Download Normafluor DNF7

Transcript
Normafluor
DNF7-DNF7S
7
Operation (contd.)
7.3 Closing operation of the earthing
switch
■■ Insert the lever in the vertical position, handleat the bottom.
■■ Using your left hand, push the unlocking lever down.
■■ Using your right hand, hold the lever by the handle and push it up to the left.
■■ Release the unlocking lever, which remains in the same position.
■■ Hold the lever using both your hands in order to finish the closing
operation of the earthing switch.
■■ At the end of the operation, the unlocking lever returns its original position.
■■ The earthing switch is closed.
■■ Check its physical position through both inspection windows of the rear
panel.
7.4 Plugging-in and unplugging operations
of the circuit breaker
■■ Instruction plate at the front of the circuit breaker.
7.5 Unplugging operation of the circuit
breaker up to the "test" position
■■ Open the door of the circuit breaker compartment.
■■ Make sure the circuit breaker is released.
■■ Insert the operating lever in the operation position on the right.
AMTNoT013-02
29