS) ahw0864.eps Link Status (LNK) Module Status (MS) indicator Condition: Status: Indicates: Recommended Action: off no power The controller does not have power. Check the controller power supply. flashing green standby The port does not have an IP address and is operating in BOOTP mode. Verify that the BOOTP server is running. solid green OK The port is operating correctly. Normal operation. No action required. DriveLogix5730 Controller Specifications Condition: Status: Indicates: Recommended Action: solid red held in reset The controller is holding the port in reset or the controller is faulted. Clear the controller fault. Replace the controller. self-test The port is performing its power-up self-test. Normal operation during power-up. No action required. major fault An unrecoverable fault has occurred. Cycle power to the controller. Replace the controller. updating firmware The port firmware is being updated. Normal operation during firmware update. No action required. flashing red A-7 Network Status (NS) indicator Condition: Status: Indicates: Recommended Action: off not initialized The port does not have an IP address and is operating in BOOTP mode. Verify that the BOOTP server is running. flashing green no CIP connections established The port has an IP address, but no CIP connections are established. Normal operation if no connections are configured. No action required. If connections are configured, check connection originator for connection error code. solid green CIP connections established The port has an IP address and CIP connections (Class 1 or Class 3) are established. Normal operation. No action required. solid red duplicate IP address The port has detected that the assigned IP address is already in use. Verify that all IP addresses are unique. flashing red/green self-test The port is performing its power-up self-test. Normal operation during powerup. Link Status (LNK) indicator Condition: Status: Indicates: Recommended Action: off no link The port is not connected to a powered Ethernet device. The port cannot communicate on Ethernet. Verify that all Ethernet cables are connected. Verify that Ethernet switch is powered. flashing green self-test The port is performing its power-up self-test. Normal operation during powerup. data transmission and reception The port is communicating on Ethernet. Normal operation. No action required. link OK The port is connected to a powered Ethernet device. The port can communicate on Ethernet. Normal operation. No action required. solid green A-8 DriveLogix5730 Controller Specifications Battery Life Time ON/OFF at 25°C (77°F) at 40°C (104°F) at 60°C (140°F) Always OFF 14 months 12 months 9 months ON 8 hours per day 5 days per week 18 months 15 months 12 months ON 16 hours per day 5 days per week 26 months 22 months 16 months Always ON There is almost no drain on the battery when the controller is always ON. Battery duration after the LED turns on The battery indicator (BAT) warns you when the battery is low. These durations are the amounts of time the battery will retain controller memory from the time the controller is powered down after the LED first turns on. Temperature Duration 60°C 8 days 25°C 25 days Appendix B Access Procedures Removing Power from Drive and Compact I/O ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the +DC & –DC terminals of the Power Terminal Block. The voltage must be zero. ! Remove power before making or breaking cable connections. When you remove or insert a cable connector with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by: • sending an erroneous signal to your system’s field devices, causing unintended machine motion • causing an explosion in a hazardous environment Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance. L1 L2 L3 Task I A B io_bd1.eps C O Description Turn off and lock out input power. Wait five minutes. Verify that there is no voltage at the drive’s input power terminals. Measure the DC bus voltage at the +DC & -DC terminals on the Power Terminal Block. The voltage must be zero. B-2 Access Procedures Opening Door Over Power Structure and Main Control Board ahw0966.eps Frames 1-4 Locate the