Download ControlLogix Redundancy System
Transcript
Appendix C Attributes of the Redundancy Object Use the redundancy object to learn about the status of your redundancy system. For this information Get this attribute Data type GSV/SSV Description Redundancy status of the entire chassis ChassisRedundancy State INT GSV If Then 16#1 Power up or undetermined 16#2 Primary with synchronized secondary 16#3 Primary with disqualified secondary 16#4 Primary with no secondary If Then 16#8 Synchronized secondary 16#9 Disqualified secondary with primary 16#E No partner If Then 16#1 Power up or undetermined 16#2 Primary with synchronized secondary 16#3 Primary with disqualified secondary 16#4 Primary with no secondary 16#6 Primary with synchronizing secondary If Then 16#7 Synchronizing secondary 16#8 Synchronized secondary 16#9 Disqualified secondary with primary 16#E No partner If Then 0 Undetermined 1 No compatible partner 2 Fully compatible partner Redundancy state of the partner chassis Redundancy status of the controller Redundancy state of the partner Results of the compatibility checks with the partner controller 171 PartnerChassis RedundancyState ModuleRedundancy State PartnerModule RedundancyState INT INT INT CompatibilityResults INT GSV GSV GSV GSV Publication 1756-UM523F-EN-P - September 2006