Download WINDY BOY 2500 / 3000
Transcript
SMA Solar Technology AG Electrical Connection 5.2.2 Connecting to the Public Grid (AC) Overview of the AC connection socket Object A B C D E F Description Socket element Threaded sleeve Sealing ring PG13.5 Fastening case PG13.5 Pressure screw for PG13.5 (for a cable diameter between 9 mm … 13.5 mm) Cable gland PG16 (for a cable diameter between 13.5 and 17 mm) Procedure 1. Choose an appropriate screw fitting for the AC cable. 2. Check that the grid voltage is within the admissible voltage range. The exact operating range of the inverter is specified in the operating parameters. The corresponding document is available in the download area at www.SMA.de/en in the category "Technical Description" of the respective inverter. 3. Disconnect the line circuit breaker and secure against re-connection. 4. Strip approx. 30 mm from the AC cable. 5. Shorten L and N by 5 mm. 6. Strip 4 to 5 mm of insulation from the AC cable. 7. Lead the pressure screw and/or cable gland and threaded sleeve over the AC cable. Installation Guide WB25_30-IEN101030 21