slot in the upper left corner. Slide the locking tab up and swing the cover open. Special hinges allow cover to move away from drive and lay on top of adjacent drive (if present). Frame 5 Slide the locking tab up, loosen the right-hand cover screw and remove. Frame 6 Loosen 2 screws at bottom of drive cover. Carefully slide bottom cover down & out. Loosen the 2 screws at top of cover and remove. Removing the Control Cassette from Frame 1-6 Size Drives B Task A B B C Description Open the door of the power structure and disconnect the cables that connect to the main board Loosen screws on face of cassette Remove the cassette A 1 BR 2 BR PE L2 DC DC- + U/ V/ T1 W T2 R/L1 /T3 C esd.eps = ahw0752.eps Access Procedures B-3 Removing the Outside Covers Task A B Description Loosen screws on face of front cover and remove the cover Loosen screws on side of rear cover and remove the cover Proper tightening torque for reassembly is 7-10 lb.-in. A ahw0751.eps esd.eps = B Removing the Inside Cover Proper tightening torque for reassembly is 7-10 lb.-in. A = A A ahw0863.eps A Description Loosen screws on face of front cover and remove the cover esd.eps Task Access Procedures Connecting the Battery Allen-Bradley ships the DriveLogix controller with the battery installed, but disconnected. You must connect the battery while installing the drive. ahw0865.eps B-4 Battery Plug and socket Battery clip Storing the Battery ! ATTENTION: Store batteries in a cool, dry environment. We recommend 25° C with 40% to 60% relative humidity. You may store batteries for up to 30 days between -45° to 85° C, such as during transportation. To avoid possible leakage, do not store batteries above 60° C for more than 30 days. Access Procedures B-5 Replacing the Battery ! ! ATTENTION: Servicing energized equipment can be hazardous. Severe injury or death can result from electrical shock, burn or unintended actuation of controlled equipment. Follow Safety related practices of NFPA 70E, ELECTRICAL SAFETY FOR EMPLOYEE WORKPLACES. DO NOT work alone on energized equipment! ATTENTION: The controller uses a lithium battery, which contains potentially dangerous chemicals. Before handling or disposing a battery, review Guidelines for Handling Lithium Batteries, publication AG-5.4. 1. Open the drive door and connect to the appropriate communication port on the controller while the drive and the DriveLogix5730 controller are energized. 2. Upload the controller’s memory and program to a computer with RSLogix 5000 programming software. 3. Remove power from the drive and the DriveLogix5730 controller. Verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the +DC & –DC terminals of the Power Terminal Block. The voltage must be zero. 4. Remove control cassette. 5. Does the existing battery show signs of leakage or damage? If: Then: Yes Before handling the battery, review Guidelines for Handling Lithium Batteries, publication AG-5.4. No Go to the next step. 6. Remove the old battery, by unplugging the battery and opening the clip which secures the battery. 7. Install a new 1769-BA battery, by plugging the battery lead into the socket. ! ATTENTION: Only install a 1769-BA battery. If you install a different battery, you may damage the controller. 8. Attach the battery label. Write on the battery label the date you install the battery. 9. Secure the new battery in the battery clip. 10.Re-install the control cassette. 11.Energize the drive and the DriveLogix5730 controller. B-6 Access Procedures 12.On the front of the controller, is the BATTERY LED off? If: Then: Yes Go to the next step. No A. Check that the battery is correctly connected to the controller. B. If the BATTERY LED remains on, install another 1769-BA battery. C. If the BATTERY LED remains on after you complete Step B., contact your Rockwell Automation representative or local distributor. 13.Download the controller’s memory and program from the computer with RSLogix 5000 programming software. 14.Remove power from the drive and the DriveLogix5730 controller. Verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the +DC & –DC terminals of the Power Terminal Block. The voltage must be zero. 15.Disconnect from the communication port. 16.Re-install the cover(s). 