Section 6: Specifications 6.3 Electrical Interface 6.3.1 Inputs Figure 6-2 Opto-Isolated Inputs Parameter Symbol Min. Input voltage range Vmax 0 Isolation voltage Viso 1000 ON voltage level VH 3 OFF voltage level VL Min. ON time tmin Pull-up current IPU Norm. Max. Unit 30 V V 30 V 1 V 1 ms 10 mA 6.3.2 Outputs Relay Outputs Only Qualified Electricians should connect primary voltages. Figure 6-3 Relay Outputs Parameter Small relay contact ratings (continuous A) Small relay contact ratings Large relay contact ratings (continuous A) Large relay contact ratings (resistive) Wire size accepted - Clip terminals Christie ACT User Manual 020-100129-05 Rev. 1 (02-2010) Pin 1 to 12 13 & 14 Symbol ICMax VCMax ICMax VCMax Gauge Min. 0.1 Nom. - 28 - Max. 1 220 8 240 16 Unit A V DC A V AC AWG 6-3