17.Dispose the old battery according to state and local regulations. ! ATTENTION: Do not incinerate or dispose lithium batteries in general trash collection. They may explode or rupture violently. Follow state and local regulations for disposal of these materials. You are legally responsible for hazards created while your battery is being disposed. Access Procedures Installing the Embedded EtherNet/IP Option Board Task A B C D Description Install and tighten standoffs (7-10 lb.-in.) Align connector on Embedded EtherNet/IP Option Board with connector on Main Control Board Place Embedded EtherNet/IP Option Board on the Main Control Board Install and tighten screws (7-10 lb.-in.) B esd.eps = A D ahw0862.eps C A D Installing the DriveLogix5730 Expansion Board Task A B C Description Align connector on DriveLogix5730 Expansion Board with connector on Main Control Board Place DriveLogix5730 Expansion Board on the Main Control Board Install and tighten screws (7-10 lb.-in.) esd.eps = A C ahw0866.eps B C C C B-7 B-8 Access Procedures Installing the Compact I/O Cable Task B C A D A B B C D E Description Remove screws Install clips on controller end of cable Plug controller end of cable into mating connector on the Logix Expansion Board Install and tighten screws (7-10 lb.-in.) Route and secure cable E = esd.eps E Use cable tie to anchor cable to slots on this flange for strain relief E E ahw0741.eps ahw0738.eps A D Access Procedures B-9 Installing the Communications Daughtercard A B C C Description Align circuit board in Communications Daughtercard with rail on Daughtercard slot Insert the Communications Daughtercard C = esd.eps Task Tighten screws (7-10 lb.-in.) A A B ahw0867.eps Important: This procedure can be performed without removing the cassette, if the Logix Expansion Board is already installed. B-10 Notes: Access Procedures Appendix C Application Restrictions Additional Memory Requirements If you have this firmware revision (add all that apply): Revision 15.0 or later may require more memory than previous revisions (e.g., 10.x, 11.x). To estimate the additional memory that your project may require, use the following table: Then add the following memory requirements to your project: Increase per instance Component Which comes from this type of memory: I/O (base) Data and Logic (expansion) 15.x or earlier tag that uses the COORDINATE SYSTEM data type 60 bytes ✔ 13.x or earlier program 12 bytes ✔ task 4 bytes ✔ user-defined data type 4 bytes ✔ I/O module 16 bytes produced or consumed tag Restrictions 8 bytes ✔ ✔ (8 bytes) (8 bytes) ✔ This firmware version has these restrictions: Restriction: Description: Forcing is not supported between the PowerFlex 700S and DriveLogix The forcing values can be set for the controller inputs and outputs. However, these values will not be used by the Logix program nor will they be transmitted to the PowerFlex 700S. Unsupported Motion Commands The following Logix Motion Instructions are not intended for use with DriveLogix and the PowerFlex 700S: Motion State (for 1756-MO2AE Only) • MDO (Motion Direct Drive On) • MDF (Motion Direct Drive Off) Motion Configuration (for tuning SERCOS cards only) • MAAT (Motion Apply Axis Tuning) • MRAT (Motion Run Axis Tuning) • MAHD (Motion Apply Hookup Diagnostics) • MRHD (Motion Run Hookup Diagnostics) Power down banks of local I/O when the controller is powered down. When powering down the controller (the host drive), also power down any banks of local I/O modules. Leaving additional banks of I/O modules powered on may result in major fault code 22 during the power-up process of the controller. C-2 Application Restrictions Restriction: Description: In a Tag of a User-defined Data Type, an Instruction May Write Past the End of an Array. If you write too much data to an array that is within a user-defined data type, some instructions write beyond the array and into other members of the tag. Example 1: Instruction Stops at the End of the Array If the length is greater than the number of elements in the destination array . . . . . . then the instruction stops at the end of the array. Example 2: Instruction Writes Beyond the Array If the length is greater than the number of elements in the destination array . . . . . . then the instruction writes data beyond the end of the array into other members of the tab. Regardless of the length specified for the instruction, it stops writing if it reaches the end of the tag. The following instructions write beyond the array into other members of the tag: BSL BSR COP CPS DDT FBC FFL FFU FLL GSV LFL LFU SQL SRT SSV This restriction also applies to all previous revisions. To prevent writing beyond the limits of the destination array, make sure that the length operand of the instruction is less than or equal to the number of elements in the array. Application Restrictions C-3 When 1769 Compact I/O modules are used as local I/O modules in a Hold Last State and User-Defined Safe State Not DriveLogix5730 system, the local I/O modules do not support the Hold Last State or User-Defined Safe State features, even though you can configure Supported these options in the programming software. • If a local I/O module fails such that its communication to the controller is lost, or if any module is disconnected from the system bus while under power, the controller will go into the fault mode. All outputs turn off when the system bus or any module faults. • RSLogix 5000 software creates tags for modules when you add them to the I/O configuration. The 1769 module tags define configuration (C) data type members which may include attributes for alternate outputs. DriveLogix5730 does not enable local modules to use the alternate outputs. Do not configure the attributes listed below: For digital output modules: For analog output modules: • ProgToFaultEn • CHxProgToFaultEn • ProgMode • CHxProgMode • ProgValue • CHxFaultMode • FaultMode • where CHx = the channel number • FaultValue Any 1769 Compact I/O modules used as remote I/O modules in a DriveLogix5730 system do support the Hold Last State and User-Defined Safe State features. C-4 Notes: Application Restrictions Index Numerics 1769-ADN adapter 8-3 1769-CRL1/-CRL3 cable 3-2 1769-CRR1/-CRR3 cable 3-2 1788-DNBO DeviceNet scanner 8-5 20D-DL2-CL3 cable 3-2 20D-DL2-CR3 cable 3-2 A accessing distributed I/O on ControlNet 7-5 distributed I/O on EtherNetI/P 6-13 I/O data 3-12 Additional Memory Requirements C-1 addresses ControlNet communication to non-Logix controllers 7-12 aliases 3-14 certifications A-2 clock accuracy A-2 communicating master/slave serial methods 5-8 to non-Logix controller over ControlNet 7-11 communication format 2-1, 2-5, 3-8 Motion Control 2-8 Position Control 2-7 Speed Control 2-6 User-Defined 1 2-9 User-Defined 2 2-10 communications driver configuring for serial link 5-5 ControlNet 7-2 EtherNet/IP 6-10 CompactBus configuring 3-5 arrays C-2 CompactFlash 1-4, 1-5 ASCII device 5-11 instructions 5-12 configuring 1769-ADN adapter 8-3 communications driver for serial link 5-5 CompactBus 3-5 controller response to connection failure 3-12 ControlNet daughtercard 7-3 DF1 master 5-9 DF1 point-to-point station 5-6 DF1 slave 5-8 DH-485 port 9-3 drive 2-3 EtherNet/IP communications driver 6-10 generic 1769-MODULE 3-17 local I/O 3-7 network parameters with BOOTP/DHCP 6-3 network parameters with RSLinx 6-6 network parameters with RSLogix 5000 6-7 remote connection via serial link 5-7 system for ControlNet 7-1 system for DH-485 9-2 system for serial link 5-1 the serial port 5-3 AutoFlash 1-4 B battery connecting B-4 disposing B-6 LED A-4 life A-8 replacing B-5 specification A-1 storing B-4 BOOTP/DHCP configuring network parameters 6-3 C cable 1769-CRL1/-CRL3 3-3 20D-DL2-CL3 3-2 20D-DL2-CR3 3-2 Belden 3106 9-7 Belden 9842 9-7 Compact I/O A-1 installing Compact I/O B-8 serial A-1 connecting ASCII device 5-11 battery B-4 Index-2 connection failure configuring controller response to 3-12 ControlFlash 1-3 ControlNet accessing distributed I/O 7-5 communicating to non-Logix controllers 7-11 configuring communications driver 7-2 configuring system for 7-1 consuming tags 7-16 daughtercard 7-3 I/O 7-4 mapping addresses communication to non-Logix controllers 7-12 messages 7-9 producing and consuming data 7-14, 7-20, 7-23 producing tags 7-16 scheduling network 7-7 D daughtercard ControlNet 7-3 installing B-9 De-energizing the Drive 1-2, 2-1, 3-1, 4-1, 5-1, 6-1, 7-1, 8-1, 9-1, B-1 DeviceNet 1769-ADN adapter 8-3 1788-DNBO DeviceNet scanner 8-5 I/O 8-2 DF1 master 5-9 point-to-point station 5-6 slave 5-8 DH-485 Belden 3106 cable 9-7 Belden 9842 cable 9-7 browsing 9-9 configuring port 9-3 configuring system for 9-2 configuring the port 9-3 grounding 9-8 installing network 9-6 network initialization 9-5 network planning 9-4 nodes 9-5 terminating 9-8 token rotation 9-4 DriveExecutive 2-12 E Email using an EtherNet/IP msg 6-24 EtherNet/IP accessing distributed I/O 6-13 configuring communications driver 6-10 configuring network settings with BOOTP/DHCP 6-3 configuring network settings with RSLinx 6-6 configuring network settings with RSLogix 5000 6-7 consuming tags 6-18 controller connections 6-11 controller to controller communication 6-31 determining network settings 6-2 distributed I/O 6-12, 6-31 Email 6-24 messages 6-19 producing and consuming data 6-15 producing tags 6-17 specifications A-1 F fault data 3-15 firmware loading 1-2 loading with AutoFlash 1-4 loading with CompactFlash 1-4 loading with ControlFlash 1-3 forcing values C-1 G Grounding DH-485 network 9-8 H Hold Last State and User-Defined Safe State Not Supported C-3 Index-3 I I/O accessing data 3-12 accessing distributed on ControlNet 7-5 accessing distributed on EtherNet/IP 6-13 configuring local 3-7 ControlNet 7-4 DeviceNet 8-2 direct connections 3-14 distributed over EtherNet/I/P 6-12, 6-31 end-cap detections 3-15 generic 1769-MODULE 3-17 hold last state 3-8 inhibiting 3-9 layout 3-3 max modules A-1 max number banks A-1 module faults 3-15 monitoring 3-15 placing 3-2 update 3-4 user-defined safe state 3-8 inhibiting I/O 3-9 the drive connection 2-11 installing Compact I/O cable B-8 daughtercard B-9 DH-485 network 9-6 DriveLogix5730 Expansion Board B-7 Embedded EtherNet/IP Option B-7 new battery B-5 K keying 2-4 L loading firmware 1-2 firmware with AutoFlash 1-4 firmware with CompactFlash 1-4 firmware with ControlFlash 1-3 M mapping 7-12 addresses EtherNet/IP communication to non-Logix controllers 6-22 Motion Control communication format 2-8 Position Control communication format 2-7 Speed Control communication format 2-6 User-Defined 1 communication format 2-9 User-Defined 2 communication format 2-10 master/slave communication methods 5-8 memory specifications A-1 messages ControlNet 7-9 EtherNet/IP 6-19 Motion Control communication format 2-8 N network settings EtherNet/IP 6-2 P placing drive 2-3 I/O 3-2 Position Control communication format 2-7 Powering Down 1-2, 2-1, 3-1, 4-1, 5-1, 6-1, 7-1, 8-1, 9-1, B-1 producing and consuming data ControlNet 7-14, 7-20, 7-23 EtherNet/IP 6-15 programming ASCII instructions 5-12 programs defining 1-8 developing 1-6 local I/O C-1 R remote connection serial link 5-7 Index-4 replacing battery B-5 routines defining 1-9 RPI 3-4, 3-6 RS-232 5-1 RSLinx configuring EtherNet/IP network parameters 6-6 RSLogix 5000 configuring network parameters 6-7 S scheduling ControlNet 7-7 serial link ASCII device 5-11 configuring communications driver 5-5 configuring serial port 5-3 configuring system for 5-1 DF1 point-to-point station 5-6 master 5-9 master station 5-9 master/slave 5-8 remote connection 5-7 slave 5-8 specifications A-1 specifications A-1 electrical A-1 environmental A-1 EtherNet/IP A-1 memory A-1 serial port A-1 Speed Control communication format 2-6 system overhead percentage 1-9 T tags aliases 3-14 consuming ControlNet 7-16 consuming EtherNet/IP 6-18 producing ControlNet 7-16 producing EtherNet/IP 6-17 tasks defining 1-6 task priorities 1-7 Turning Drive Off 1-2, 2-1, 3-1, 4-1, 5-1, 6-1, 7-1, 8-1, 9-1, B-1 U Unsupported Motion Commands C-1 User-Defined 1 communication format 2-9 User-Defined 2 communication format 2-10 user-defined data types C-2 V virtual backplane 1-12 www.rockwellautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication 20D-UM003B-EN-P – January 2006 Supersedes 20D-UM003A-EN-P – July 2004 Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in USA. Allen-Bradley DriveLogix 5730 Controller User Manual